NNI system function
Provides alarms, indications, and control signals for system variable such as temp, press, flow, and level.
Encompasses all instrumentation other than Nuclear Instrumentation.
discuss a Type A variable
provides info req’d to allow operators to take manual actions for which no auto control is provided AND
are req’d for a safety system to do its safety function
Discuss Type B Variable
provide info to indicate whether plant safety functions are being accomplished such as:
- reactivity control
- core cooling
- maintain RCS integrity
- maintain containment integrity
Discuss Type C Variable
Provide info to indicate potential for breach of barriers to fission product release.
Discuss Type D variables
provide info to indicate the operations of ind. safety systems
Discuss Type E variables
provide info req’d to determine the magnitude of the release of radioactive materials and for continuously assessing such releases
Which variables are category 1? the most stringent cat.
A, B, & C
Which variables fall into category 2?
Type D & E
Which variables fall into category 3?
all backup variables fall into this cat.
What is a key variable?
single variable that most directly indicates the accomplishment of a safety function or indication of radioactive release
What is a backup variable?
additional variables to provide info to backup the key variables and allow diagnosis
NNI X is powered from ____.
NNI Y is powered from ____.
RS-1 or Y-02
RS-4 or Y-01
each channel has normal seeking ABT
Power supply monitor will trip the S-1 and S-2 switches when any DC power is lost for ____ seconds.
> 0.5 seconds
Smart Automatic Signal Selector (SASS) System does what?
SASS transfers to a redundant input when a rapid signal failure is detected.
Placing the mismatch alarm bypass switch to ON has ___ effect on auto transfer capabilities.
no effect