PEC 8 Flashcards
Connection or fittings shall NOT connect grounding electrode conductors to equipment by means of ______
solder.
Each length of non-metallic conduit shall be clearly and durably marked at least every ________(mm) as required.
3,000 mm
Doors leading into a transformer vault shall be kept locked and access allowed only to ___________.
qualified person
Resistors and reactors shall NOT be installed in close proximity to combustible materials such that it constitutes a fire hazard. What is the minimum clearance that is required by the Code? (mm)
Ans. 300 mm
The grounded conductor shall be equal to the largest phase conductor.
6. Completely enclosed, ventilated transformers equipped with an 80C rise insulation may be installed in a room of ______________
fire resistant construction
In a switchboard there shall be an air space of at least _______(mm) between the energized metal part and the door of the cabinet.
25 mm
. Electrical metallic tubing shall be securely fastened in place within _____(mm) of each outlet box, junction box, cabinet or fitting.
900 mm
Lead-in antenna conductors for television or radio equipment shall be securely ________(2) to antennas.
attached & fastened
Lighting fixtures approved for damp locations shall be installed only in ________.
damp locations
What is the metric size equivalent of 1,000 MCM? (mm2)
Ans. 500 mm2
Antenna conductors for television equipment shall be installed so they will not ____ under open electric light or power conductors where possible
cross
For churches, the general lighting load shall be computed at ____VA/m2.
8VA/m2
The following are common splicing rules EXCEPT one. Which one is this? (April 2016)
Wires of the same size should be spliced together in line
. Electric discharge lighting shall be connected by flexible cord if the cord is visible for ____% of its entire length.
100%
What is the latest edition of the PEC, Part 2?
Ans. 1988
is all circuit conductors between the service equipment or the generator switchboard of an isolate plant, and the final branch circuit over-current device.
Feeder
is a disruptive discharge through insulation.
Breakdown
Insulators used to support wires under cross arms are________ .
suspension
______________ is a pliable corrugated raceway of circular cross-section with integral or associated couplings, connectors and fittings for the installation of electric conductors.
Electrical non-metallic tubing
. The scope of the PEC covers all electrical conductors including optical fiber cable and equipment installed within or to or from any of the following premises, which one is NOT included?
Aircraft
Motor vehicles
Railway rolling stocks
All of these
All of these
The maximum size of liquid tight flexible metal conduit shall be ________(mm) trade size.
100 mm
Transformers that are installed in unsupervised locations and rated over 600 V are protected by fuses on the primary side and cannot exceed _____% of the primary full load current.
300%
Each length of intermediate metal conduit shall be clearly and durably identified at ______(mm) intervals with the letters “_____”.
760 mm
IMC
. What is the maximum rating of a molded case circuit breaker to protect a 10 hp squirrel cage induction motor rated at 230 volts, 3-phase, 60 Hz with a full load rating of 28 A? (A)
Ans. 70 A
Size = 250% of FLA = 2.5(28) = 70 A
Conductors used only for grounding shall be________(3) . (April 2016)
green, green with yellow stripes, or bare
The grounded conductor shall be equal to the largest _____ conductor.
phase
Screw type lamp holders shall have the _______conductor connected to the screw shell. (April 2016)
grounded
is the ratio of the maximum demand of a system or part of a system to the total connected load of a system or the part of the system under consideration.
Demand factor
Electrical non-metallic tubing smaller than ______(mm) (outside diameter) electrical trade size shall NOT be used.
20 mm
Fixture studs in octagonal boxes used to mount lighting fixtures are computed on the ______conductor entering the box.
biggest
Type NM (non-metallic sheathed cable) shall be permitted for__________(2) work in normally dry locations.
exposed & concealed
Transformers rated over ____V and installed in supervised locations are protected by circuit breakers on the primary side and cannot exceed ____ % of the primary full load current.
600 V
600%
. The unit lighting for a dwelling unit expressed in watts per square meter shall be _____w .
24 watts
A ______(2) (A) branch circuit shall be permitted to supply lighting units, other than utilization equipment or a combination of both.
15 A or 20 A
Type FCC cable shall be clearly and durably marked on both sides at intervals of NOT more than _______(mm)
600 mm
The starting winding of an induction motor is wound _______of the main winding.
on top
Outlet boxes are not required to have blank covers to prevent the escape of _______(2).
arcs and sparks
is a single or multi-conductor solid dielectric insulated cable rated 2,001 volts or higher.
Type MV
Intermediate metal conduit shall be permitted to be installed in or under cinder fill where subject to permanent moisture when protected on all sides by a layer of non-cinder concrete NOT less than______(mm) thick.
50 mm
is a factory assembly of one or more conductors, each individually insulated and enclosed in a metallic sheath of interlocking tape of a smooth or corrugated tube.
Type MC Cable