HSI Quiz Bank Flashcards
Which of the following terms is defined as the scan rate values of a Balancing Authority’s ACE measured in MW, which includes the difference between the Balancing Authority’s Net Interchange Actual and its Net Interchange Scheduled, plus its Frequency Bias obligation, plus any known meter error?
Automatic Time Error
Reporting ACE
Reserve Sharing Group Reporting
ACE Control Error
Reporting ACE
The Control Performance Standards limit the width of the regulation boundaries for which of the following?
AGC
ACE
Frequency
Voltage
ACE
Each Balancing Authority must fulfill its commitment to the Interconnection and not __________the other Balancing Authorities in the Interconnection.
Communicate with
Own Joint units
Burden
Trade with
Burden
Which of the following terms applies to the Western Interconnection only, and the addition of a component to the ACE equation that modifies the control point for the purpose of continuously paying back Primary Inadvertent Interchange to correct accumulated time error?
Reserve Sharing Group Reporting ACE
Automatic Time Error Correction
Reporting ACE
Regulation Reserve Sharing Group
Automatic Time Error Correction
In the ACE equation (NIA - NIS) reflects which portion?
Load
Interchange
Generation
Frequency
Interchange
You are a Balancing Authority Operator. A neighboring Balancing Authority in the Interconnection suddenly has a 500 MW generator trip due to a generator ground. What part of the ACE equation, ACE = (NIA-NIS) - 10B (FA-FS) - IME, allows you and other Balancing Authorities in the Interconnection to help stabilize the Interconnection frequency error?
IME
(FA- FS) - IME
NIA - NIS
10B (FA-FS)
10B (FA-FS)
Balancing Authority A is scheduled to import a net 200 MW and is actually importing a net 150 MW. The Bias Setting is -100 MW/.1 HZ and Actual Frequency is 59.95 Hz. What is Balancing Authority A’s ACE reading?
-100 MW
-55 MW
+100 MW
0 MW
0 MW
Feedback: The key to this question is recognizing the word import. That means the schedule and actual interchange are negative values.
ACE = [(-150) – (-200)] – [10(-100)(59.95 – 60.00)]
ACE = [+50] – [+50]
ACE = 0
Which of the following elements is NOT included in the ACE equations frequency component?
Actual Frequency (FA)
Scheduled Frequency (FS)
Meter Error (IME)
Frequency Bias Setting (B)
Meter Error (IME)
A Balancing Authority has a tie-line meter that has been verified reading 5 MWs high. The flow on the tie-line is out of the BA’s Area. What effect will this have on the ACE reading?
ACE will read 5 MW above its actual value
ACE will not be affected by the inaccurate reading
It depends on whether frequency is high or low
ACE will read 5 MW below its actual value
ACE will read 5 MW above its actual value
What happens when a Balancing Authority is being evaluated for its CPS1 Control Performance, and a sustained interruption in the recording of ACE or Frequency Deviation due to loss of telemetering or computer unavailability results in a one-minute interval not containing at least 50% of samples of both ACE and Frequency Deviation?
The one-minute interval is excluded from the CPS1 calculation.
The information that was salvaged is saved and added to another partial interrupted minute, then included in the calculation when the total information gathered equals one-minute.
The information is used because at least 10% of the data was accumulated.
The information from the partial minute is sent to the NERC Operating Committee for evaluation.
The one-minute interval is excluded from the CPS1 calculation.
A Balancing Authority has an ACE of -50 MW when Interconnection frequency is 60.04 Hz. Is the BA in danger of exceeding the Balancing Authority ACE Limit (BAAL)?
Yes, if the BA’s Frequency Bias is less than or equal to -100MW/.1 Hz
No, there is no low BAAL when frequency is high
Yes, if the BA’s Frequency Bias is greater than -100MW/.1 Hz
No, there is no low BAAL when frequency is high
To conform to CPS requirements, a Balancing Authority must have which of the following?
CPS1 greater than or equal to 90% or BAAL greater than or equal to 100%.
CPS1 greater than or equal to 100% and ACE does not exceed BAAL more than 15 consecutive minutes.
CPS1 greater than or equal to 90% and ACE does not exceed BAAL more than 30 consecutive minutes.
CPS1 greater than or equal to 100% and ACE does not exceed BAAL more than 30 consecutive minutes.
CPS1 greater than or equal to 100% and ACE does not exceed BAAL more than 30 consecutive minutes.
The purpose of Reliability Standard BAL-001, which defines CPS1 and BAAL compliance requirements is:
To ensure Balancing Authorities within an Interchange with multiple Balancing Authorities maintain regulation reserves equal to or greater than their MSSC.
To control Interconnection frequency deviations to less than or equal to two standard deviations.
To ensure equitable market operations between Balancing Authorities within the identified BES Interchange.
To control Interconnection frequency within defined limits.
