When will the lead compressor load and unload?

A

125 - 135 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

when will the lag compressor load and unload?

A

120-130 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What flow will throttle the F501 valve, with 1 compressor running?

A

> 985 scfm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

what flow will throttle the F501 valve, with 2 compressors running?

A

> 1970 scfm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When will the air bleed-off valve for instrument and plant air auto open?

Why does it do this?

A

opens at 30 psig.

it does this to force F532 to fail open, allowing air to vent to Aux bldg to be processed by STBY gas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When will standby mode be exited?

A
Standby pressed a second time
Start button pressed
Shutdown button pressed
It is the only PAC running
Second PAC placed in standby
if it starts 5 times in 24 hours
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many PACS can be placed in STBY at same time?

A

one

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is normal and backup cooling for PAC’s?

A

normal - TBCW

backup - SSW B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Will SSW B auto align to PAC in a loss of TBCW?
LOP?
LOCA?

A

TBCW - NO

LOP - YES

LOCA - NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Will PAC A restart automatically after a BUV/LOP?

A

No, but it can be manually started 20 SECONDS after diesel takes the bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what pressure will cause a control rod drift?

A

70 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What pressure does the ADS compressors boost instrument air to?

A

165 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Will lamp test button alarm the control room?

A

Yes, after 5 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens if STBY unit runs unloaded for continuous 60 minute time period?

A

Turns off - but remains in standby

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How is PAC reset after a trip?

A

Push shutdown button locally OR take control room switch to STOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the power supplies to Plant Air Compressors and the Aux power supplies?

A

A - 16 - 16B42
B - 14 - 22B31
C - 13 - 11B31

17
Q

What control Room panels are the PAC’s controlled from?

A

A - 870
B - 854
C - 854

18
Q

What are the Plant Air Compressor Trips?

A
  1. Low oil pressure
  2. Discharge pressure high
  3. power failure
  4. cabinet high temp
  5. oil pump trip
  6. cabinet vent fan trip
  7. motor contact trip
  8. INFI-90 trouble
  9. LSS for PAC A
19
Q

Where can a PAC be placed in STBY from?

A

Locally only

20
Q

When will a STBY PAC auto start?

A

Trip of running PAC
Service air low 90 psig for 40 seconds
Plant air low 115 psig for 5 seconds

21
Q

When will the F501 close on service air?

A

100 psig on plant air

22
Q

What pressure does the primary valve for instrument air maintain?

The backup valve?

A

primary - 110 psig

backup - 100 psig

23
Q

What pressure does service air maintain?

A

110 psig

24
Q

When will the service air pressure control valve go fully closed?

A

100 psig on plant air