Other Important Shit Flashcards

1
Q

Which unit can open ZMO-10 and 20?

A

Either Unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which unit can close ZMO-10 / 20

A

BOTH units are needed to close these valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If there is a CRCV Fire in Unit 1, what fire protection is available?

A

Auto Halon

Manual CO2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If there is a CRCV Fire in Unit 2, what fire protection is available?

A

Auto Halon

Manual CO2

Auto Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is special if Halon is actuated at the cylinder?

A

Extended discharge cylinders won’t acutate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the Containment Chill Water Purpose?

A

Provide 55*F water to containment loads

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens if you use disable on the HMI for containment chill water?

A

You shutdown the entire system (chillers and pumps)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What makes up the Hi-Storm 100 System?

A
  1. Hi-Storm Overpack
  2. MPC
  3. Hi-Trac Transfer
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the purpose of Helium in the dry cask system?

A

Cooling

Inert Atmosphere to prevent chemical reaction

Leak detection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How does Liquid Release Valve RRV-285 fail on a loss of CA?

A

Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the inputs to the RCDT?

A

Receives drains from:

Accumulator Drains
XS LD Hx Drains
Regen Hx Drains
RCS Loop Drains
RCP #2 Seal Leak off
Rx Vessel Flange Leakoff
Refueling Cavity

OUTLET OF TANK

RCP #3 Seal Leak off
PRT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How many Ctmt Sumps are there and what are they?

A
  1. Recirc Sump
  2. Rx Cavity Sump
  3. Lower Ctmt Sump
  4. Pipe Tunnel Sump
  5. Instrument Room Sump
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What goes into the CWHUT

A

Hard piped drains from 609’ and above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What goes into the DWHUT

A

Floor drains from 609’ and above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What goes into the Clean Waste Sump Tank

A

Hard piped drains from 587’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What goes into the Dirty Waste Sump Tank

A

Floor drains from 587’

17
Q

What goes into the AB Sump

A

573’ Floor Drains

Including Clean and Dirty Waste Sump Tanks overflow

18
Q

What is the purpose of the Waste Gas Release Pressure Control Valve RRV-305?

A

Maintains a constant 5# inlet pressure to RRV-306

19
Q

What is the Waste Gas Release Flow Control Valve RRV-306 used for?

A

Manually positioned to control release flow rate

20
Q

What is the purpose of the Moisture Separator Gas Recycle Valves?

A

Control Vent Header Pressure

21
Q

What is the purpose of the WG Separator Unloader Valve

A

Prevents compressor from starting under load

22
Q

Purpose of WGC Inlet Isolations?

A

Prevents short-circuiting gas thru the S/B WGC

23
Q

What is the design of the Waste Gas System?

A

adequate processing for both plants assuming 1% fuel defects in 1 Unit

24
Q

Which systems / components vent to the waste gas vent header?

A

RCDT

CVCS HUTs

VCT

AGA

PRT

NBAE Vent Condenser

SRST

WG Recycle Lines

Waste Gas Drain Tank Vents

25
What is the purpose of the AGA?
Monitors waste gas system tanks for flammable mix of Hydrogen and Oxygen
26
What is the purpose of the AOM?
Monitors OXYGEN at discharge of compressors
27
What is the purpose of the Waste Gas Compressor?
Maintain Waste Gas Vent Hdr pressure 1.3 - 2.0# by auto starting and stopping as needed
28
What pressure must the waste gas header be at for the pump to start?
< 0.5 #
29
8.7.13 Gas Storage Tanks Basis - Restricting the quantity of radioactivity contained in each gas storage tank provides assurance that in the event of:
an uncontrolled release, the resulting total body exposure to an individual at the nearest site boundary will not exceed 0.5 rem