To control Interconnection frequency within defined limits.
If a Balancing Authority does not comply with the Control Performance Standard, it is not permitted to provide which of the following for any other Balancing Authority entities?
Regulation of other services related to control performance
Scheduled transactions
System support
Frequency control
Regulation of other services related to control performance
Which statement best describes the CPS1 requirement?
The Responsible Entity must operate so its CPS1 is greater than or equal to 100% for the preceding 12-month period.
The average ACE for a defined 10-minute period must be within a limit called L10.
ACE must follow changes in load and schedule within a bandwidth called L10.
ACE must start to return to zero one minute after crossing zero.
The Responsible Entity must operate so its CPS1 is greater than or equal to 100% for the preceding 12-month period.
A Balancing Authority’s CPS1 calculation is computed using its clock-minute average of two values. What are those two values?
Actual and Scheduled Net Interchange NIA and NIS.
Reporting ACE and Frequency Error
L10 and Reporting ACE
Actual and Scheduled Frequency (FA and FS)
Reporting ACE and Frequency Error
A Balancing Authority is slightly undergenerating its Actual System Frequency (FA) is 60.03 Hz. What is the result of the Balancing Authority’s action?
The Balancing Authority is hurting the Interconnection Frequency.
The Balancing Authority is helping the Interconnection Frequency.
The Balancing Authority is in CPS1 violation.
The Balancing Authority is in BAAL violation
The Balancing Authority is helping the Interconnection Frequency.
What should a Balancing Authority set Scheduled Frequency to for a slow Time Error Correction?
59.80 Hz
59.98 Hz
60.20 Hz
60.02 Hz
60.02 Hz
What happens to frequency on the Interconnection (measured by FA in the ACE equation) when its generation does not match its load?
The Interconnection’s Scheduled Frequency will no longer be included in the ACE equation calculation.
The Interconnection’s Actual Frequency will match its Scheduled Frequency.
The Interconnection’s Frequency will increase by 0.05 Hz.
The Interconnection’s Actual Frequency will either increase or decrease in proportion to the generation/load mismatch
The Interconnection’s Actual Frequency will either increase or decrease in proportion to the generation/load mismatch
What should a Balancing Authority set Scheduled Frequency to for a fast Time Error Correction?
60.20 Hz
59.98 Hz
60.02 Hz
59.80 Hz
59.98 Hz
Feedback: If there is a fast time error, that means frequency has averaged above 60.00 Hz for a period of time. To correct that time error. All BAs in the Interconnection set their Scheduled Frequency to 59.98 Hz to bring the average frequency back down to 60.00 Hz.
Balancing Authority B has a Net Interchange Schedule of 300 MW and a Frequency Bias of -80 MW/.1 Hz. A 400 MW generator in the BA’s area trips resulting in a New Interchange Actual reading of -80 MW and frequency of 59.96 Hz. What is BA B’s ACE?
-384 MW
+412 MW
-412 MW
-700 MW
-412 MW
When does the Contingency Reserve Restoration Period begin?
At the top of the hour after the Reportable Disturbance
At the end of the Disturbance Recovery Period
When all Contingency Reserve has been exhausted
At the start of the Reportable Disturbance
At the end of the Disturbance Recovery Period
Feedback: The Contingency Reserve Restoration Period begins at the end of the Disturbance Recovery Period.
NERC Standard BAL 002
How often must each Reserve Sharing Group and Balancing Authority review their probable contingencies to determine their prospective most sever single contingency?
Monthly
Annually
Quarterly
Semi-annually
Annually
Feedback: At a minimum, the Balancing Authority or Reserve Sharing Group shall carry at least enough contingency reserve to cover the most severe single contingency. All Balancing Authorities and Reserve Sharing Groups shall review, no less frequently than annually, their probable contingencies to determine their prospective most severe single contingencies.
Balancing Authorities change. New generators and lines are added as system demands grow. Failing to recognize the need for increased contingency reserve could cause a Balancing Authority or its Reserve Sharing Group to fail to meet the DCS.
NERC Standard BAL-002
The Contingency Reserve Restoration period is ________.
One minute
90 minutes
15 minutes
45 minutes
90 minutes
Feedback: The Contingency Reserve Restoration Period begins at the end of the Disturbance Recovery Period.
The default Contingency Reserve Restoration period is 90 minutes. This period may be adjusted to better suit the reliability targets of the Interconnection based on analysis approved by the NERC Operating Committee.
The Contingency Reserve Restoration period is 90 minutes beyond the 15-minute Disturbance Recovery Period. Meaning the Balancing Authority or Reserve Sharing Group must obtain enough reserves to respond to the next most severe single contingency not longer than 90 minutes later. Shedding load would be an option to acquire enough contingency reserves to meet the next reportable disturbance if the reserves cannot be obtained by more normal means.
NERC Standard BAL-002