Where flexible tubing is used to encase the conductors, the tubing shall extend from the last insulating support to NOT less than _____(mm).
6.4 mm
Metal raceways, enclosures, frames and other non-current carrying metal parts of electric equipment shall be kept at least ______(mm) distance from lightning rod conductors.
1,900 mm
Where no standard electrical equipment of the exact size or rating is available and the next larger size is neither available the next smaller size or rating maybe used provided a special permission is obtained from ___________
Electrical Inspector
Instruments, pilot lights, potential transformers and other switchboard devices with potential coils shall be supplied by a circuit that is protected by a standard over-current device rated up to ___(A)
15 A
___ is a wire or other mechanical member having one end secures and the other end fastened to a pole maintained under tension
Guy (Guy wire)
Below the factors that affect the ampacity of an electrical conductor EXCEPT one. Which one is this?
Insulation resistance
Length of the conductor
Conductor material
Cross-sectional area of the conductor
Insulation resistance
For circuits over 600 V nominal, conductors shall NOT be bent to a radius less than ____ the diameter for shielded or lead covered conductors.
12 times
Which of the following statement about over-current devices is NOT correct?
It shall be located where they will not be exposed to physical damage.
It shall be readily accessible.
It can be located inside clothes closets.
In a multi-family dwelling, each occupant shall have ready access to over-current device protecting his occupancy.
It can be located inside clothes closets.
Which of the following statements is NOT true?
Conductors in raceways shall be continuous between outlets.
Metal raceways, boxes, cabinets and fittings shall be grounded.
Metal or non-metallic raceways shall be continuous between cabinets, boxes or other enclosures.
Raceway shall be used as a means of support for other raceways.
Raceway shall be used as a means of support for other raceways.
For receptacle outlets, each single or each multiple receptacle on one strap shall be considered NOT less than ____(VA).
180 VA
Corner joints on a gutter shall be made tight, where the assembly is held together by rivets or bolts. The spacing shall NOT be more than _____(mm).
NOT be more than 300 mm
is the total number of mechanical degrees that a PVC conduit run maybe bent between pull joints (pull boxes, junction boxes or utility boxes).
360 degrees
The minimum size of wire used in electrical wiring is the former #14 AWG. Under the SI standard in the PEC, what is the diameter of this wire?
(1.2 mm, 2.0 mm, 1.5 mm, 1.6 mm).
1.6 mm
is a box with a blank cover which is inserted in one or more runs of raceway to facilitate pulling of the conductors.
Pull box
The neutral conductor from the neutral point of the transformer or generator to its connection point to the grounding impedance shall be __________ .
shall be fully insulated
The sum of the cross sectional area of all conductors in a wireway must _______% of the cross-sectional area of the wireway.
NOT exceed 20%
. Circuit containing electric discharge lighting transformer exclusively shall NOT be rated in excess of ___(A).
30 A
For ranges of 8.75 kW or more in rating, the minimum branch circuit required shall be ___(A)
40 A
Lighting fixtures shall be wired with a fixture flexible cord with a cross-sectional area of NOT less than _______(mm2)
0.75 mm2.
If the setting of over-current device in a circuit ahead of equipment is 60 A, the minimum required grounding conductor using copper is______(mm2).
5.5 mm2
Mineral insulated metal sheathed cable shall be permitted in any of the following installations EXCEPT one. Which one is this? For control circuits Where exposed to oil and gasoline For feeder circuits Where exposed to corrosive atmosphere
Where exposed to corrosive atmosphere
Conductors which run above the top level of a window shall be permitted to be less than 1,000 mm but in no case shall be less than ____(mm).
300 mm
For barber shops and beauty parlors, the general lighting load per square meter of area shall be _____W
24 watts.
Liquidtight flexible non-metallic conduit shall be permitted to be used:
for direct burial, where flexibility is required, in exposed or concealed locations
Flexible metal conduits must NOT be used in :
wet locations, hoistways, and storage battery rooms.
For 25 to 50 A circuits, the minimum insulation resistance is (ohms) .
250,000 ohms
____C is the maximum operating temperature of type THWN conductor.
75C
is a conductor encircling a building and interconnecting all ground terminals.
Counterpoise
The conductor connecting the neutral point of the transformer or generator to the grounding impedance .
shall be permitted to be installed in a separate raceway
The total load on over-current device located in a panel board shall NOT exceed to ___% of its rating.
80%
For underground feeder and branch circuits, ____ of conductors shall be used.
UF type
an insulating element, generally of elongated form with transverse holes or slots for the purpose of insulating two sections of a guy or provide insulation between structure and anchor.
