How can diesel be started in the maintenance mode?
automatic and remote starts are disabled, but may be started locally
what are the start and stop auto signals for the fuel oil pump in reference to the day tank?
18.8” - 41”
What should the exhaust temperature maintain between the 2 engines?
Within 200ºF of each other (111ºC)
What is the minimum air pressure allowed by the tech spec?
175 psig
what’s the tech spec limit for fuel level? How long will this allow it to run?
44,616 gallons (7 days) or >6.2 feet
What temperature does the temp control valve maintain?
what temp does the jacket water heater maintain?
180ºF
140-155ºF
what is the power supply to the motor driven air compressor?
12B51
When does the motor driven compressor cycle on and off?
ON - 220 psig
OFF - 235 psig
When does the diesel driven compressor cycle on and off?
ON - 190 psig
OFF - 225 psig
If diesel is carrying the bus alone with NO offsite power, what happens if LOCA signal is received?
Nothing, the diesel keeps the bus
What is the purpose of the scavenging pump?
Runs durin operation to filter and cool lube
what is the purpose of the soak back pump?
Circulate oil from lube oil pump to turbo bearing to cool bearing after oil system has shut down. It circulates through lube oil cooler to pick up heat while in STBY
What are the Electrical Trips?
RLOG
- Reverse power
- Loss of excitation
- Overcurrent with voltage restraint
- Generator differential
What are the mechanical trips?
- Overspeed 1035 rpm
- Low lube oil pressure <20psig
- High jacket water temp >205ºF
- High crankcase pressure 1” water column
How long will the diesel attempt to start after receiving a start signal?
5 seconds
When is air supply cut off when starting
150 rpms
When can the starting motors be re-engaged?
< 50 rpms
How can starting logic be reset after a failed start?
Engine lockout pushbutton must be depressed
How does diesel respond to a LOCA signal? (with no other signal)
Diesel will start and wait as long as BUS still has voltage. breaker cannot be closed manually or automatically with only LOCA signal present
What’s the tech spec rating of DIV 3
3300 kw
What trips are in on a LOCA and BUV signal?
Generator differential and overspeed
How does diesel shutdown on normal shutdown?
Engine runs for 10 minutes @ 450 RPMs to allow engine to cool prior to shutdown
How does diesel shutdown in emergency shutdown?
Shuts down immediately
What is the purpose of the Div 3 diesel?
provide backup power to HPCS
How long can diesel run on Day tank?
2 hours
what is the tech spec limit for fuel oil day tank?
220 gallons?
What initiation logic can be reset even while it is still sealed in?
Drywell pressure
What happens if Diesel detects a BUV or LOCA during the 10 minute cooldown?
increases back to 900 rpm, but will not take the BUS until voltage reset pushbutton is depressed