NERC PRACTICE SET 4 Flashcards
In the ACE equation, (NIA - NIS) reflects the _______ portion.
a. frequency
b. interchange
c. load
d. generation
b. interchange
Multiple contingencies occurring within ______ of each other shall be treated as a single contingency.
a. One minute or less
b. 15 minutes
c. 5 minutes
d. 2 minutes
a. One minute or less
On a radial transmission system a generator has a capacity of 600 MWs. The Droop
characteristic is at 5% and the generator is currently loaded at 300 MWs. If frequency
suddenly drops to 59.3 Hz, what would be the total generator output?
a. 350
b. 400
c. 440
d. 600
c. 440
Interconnection frequency is 60.20 Hz. Your ACE is a large positive value, and your AGC is
pulsing your units down. What should you do?
a. Place AGC in constant frequency control
b. Place AGC in flat tie line control
c. Suspend AGC and investigate
d. Leave AGC in operation as your units respond
d. Leave AGC in operation as your units respond
Balancing Authority B has scheduled interchange of 100 MW from Balancing Authority A
and 100 MW to Balancing Authority C. Actual interchange is 115 MW from Balancing
Authority A and 95 MW to Balancing Authority C. What is the inadvertent interchange
for Balancing Authority B?
a. -20 MW
b. 20 MW
c. -40 MW
d. 40 MW
a. -20 MW
Low Voltage is a result of:
a. VAR Losses associated with heavy power transfers
b. Insufficient generation
c. Insufficient transmission capacity
d. Insufficient shunt reactors in service
a. VAR Losses associated with heavy power transfers
At 1105 frequency drops to 59.95 Hz due to a disturbance elsewhere in the Interconnection. The frequency returns to 60.00 Hz shortly afterwards and Balancing Authority A’s ACE is zero for the remainder of the hour. How would this affect the Balancing Authority’s Inadvertent Interchange for that hour?
a. Inadvertent would increase in the positive direction.
b. Inadvertent would increase in the negative direction.
c. Inadvertent would remain unchanged.
d. Inadvertent would go to zero.
a. Inadvertent would increase in the positive direction.
A Balancing Authority’s ACE has been 0 for the entire hour. After the hour the Balancing Authority operator notices that last hour its Inadvertent was +20. What is the likely cause of this Inadvertent?
a. Average frequency was high during the last hour.
b. Average frequency was lower than 59.96 Hz during the last hour.
c. Frequency was exactly 60.00 Hz for the entire last hour.
d. The average frequency for the last hour was 60.02 Hz.
b. Average frequency was lower than 59.96 Hz during the last hour.
Two Balancing Authorities have arranged a schedule of 500 MW between them, well within their transfer capability. Before the ramp has begun, the Reliability Coordinator informs them that implementing the schedule will result in overloading a transmission line in a neighboring system. What action should the two Balancing Authorities take?
a. Reduce the schedule to a level that will not cause a problem in the neighboring system.
b. Promise to reduce the schedule in the next scheduling hour, since it is too late to make changes now.
c. Inform the Reliability Coordinator that they are well below their allowed schedule magnitude and will not make any changes.
d. Implement the schedule and rely on the Reliability Coordinator to initiate transmission loading relief procedures if a problem actually occurs.
a. Reduce the schedule to a level that will not cause a problem in the neighboring system.
The load on a power transformer is 80 MW and 60 MVAR. What is the Transformer’s Power Factor?
a. 0.80 PF
b. 0.70 PF
c. 0.60 PF
d. 0.50 PF
a. 0.80 PF
A 50 MVA rated transformer has 40 MW of load. How many MVARs can flow through the transformer without exceeding the rating?
a. 50 MVAR
b. 40 MVAR
c. 30 MVAR
d. 0 MVAR
c. 30 MVAR
A transformer rated at 550 MVA has 500 MW and 55 MVAR passing through it. Which of the following is true?
a. No action is required because the transformer is within limits
b. No action is required because the transformer is less than 10% above its limit
c. The load on the transformer must be reduced because it is above its limit
d. The load on the transformer cannot be determined without knowing the power factor
a. No action is required because the transformer is within limits
Which statement describes a transmission line loaded at its Surge Impendence Loading (SIL)?
a. The line is inductive
b. The line is capacitive
c. The lines natural capacitance is equal to its inductance with no impact to voltage.
d. The line will exceed it SOL
c. The lines natural capacitance is equal to its inductance with no impact to voltage.
350 MW is flowing into a 230/100 kV transformer rated at 500 MVA transformer. What MW value is flowing on the low side of the transformer?
a. 100 MW
b. 230 MW
c. 350 MW
d. 500 MW
c. 350 MW
If the frequency on both sides of an open breaker is exactly matched, which of the following statements is true?
a. The phase angle across the breaker is zero
b. The phase angle across the breaker is constant
c. The voltage magnitude across the breaker is matched
d. The phase angle across the breaker is 180 degrees
b. The phase angle across the breaker is constant