Guy insulator
__(A) is the ampacity of a 5.5 mm2 TW copper conductor.
30 A
A two wire DC system supplying premises wiring shall be grounded EXCEPT,
A system equipped with ground detector and supplying only industrial equipment in limited areas.
A system operating at 50 V or less between conductors.
A rectifier device DC system supplied from an AC system.
All of these
All of these
__________ – hazardous location in which ignitable concentrations of flammable gases or vapors can exist under normal operating conditions.
37. Switches are operated vertically rather than horizontally. The upward position of the handle shall mean switch-on position.
Class I, Division 1
The use of surface non-metal raceway is NOT permitted in all those mentioned below EXCEPT one. Which one is this?
Dry locations
Where subject to severe physical damage
Where the voltage is over 300 V
Where concealed
Dry locations
The branch circuit rating shall NOT be less than ____ of the non-continuous load.
100% of the non-continuous load.
For installation consisting of not more than two 2-wire branch circuits, the service disconnecting mains shall be rated NOT less than ___(A).
30 A
What is the lowest dielectric strength of transformer oil, which is acceptable to the PEC? (V)
Ans. 25,000 volts
Switches are operated vertically rather than horizontally. The upward position of the handle shall mean
switch-on position.
Wireways shall be supported at intervals NOT to exceed ________(mm).
1,500 mm
For a dwelling unit having a floor area NOT more than 50 square meters shall be permitted to have a single 20-A, 2-wire branch circuit provided the total load shall NOT exceed ______(VA)
3,680 VA
For show window lighting, a load of NOT less than ______(VA) shall be included for each liners meter of show window.
600 VA
The maximum setting of the ground fault protection of equipment shall be ______(A).
1,200 A
______ is a grounded metal enclosure containing a factory mounted, bare or insulated conductors, which are usually copper, or aluminum bars, rods or tubes.
Busway
Flat Conductor Cable (FCC) system shall NOT be used in the locations enumerated below EXCEPT one. Which one is this?
Locations where subject to corrosive vapors
Damp locations
Residential buildings
Outdoors
Damp locations
Type MI cables shall be securely supported at intervals NOT exceeding _____(mm).
1,800 mm
The grounding impedance for neutral system shall be installed between the _____________ and __________
the grounding electrode and system neutral.
In any watercraft, receptacle outlets operating at ___V or more ____________.
50 V
shall have a grounding pole
Space heating cables shall be secured at intervals NOT exceeding ______(mm).
200 mm
A run conduit between outlets, between fittings, between outlet and fitting shall NOT contain more than the equivalent of ___________ .
4 quarterbends
is a general term covering an assembly or assemblies of devices for the interruption, control and metering of electric power
Switchgear
Thermoplastic insulated fixture wires shall be _____ on the surface at intervals NOT exceeding ____.
durably marked
600 mm
The average distance between down conductors in a lightning protection system shall NOT exceed _____m
30 m
Type AC cable shall NOT be permitted to be used:
In storage battery
On cranes or hoists
In motion pictures
is a single conductor or multi-conductor assembly provided with or without an overall covering, primarily used for services.
Service entrance cable
Fixture wires shall NOT be smaller than _______ (mm2).
0.75 mm2
Standard ___________ shall NOT be used as a bond for the service entrance raceway.
locknuts and bushings
Transformers that contain liquid that will burn shall be installed only in approved vaults and shall also comply with the following conditions EXCEPT one. Which one is this?
Ample ventilation shall be provided for the continuous removal of flammable gases.
Vent openings shall lead to a safe location outside the building.
All vent ducts and openings shall be of sufficient areas to reliable explosion pressures within the vault.
There shall be robust door between the vault and any non-hazardous location.
There shall be robust door between the vault and any non-hazardous location.
Flat cable assemblies shall have conductors of ____ (mm2)special stranded copper wires.
5.5 mm2
is a short length of a conductor used to make a connection between terminals or around a break in a circuit.
Jumper
The surface non-metallic raceway may NOT be used in the following locations EXCEPT one. Which one is this?
In dry locations
Where concealed
Where subject to severe physical damage
In hoistways
In dry locations
For bare metal parts, busbars, etc of opposite polarity held free in air shall maintain a minimum spacing of ______(mm) for voltages rated NOT over _____v.
19 mm
250 V
Type IGS cable is using a dry kraft paper tape and an SF6 gas. What do you mean by SF6?
Ans. Sulfur hexafluoride
_____________ do NOT allow the installation of PVC rigid conduits
Hazardous locations
Flat cable assemblies shall NOT be installed:
In hoistways
In any hazardous locations
Outdoors
Ground connections shall be made at approximately every other steel column around the perimeter of the building and shall NOT be more than ______m.
18 m apart
For school buildings, the general lighting load is ___________(VA/m2).
