Ontario Building Code Assignment Flashcards
May a un-listed cable be ran 2 meters exposed inside a building?
Yes
What are the requirements of a service room located in combustible construction, in which an exposed unlisted communications service entrance cable over 3 meters long is placed?
Must be → separated from the rest of the building,
Fire rating of → not less than 1 hour
Describe all the methods that may be used to install 6 meters of unlisted communications service entrance cable, in a building constructed of noncombustible material?
Totally enclosed in a noncombustible raceway,
Concealed spaces in walls,
Concrete slabs,
Service room separated with a 1 hr fire separation,
Totally enclosed in a nonmetallic raceway
What are the ‘FT Rating” of cables that may be installed exposed in a computer room floor? (please select one or more)
FT1,
FT4,
FT6
Service Room is used to describe the area within a building that contains electrical equipment.
True
Under what conditions may a plywood backboard be used in a telecommunications room of a noncombustible construction?
Plywood not more than 25 mm thick,
Flame-spread rating of not more than 150
How should electrical outlet boxes be installed on opposite sides of a firewall in a building constructed of noncombustible materials without using fire stop material?
Separated horizontally not less than → 600 mm,
Boxes must be → Installed in adjacent stud cavities
What must be done to avoid using fire stop material when penetrating a membrane of a fire wall with a rigid conduit in a building constructed of noncombustible materials?
Tightly fitted