Part 3 Flashcards
Is the following statement True or False?
The electrical work supervisor is responsible for ensuring that the electrical work is
performed in accordance with 1135/2016.
Correct.
The electrical work supervisor is responsible for ensuring that the electrical work is performed in
accordance with 1135/2016.
STL 1135/2016 59§
Is the following statement True or False?
If an operator fails to observe the Electrical Safety Act or the provisions or regulations
issued under it the Electrical Safety Authority shall request the operator to correct the
inadequacy within a specified time.
Correct.
If an operator fails to observe this Act or the provisions or regulations issued under it the Electrical
Safety Authority shall request the operator to correct the inadequacy within a specified time.
[STL 1135/2016 95§]
Is the following statement True or False?
Electrical qualification 3 entitles you to work as electrical work supervisor in the work of
replacing a supply cable and a final panelboard for an apartment?
Wrong.
STL (1135/2016) 69§:
“The holder of electrical qualification 3 may work as an electrical work supervisor in repairs of electrical
equipment intended to be connected with an AC network not exceeding 1,000 V or a DC network not
exceeding 1,500 V.
Replacing a single component of electrical installations and the installation of a single feeder line of
electrical equipment or set of electrical equipment intended to be repaired or connected to the network as
new from the installation box or the building distribution board without any structural changes to the
distribution board is considered repair work.”
The task of the electrical work supervisor is to ensure that the persons performing
electrical installation work are professional and adequately instructed in their tasks. A
person who has been instructed and instructed in the repair of electrical equipment
independently is considered to be sufficiently professional to perform and supervise the
repair of electrical equipment independently.
Is the following statement Correct or Wrong?
suitable vocational upper secondary qualification or a similar qualification obtained before that and
one year’s work experience in electrical work in electrical work on similar type of electrical equipment.
Correct.
STL (1135/2016) 73 § 4)
The task of the electrical work supervisor is to ensure that the persons performing
electrical installation work are professional and adequately instructed in their tasks. A
person who has been instructed and instructed in the repair of electrical equipment
independently is considered to be sufficiently professional to perform and supervise the
repair of electrical equipment independently.
Is the following statement Correct or Wrong?
suitable vocational upper secondary qualification and six year’s work experience in electrical work
Correct
STL (1135/2016) 73 § 4
The task of the electrical work supervisor is to ensure that the persons performing
electrical installation work are professional and adequately instructed in their tasks. A
person who has been instructed and instructed in the repair of electrical equipment
independently is considered to be sufficiently professional to perform and supervise the
repair of electrical equipment independently.
Is the following statement Correct or Wrong?
suitable vocational upper secondary qualification, further vocational qualification, specialist vocational
qualification and three months’ work experience in electrical work.
Wrong.
STL (1135/2016) 73 § 3)
Is the following statement Correct or Wrong?
The qualifications of the electrical work supervisor is assessed by a qualification
assessment body, which also issues them with a qualification certificate.
Correct.
STL1135/2016 § 65:
“The qualifications of the electrical work supervisor and the supervisor of
operations is assessed by a qualification assessment body, which also issues them with a qualification
certificate.“
Is the following statement Correct or Wrong?
Tukes (Finnish Safety and Chemicals Agency) has been notified of the activities before
the start of the electrical work.
Correct
(STL1135/2016 § 55 4) Tukes is the Electrical Safety Authority in Finland
Choose the correct option(s):
The absence of operating voltage shall be verified
a) by using of a double pole voltage detector (proved to be working before measurement) to verify
the dead condition of all phase-, neutral- and central point conductors.
b) by using an universal instrument to measure between the phases inside the working location
c) by the position indication of the locked disconnection device
SFS 6002/6.2.4.1 -> a) is correct
The nominated person in charge of the electrical work must be present at the place of
work, except in the case of short-term absences such as annual leave.
Correct or incorrect?
Incorrect.
SFS 6002 Appendix X.6:
If a person in charge of the electrical work is not required, the worker shall himself control the electrical
safety during work.”
Gov Decree on Electrical Work and Operational Work of Electrical Installations (1435/2016):
“If an electrical work supervisor is not required for electrical work, electricians shall supervise electrical
safety themselves while performing the work.”
What is the correct way to carry out earthing and short-circuiting with portable earthing devices?
SFS 6002 6.2.5.1
Earthing and short-circuiting equipment or devices shall be first connected to the earthing point and then
to the components to be earthed and in reverse order when removing.
In all cases, it shall be ensured that the earthing and short-circuiting equipment or devices and cables and
connectors for bonding used for this purpose are suitable and adequately matched to the fault rating of the
electrical installation where they are installed.