L11 - DC Flashcards

1
Q
What are the charger feeds for the following DC busses?
11DD
11DE
11DG
21DG
11DK
11DL
11DF
11DH
11DJ
A
11DD - 15
11DE - 16
11DG - 18
21DG - 28
11DK - 15
11DL - 16
11DF - K and L in series
11DH - 15P
11DJ - 16P
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How long will div 1 and 2 batteries last during power outage and what voltage must it maintain?

How long does it take to charge them?

A

4 hours, 2.13 volts per cell

12 hours to charge them

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If one charger is INOP what should be done in one hour?

what if that action can’t be met?

A

verify battery cell parameters are met

Declare battery INOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
what are the batteries associated with the following busses?
1901
1902
1903
1904
1905
2901
2902
A
1901 - E
1902 - E
1903 - D
1904 - E
1905 - D
2901 - D
2902 - D
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the battery charger normally in service for Div 3?

A

C4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How long will Div 3 batteries last?

how long does it take to charge them?

A

2 hours

8 hours to charge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

On battery chargers, what order do you close the breakers when you put them in service?

A

DC before AC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many DC busses are required in modes 1,2,3?

A

Div 1,2,3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If AC supply is out of service to battery charger, what else should be done? Why?

A

Open associated charger output breaker to prevent battery from discharging

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What temp should battery rooms be maintained at?

What happens if it’s not maintained?

A

should be maintained >62 deg F

<60 deg F, INOP battery

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What should always be operable in the battery room?

A

Hydrogen detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

At what percent hydrogen should chargers be taken to equalize?

A

50%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
What's the power supplies to the following battery chargers?
1A4
1A5
1B4
1B5
A

1A4 - 15BA6
1A5 - 15BA3
1B4 - 16BB6
1B5 - 16BB3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the power supply to 1C4 and 1C5 battery chargers?

A

1C4 - 17B01

1C5 - 13B11

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

1C4 battery charger output breaker trips open due to internal breaker fault, voltage on 11DC drops by how many volts?

A

5-10 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly