NOTIFICATION MADE TO THE FDNY ANYTIME STANDPIPE SYSTEM IS OR WILL BE OOS
ANYTIME NO EXCEPTIONS
NOTIFICATION OF SPRINKLER OOS:
- more than one floor
- more than 8 hours
- other fire protection system OOS (aside from sprinkler–meaning fire alarm/standpipe ) in the same area
FIRE ALARM:
- more than one floor
- more than 8 hours in 24 hour period
- one or more in same area (same as sprinkler )
Standpipe system at CONSTRUCTION SITE
- immediately notify FDNY of any UNPLANNED OOS
- NOTIFY AT LEAST 24 HOURS planned to removal of standpipe system from service
if standpipe is OOS —-NO TORCH WORK
Officer receiving notification of OOS FIRE PROTECTION SYSTEM
obtain particulars and make journal entry
–if not admin district, phone OFFICER of admin unit
Upon notification of OOS fire protection system…immediately investigate with members and apparatus ….
EXCEPTION: a shut down for SCHEDULED, TESTING, MAINTENANCE AND THE SYSTEM WILL BE PLACED BACK IN SERVICE PRIOR TO END OF BUSINESS DAY , investigation is NOT NECESSARY, unless OFFICER feels its required
**Officer should however, advise surrounding units, BC and DC
SYSTEM found to be OOS (FDNY was not notified) during inspection or routine response
-request BC , if OFFICER FEELS RESPONSE IS NECESSARY
NOTE: Occupancies with LARGE LIFE HAZARD , LARGE PROPERTY VALUE, OR SPRINKLER HEAD REPLACEMENT IS CONSIDERED, REQUEST BC
OOS SYSTEM
-tags placed by IMPAIRMENT COORDINATOR ….FDNY DOES NOT PLACE TAGS
- Place proper disk (white OOS / BLUE-Partial , if supplied)
- issue VO forthwith for RESTORATION OF SYSTEM
- CONSIDER VO FOR FIRE WATCH BY FIRE GUARD (4 hours/ 50,000 sq feet)…building shall be evacuated if fire watch cannot be maintained
- *impairment coordinator or other building staff TRAINED may conduct fire watch during initial 4 hours provided the floor area IN WHICH FIRE PROTECTION SYSTEM IS OOS DOES NOT EXCEED 50,000 SQUARE FEET
- SUMMONS FOR FAILURE TO NOTIFY
- A-8 TO FIRE PREVENTION (so thEY CAN SCHEDULE TEST OF SYSTEM)
-
Fire alarm activates, do exterior inspection ….no indications of fire, etc…direct DISPATCHER to notify alarm company
WATER FLOW- if force entry and sprinkler is monitored by alarm, notify dispatch
if NOT MONITORED BY ALARM, NOTIFY FIRE MARSHALS for notification to responsible party
-NYPD for security
COMMERCIAL PROPERTY
STANDPIPE OOS and no responsible party present
NOTIFY FIRE MARSHALS
RESIDENTIAL NOTIFICATION
OOS SYSTEM
NOTIFY OEM
OOS during inspection at private dwelling
ISSUE VO for restoration of fire alarm system
ISSUE VO for restoration of sprinkler system
replacing SPRINKLER HEADS?
- -must have HEADS AND WRENCH in locked metal cabinet
- safety of ours members not compromised
- *do not replace in sprinkler chutes, shafts , other unsafe areas as determined by IC**
- DO NOT replace is owner, impairment coordinator, building staff is available
BATTALION CHIEF MUST ORDER REPLACEMENT