24 VA per square meters
is fabricated assembly of insulated conductors in a flexible metallic enclosure
Type AC
_____ and _____ in messenger wire shall be made by approved methods.
Splices and taps
A storage battery supplying emergency lighting and power shall maintain NOT less than ____% of full voltage at total load for a period of at least ___ hours.
- 5%
1. 5
is an appliance which can easily be moved from one place to another in normal use.
Portable appliance
The feeder demand factor for three kitchen equipment other than dwelling kitchen equipment shall be ___% .
90%
To provide for small appliance load in a dwelling unit, the feeder should be computed at _______w.
1,500 watts
The nearest ground terminal shall be NOT less than _____ (mm) from the foundation wall
600 mm
is the circuit conductors between the service entrance equipment or isolated generating plant and the branch circuit overload device or devices
Feeder
Conductors shall be securely attached to the buildings using fasteners. Fasteners shall be spaced NOT more than ______(mm).
900 mm
The minimum diameter of air terminal used at the top of a heavy duty smoke or vent stacks shall be ____(mm), exclusive of the corrosion protection.
15 mm
_____ are used on conduits and are located inside and outside of the box. (April 2016)
Locknuts
No parts of cord connected fixtures, hanging fixtures or pendants shall be located within a zone measured ______(mm) horizontally from a bathtub rim.
900 mm
Busbars shall be copper having a minimum conductivity of ____.%
97%
___C is the temperature rating of THW insulation.
75C
Individual open conductors and cables other than service entrance cables shall NOT be installed within ________ (mm) of every grade level.
3,100 mm
An insulated grounded conductor of _____(mm2) or smaller shall be identified by a continuous ____________ outlet finish along its entire length.
14 mm2
white or naturally gray
Messenger supported wiring is permitted only in ______________ where maintenance personnel service the system.
industrial establishments
In damp or wet locations, boxes and fittings should be properly placed or insulated to
prevent water from entering the box or fitting. (April 2016)
Equipment having an open circuit voltage exceeding ____(V) shall NOT be installed in dwelling occupancies.
300 V
Concealed knob and tube wiring conductors shall be rigidly supported on knobs NOT more than ______(mm) of minimum distance apart.
1,300 mm
are used to support the conductor in the open wiring method
Split knobs
The minimum size of type IGS cable shall be _____(mm2).
125 mm2
Watercraft’s switchboards shall be provided with a clear working space of at least ______(mm) at the front.
1,000 mm
For grounding electrode to which portable or mobile equipment system neutral impedance is connected, shall be isolated from the ground by at least _______(mm) from any other system or equipment grounding electrode.
6,000 mm
______ metal is the best conductor of electricity.
Copper
Incandescent lamp fixtures shall be marked to indicate the allowable wattage of lamps. The markings shall be permanently installed in letters at least _____(mm) high.
6.4 mm
If the duty cycle of a motor-generator arc welder is 100%, the supply conductors shall NOT be less than ____% of its rated primary nameplate current.
100%
Most wires used in residential house wiring are usually insulated by __________.
thermoplastic
Open wiring on insulators shall be permitted for wiring systems of ______V or less.
600 V
Stage equipment like footlights, border lights and others shall be so arranged that no branch circuit supplying such equipment will carry a load exceeding ____(A).
20 A
Metal poles ___________ to be used to support _________ and ______________
shall be permitted
lighting fixture
enclosed supply conductors
____________ raceway method is NOT allowed to be used in a hazardous location.
Rigid non-metallic conduit
_________ of any pull box shall be removable.
1 or more sides
Dimmers installed in ungrounded conductors shall be protected by OCPD NOT exceeding ____% of their rating.
125%
Mobile home service equipment shall be rated NOT less than _____(A).
100 A
The branch circuit conductors that supply one or more units of data processing systems shall have an ampacity NOT less than _____ %of the total connected load.
125%
______ – locations which are hazardous because of the presence of easily ignitable fibers of flyings.
Class III
Where nails or screws are used to mount knobs, they shall be of a length sufficient to penetrate the wood to a depth equal to at least ______ the height of the knob.
1/2
Explosion hazards exist due to the presence of the following material EXCEPT one. Which one is this?
Combustible dust
Flammable vapors
Flammable liquids
Carbon dioxide gas
Carbon dioxide gas
Metal clad cables shall be supported and secured at intervals NOT exceeding ________(mm).
1,800 mm
The ampacities of type UF (underground feeder) cable shall be that of the _____C conductors.
60C
Some of the principal factors that affect the operating temperature of a cable are the following EXCEPT one. Which one is this?
Voltage
Ambient temperature
Ventilation
Load current
Ventilation
Communication wires and cables shall have a voltage rating of NOT less than _____V.
300 V
Self-excited generators supplying power to organs shall have a potential of NOT more than ____V.
