Which statement regarding NEXT is true?
Crosstalk is greatest at the near end (at the sender end)
What type of hard hat is recommended for Construction work?
Class E, Type 2
According to the TIA-569-D standard, what is the maximum length of conduit allowed between pull points in a horizontal cable system?
30 meters/100 feet
What must be done in order to operate a fusion splicer below 0 degrees?
Warm the splicing area
When testing cable, what does an asterisk (*) beside the NEXT value indicate?
The NEXT value is marginal
What size is the PBB (TMGB)?
0.25” x 4” x variable length
When viewed from the front of the patch panel, how are the WA cables routed on a two row 48-port hinged patch panel, that hinges towards the left?
All 48 cables are routed to the left side of the patch panel
What is the minimum diameter sheave (pulley) that is required for a 900 pair cable, 2.75” in diameter, if the bend radius for a multipair in 10 x OD?
55 inches
According to ANSI-568.0-D standard, what is the maximum installation pull/tensile load for a 4-pair cable?
25 lbf.
According to the TIA-569-D standard, what is the maximum number of 90º bends that may be placed between pull points of a horizontal conduit system?
2
Which of the jack pin/pair assignments is backward compatible with 2-pair USOC configuration?
T568A
Which firestopping material should be used to seal a round opening in a concrete wall?
Intumescent foam
A 100BASE-TX switch uses two 25-pair cables to connect to a patch panel. What is the minimum number of patch panel jacks needed to terminate the two cables?
- 12 for each cable
If a patch panel is 4 Us high, how much space in inches will it take up on the rack?
7 inches
What size of mechanical splice devices are required to splice a loose tube cable to a breakout cable?
250 µm - 900 µm
What is the minimum number of BBC’s (a.k.a., ground equalizer [GE]) required in a ten story building with two TRs per floor?
4
Which type of network topology require a central device?
Star topology
According to ANSI-568-C.2 standard, which of the following is a required certification field-test parameter?
Return Loss
Which firestopping material should not be used to seal a round opening in a concrete wall?
Self leveling caulk
A hybrid optical fiber loose-tube cable, with 6 strands per tube, has 24 SM strands in the first series of tubes. What are the colours of the strand and the tube of the MM fiber strand 18?
Red tube, white strand
An analog CCTV system is to be converted to digital. What infrastructure equipment is required to allow the use of some existing analog cameras?
A PoE Ethernet switch connected to a PoE powered video encoder
A bundle of cables in a TR are not labelled. What tool is used to identify the cables?
Toner/wand
When viewed from the front of the patch panel, how are the WA cables routed on a two row 48-port hinged patch panel, that hinges towards the left?
All 48 cables are routed to the left side of the patch panel
What is the nominal impedance of RG-58 (Series-58) cable?
50 Ω
A hybrid optical fiber loose-tube cable, with 6 strands per tube, has 24 SM strands in the first series of tubes. What are the colours of the strand and the tube of MM strand 24?
Black tube, white strand
What is done after fusing two fibers together?
Install splice protector
What instrument is required to measure the length of a coaxial cable?
Time domain reflectometer
What equipment is needed to find a defective fiber connector?
Visual fault locator
What is insertion loss?
Insertion loss is the same as attenuation
What is the allowable ampacity for a 24 awg, 75 ºC, 8 conductor Class 2 power and Data circuit, when using only 4 conductors and bundled with 1 other cable?
1.96 A
Which wire map test cannot be done with a basic continuity-type tester?
Split pairs
According to the ANSI-568.3-D standard, what is the identifying colour of a single mode optical fiber SC connectors?
Blue
When certifying a Cat. 6A direct attached link, or a.k.a., modular plug termination link (MPTL). How is the certifying equipment configured?
A link adapter at one end and a patch cord adapter at the other end
What equipment is needed to find an active fiber strand?
Fiber identifier
How many sheets of plywood are required in a TR located on an 80,000 ft² floor space, where the ratio of floor area to plywood is 75:1?
34 sheets
A 600-pair OSP feeder cable is terminated in a branch splice enclosure to two 300-pair OSP distribution cables. What is the minimum number of 25-pair straight connector modules for this enclosure?
24 modules
According to the TIA-569-D standard, what is the maximum allowable distance between non-continuous cable supports such as “J” hooks?
5 ft
Which one of the TIA standards would you refer to for information about the grounding and bonding requirements for telecommunications?
TIA-607
What is tested with a tier 2 optical fiber test?
Attenuation of cable elements
A fiber link indicates a loss of 10 dBm. How much light power is being received at the receiver?
100 µW
According to the TIA-569-D standard, what is the maximum length of conduit allowed between pull points in a horizontal cable system?
30 meters
When pulling a multi-pair cable, what is done to eliminate twisting?
Pull cable with a swivel