Minnesota Fuel Gas Code Flashcards
Unless otherwise approved in accordance with Section 105, appliances regulated by this code shall be?
listed and labeled
FG 301.7
Unlisted appliances may be approved based upon what?
an approved engineering evaluation
FG 301.7
For a label affixed to a listed fuel gas appliance, which of the following is not required information?
A. the appliance Btu/hr rating
B. if the appliance is rated for 120 or 220 volt alternating current
C. the approved fuel
D. the minimum required clearances
B. if the appliance is rated for 120 or 220 volt alternating current
FG 301.5
Combustion air requirements for appliances with power burners are determined by what?
the manufacturer’s instructions
FG 304.1
Conversion of an appliances to a different fuel gas is allowed if in accordance with what?
the manufacturer’s instructions
FG 301.7.1
Appliances in structures located in flood hazard areas shall be located at or above the what?
elevation required by the IBC
FG 301.11
Notching at the ends of wood joists shall not exceed _____ the joist depth.
1/4
FG 302.3.2
Cuts, notches and bored holes are prohibited in trusses except where the effects are what?
specifically considered in the design
FG 302.3.1
In bearing partitions, any wood stud is permitted to be cut or notched to a depth not exceeding ______ percent of its width.
25 percent
FG 302.3.3
Notches in the flange of a cold-formed steel stud in a bearing wall are?
not allowed
FG 302.6
Appliances shall not be installed in a location subject to vehicle damage except?
where protected by approved means
FG 303.4
Where used, draft hoods and draft barometric regulators shall be installed in the what?
same room as the appliance
FG 304.3
Where mechanical exhaust interferes with the operation of an appliance, what is required?
makeup air
FG 304.4
Where the air-infiltration rate is unknown, a room or space providing indoor combustion air requires a minimum volume of ______ cubic feet per 1,000 Btu/hr of the appliance input rating.
50
FG 304.5.1
When using the known air infiltration rate method for indoor combustion air, the maximum infiltration rate that can be used in the equation is what?
0.60 ACH
FG 304.5.2
Holes bored in solid wood joists shall be located not less than ______ inches from the top and bottom joist.
2 inches
FG 302.3.2
Openings obtaining indoor combustion air from a different story require a total minimum free area of ____ square inches per 1,000 Btu/hr of the total input rating of appliances.
2 square inches
FG 304.5.3.2
The minimum dimension of an outdoor combustion air opening is what?
3 inches
FG 304.7.3 #3
Where a space is provided outdoor combustion air through a single opening, a clearance of at least _____ inches is required in front of the appliance.
6 inches
FG 304.6.2
A mechanical combustion air system shall supply outdoor air at a rate not less than _______ cfm per 1,000 Btu/hr of total input rating of all appliances located within the space.
0.35 cfm
FG 304.9
Where a screen is installed at a combustion air opening, the mesh size shall not be smaller than what?
1/4 inch
FG 304.10
Equipment and appliances having an ignition source shall _______ _____ ___________ in Group H occupancies or control areas where open use, handling or dispensing of combustible, flammable or explosive materials occurs.
not be installed
FG 305.2
Appliances having an ignition source shall be elevated such that the ignition source is not less than ______ inches above the floor in a private garage.
18 inches
FG 305.3
Where vehicles are capable of passing under an appliance installed in a public garage, the appliance shall be installed a minimum of _____ inches higher than the tallest vehicle garage door opening.
12 inches
FG 305.4
Unless otherwise protected from impact, appliances located in a public garage shall be installed a minimum of ____ feet above the floor.
8 feet
FG 305.4
Unless otherwise protected from impact, appliances located in a private garage shall be installed a minimum of _____ feet above the floor.
6 feet
FG 305.5
Where the opening dimensions are large enough to allow removal of the largest pieces of equipment installed in an under-floor space, the clear access opening to the under-floor area shall be a minimum of what?
22 inches by 30 inches
FG 306.4
Guards are not required for rooftop appliances requiring service where what is installed?
approved fall-restraint devices are installed
FG 306.6 See Exception
Suspended mechanical equipment shall be installed a minimum of _____ inches above the adjoining grade.
6 inches
FG 305.7
Unless located within a dwelling unit, rooms containing appliances shall be provided with a door and an unobstructed passageway measuring not less than _____ inches wide and 80 inches high.
36 inches wide
FG 306.2
Appliances located in an attic shall be provided with a level service space not less than ______ inches deep and ______ inches wide.
30 inches deep
30 inches wide
FG 306.3
A 30 inch high attic passageway serving a gas appliance is limited in length to no more than what?
20 feet
FG 306.3
Where an appliance is located in an attic, a what is required at the access opening to the attic passageway?
a light switch
FG 306.3.1
A permanent approved means of access is required for appliances installed on roofs at a height exceeding what?
16 feet
FG 306.5 See Exception
Required guards installed around rooftop service platforms shall be not less than ______ inches in height.
42 inches
FG 306.6
Condensate waste and drain lines shall be not less than _____-inch internal diameter.
3/4-inch
FG 307.3
Condensate piping for fuel burning condensing appliances shall maintain a minimum horizontal slope of ______ units vertical in 12 units horizontal.