15 V
_____C is the temperature rating of THHN insulation.
90C
All ___________ and ______________ with autotransformer starting shall have an over-current protective device using inverse time circuit breaker with a maximum setting of _____% of its full load current rating.
AC squirrel cage motors
synchronous motors
200%
Rosettes for use with conduit boxes or raceway shall have bases high enough to keep wire and terminals at least ______(mm) from the surface wired over.
10 mm
No motor circuit in any watercraft shall have conductors less than ______.(mm2)
2.0 mm2
Sizes of building wires manufactured in the Philippines are standardized in square millimeters. What is the area of copper conductor, which is next larger than 8 mm2?
Ans. 14 mm2
Flexible cords or data processing cables used to connect computer units ___________ as part of the system.
shall be approved
Branch circuits to receptacles under raised floors in computer rooms shall be wired with:
EMT, IMC, and AC cable.
EMT, IMC, and AC cable.
As to the general rule, floating buildings shall be supplied by ____ of feeder conductors from their service equipment.
1 set
Which of the following electric wires has the highest ampacity?
(5.5 mm2, 8.0 mm2, 30 mm2, 50 mm2)
50 mm2
Indoor antennas and indoor lead-in conductors shall NOT be run nearer than _____ (mm) to conductors of other wiring systems in the premises.
50 mm
The ampacity of the neutral conductor of a dual voltage feeder shall be ____ of the ampacity of the ____________
100%
ungrounded conductors.
According to the PEC, the minimum insulation level for neutral conductors of residential installations, which have solidly grounded system, shall NOT be less than _____V.
300 V
Exit lights on watercrafts shall be provided at each point. The word “EXIT” shall be red letters NOT less than _____(mm) high.
50 mm
The nominal voltage used in elevator, dumbwaiter, escalator and moving walk driving machine motors, machine brakes and motor-generator sets shall NOT exceed_______V.
600 V
is a cable made-up of electric conductors which provides electrical connection between an elevator or dumbwaiter car and fixed outlet in the hoistway.
Traveling cable
is the minimum weight of a fixture that requires a support that is independent of the outlet box.
23 kg
For single phase AC or DC motors supplied by a two wire, single phase AC or DC with one conductor grounded. How many overload units shall be required?
Ans. (1) in the ungrounded conductor (April 2016)
is the insulation resistance acceptable by the PEC for 600-V circuits consisting of 2.0 mm2 conductor.
500,000 ohms
Each patient bed location shall be provided with a minimum of _________
4 receptacles.
Open conductors on insulators shall be separated at least ______ from metal raceways, piping or other conducting materials.
50 mm
The nominal gas pressure used in type IGS cable shall be ______ Kpa.
138 kPa
___(mm) is the smallest size of EMT (electrical metallic tubing). (April 2016)
15 mm
The use of non-metallic raceway shall be permitted in _____________.
dry locations only
Metal clad cables shall be permitted for installations in the following locations EXCEPT one. Which one is this? (April 2016)
Signal circuits
Branch circuits
Direct burial in the earth
Aerial cable
Direct burial in the earth
One set of service entrance conductors shall be permitted to supply more than ____ of service equipment.
1 set
__________________ is known in the field as PVC.
Rigid non-metallic conduit
Concealed knob and tube wiring shall be supported within _____(mm) of each side of each tap or splice.
150 mm
A 15-A or a 20-A branch circuit shall be permitted to supply lighting units and other utilization devices. The rating of any one cord and plug connected appliance shall NOT exceed ____ % of the branch circuit rating.
80%
Receptacles located on stages in theaters shall NOT exceed ____% of their ratings for continuous duty loads.
80%
Lighting fixtures exposed to cleansing water in agricultural buildings shall be _________.
watertight
is a metal raceway of circular cross section with integral or associated couplings, connectors and fittings approved for the installation of electrical conductors.
Intermediate metal conduit
Rigid metal conduit and intermediate metal conduit when used underground shall have a minimum burial of _____.
150 mm
Storage batteries used, as source of power for emergency system shall maintain a voltage applied to the load without falling below _____ % of normal value.
87.5%
Driven rods maybe used as a grounding electrode provided the driven depth shall NOT be less than ________(mm).
2,450 mm
is an enclosed channel designed expressly for holding wires, cables or busbars with additional functions as permitted
Raceway
The bonding conductor used in agricultural buildings shall be copper, insulated, covered or bare, NOT smaller than ________(mm2)`.
8.0mm2
In any watercraft, the motor circuit shall have an ampacity of NOT less than ___% of the motor’s full load current rating
100%
is an enclosed channel designed expressly for holding wires, cables or busbars with additional functions as permitted.
Raceway
.
.