1/8 units vertical
FG 307.2
Where appliances are supported by a concrete slab, the slab shall extend at least _____ inches above the adjoining grade.
3 inches
FG 305.7
Where a reduction in clearance to combustible material is permitted, the side clearance for an appliance is permitted to be reduced from 12 inches to a minimum of _____ inches by installing No. 24 gage galvanized sheet metal with a ventilated air space.
4 inches
FG Table 308.2
For a clearance reduction system using ventilated air space, the system shall maintain an air space clearance to combustible materials of at least what?
1 inch
FG Table 308.2 Exception e
Reduced clearance protective assemblies for gas appliances shall be placed a minimum of _____ inch from the appliance.
1 inch
FG Table 308.2 Exception i
The bonding jumper used to bond corrugated stainless steel tubing (CSST) gas piping to the grounding system shall not be smaller than _____ AWG copper wire or equivalent.
6 AWG
FG 310.2.2
The maximum length of an electrical bonding jumper for a corrugated stainless steel tubing (CSST) system is what?
75 feet
FG 310.2.3
For other than steel piping, exposed gas piping must be identified by a yellow label marked “Gas” in black letters and the markings spaced at intervals not exceeding what?
5 feet
FG 401.5
Where there are multiple meters, the __________ must mark the piping system supplied by each meter with an approved permanent identification.
installer
FG 401.7
The volume of gas to be provided must be determined directly from the ________ __________ of the appliance served.
input rating
FG 402.2
Gas piping is permitted to be sized in accordance with the sizing tables in the piping system’s what?
piping system manufacturer
FG 402.3 #2
Using the longest length method for sizing gas piping, each section of piping is measured from what to what?
the point of delivery to the most remote outlet
FG 402.4.1
A gas piping system located inside an ____________ building is limited to a maximum design operating pressure of 5 pounds per square inch gage (psig).
A. institutional
B. industrial
C. warehouse
D. research
A. institutional
FG 402.7 Exception #4
Used pipe, fittings, valves and other materials must not be used in a gas piping system except where they are free of what?
foreign material
FG 403.2
Copper and copper alloy gas piping is permitted to be installed when the gas contains no more than an average of _______ grains of hydrogen sulfide per 100 standard cubic feet of gas.
0.3 grains
FG 403.4.3
Field drilled and tapped pipe fittings are permitted under limited conditions when the work is performed by whom?
the gas supplier
FG 403.10.5 #9.3
For steel gas piping, threaded fittings larger than _____ inches are not permitted.
4 inches
FG 403.10.5 #1
Gas piping must not be installed in or through a what?
A. plenum
B. clothes chute
C. attic
D. enclosed space
B. clothes chute
FG 404.3
What piping is not allowed for supplying fuel gas?
A. aluminum
B. copper alloy
C. CPVC
D. polyethylene
C. CPVC
FG 403.6
Gas piping must not enter a building through where?
underground
FG 404.6
Where gas piping is required to be installed in conduit and one end terminates outdoors, the conduit must extend not less than _____ inches outside the building.
4 inches
FG 404.8.1
A required conduit containing gas piping must extend not less than _____ inches beyond the point where the pipe emerges from the floor in the building.
2 inches
FG 404.8.1
Exterior above-ground gas piping must be elevated not less than _____ inches above ground and roof surfaces.
3 1/2 inches
FG 404.9
In general, underground gas piping systems must be installed at a minimum depth of ______ inches below grade.
12 inches
FG 404.12
The unthreaded portion of gas piping outlets must extend not less than _____ inch(es) through finished ceilings and walls.
1 inch
FG 404.16
Plastic gas pipe is generally permitted to be installed where?
outdoors underground only
FG 404.17
Underground nonmetallic gas piping requires a yellow insulated copper tracer wire not less than what size?
18 AWG
FG 404.17.3
The following threaded fittings for steel gas piping are allowed in concealed locations except?
A. couplings
B. tees
C. unions
D. elbows
C. unions
FG 404.5
The test pressure must be not less than ______ times the proposed maximum working pressure of the gas piping system.
1 1/2 times
FG 406.4.1
Where steel shield plates are required to protect concealed gas piping installed through holes in wood studs, the shield plates must extend a minimum of _____ inches to each side of the stud.
4 inches
FG 404.7.1
Supports for 1-inch steel gas piping shall be spaced no more than _____ feet apart.
8 feet
FG Table 415.1
Gas piping supports for 1/2-inch copper tubing shall be spaced no more than _____ feet apart.
4 feet
FG Table 415.1
Unless incorporated as part of the appliance, a sediment trap shall be installed where?
downstream of the appliance shut off valve
FG 408.4
Sediment traps are not required for what?
A. ranges
B. water heaters
C. boilers
D. forced air furnaces
A. ranges
FG 408.4
The installation of shutoff valves shall be prohibited where?
in concealed locations and furnace plenums
FG 409.1.2
Where a single meter is used to supply gas to more than one building, a shutoff valve shall be provided where?
outdoors at each building
FG 409.3.2