Field Inspections Flashcards
Horizontal wet venting always ends with what connection?
Toilet connection
P 908.2.4
Horizontal wet venting is only for all fixtures located where?
In a bathroom group
P 908.2.5
Horizontal wet venting pipes shall be no less than ______ in diameter.
2 inches
P 908.1.1
The horizontal wet vent may not be less than _____ inches for 5 DFU specified in table 702.1.
3 inches
P 908.2.2
Only _____ wet-vented fixture drain, or trap arm, is permitted to discharge upstream of the dry vented fixture drain connection in a horizontal wet vent.
one
P 908.2.1
The dry vent connection to the horizontal wet vent shall be an individual vent for either the ________, _________ or ______.
bidet, shower or tub
P 908.2.1
No vertical wet vent shall exceed _________ in developed length.
6 feet
P 908.1
No waste connection shall be made to a closet bend or stub of a ________ _________ or similar fixture.
water closet
P 310.3
No water closet or bidet shall be set closer than _________ from its center to a side wall.
15 inches
P 402.5
Floor-outlet or floor-mounted fixtures shall be secured to the drainage connection and floor by screws or bolts of what material?
corrosion resistant (Galvanized)
P 402.3
Water closet rings must be _________ in diameter, cut flush to present a smooth surface, and be bolted down with what type of screws or bolts?
7 inches
corrosion resistant (Galvanized)
P 402.6.1 and 402.6.2
A kitchen island needs a clean out at the end of the line that connects to what?
vertical wet vent
P 909.1
The kitchen island drain shall be provided with a ______ ______ connected to the vertical fixture vent by means of a wye fitting directly beneath the floor and extending through the roof.
foot vent
P 909.1
The ________ _________ sink drain shall serve no other fixtures.
kitchen island
P 909.1
Kitchen island loop of PVC drain and vent needs to be what?
as high as possible
P 909.1
The return bend for a kitchen island shall be a one piece fitting, or an assembly of a __________, a __________, and a _________ elbow in the order named.
45 degree
90 degree
45 degree
P 909.1
Kitchens shall not have a waste outlet less than ________ in diameter.
1 1/2 inches
P 420.4
Kitchen waste outlets shall be provided with an approved what?
strainer
P 420.4
Test gauges shall have a pressure range not exceeding ______ the test pressure applied.
twice
P 318.5
DWV aired up to _____ lbs for at least ______ minutes.
5
15
P 712.3
Boca plates and nail plates need to be placed on studs and top plates within ________ of the side of the wood and shall extend ________ beyond the outside diameter of the pipe or tubing.
1 inch
1 1/2 inches
P 312.9
Showers shall be capable of encompassing __________ circle.
30 inch
P 408.6
Showers shall have a trap arm waste outlet not less than ___________ in diameter.
2 inches
P 408.4
Water supply riser for the shower head whether exposed or not shall be what?
securely attached to the structure
P 408.10
Shower compartments, regardless of shape, shall have a minimum finished interior of what?
1024 square inches
P 408.6
Shower heads and control valves shall not be pointed directly at the what of the shower?
enter or exit
P 408.9
The maximum hot water temperature discharging from a freestanding bathtub with two handles and a whirlpool bathtub filler with two handles, shall be limited to ___________ with a _________ _________ or a limiting device conforming to ASSE 1070, ASME A112.1070, CSA B125.70 or CSA B125.3.
120 degrees
mixing valve
P 409.4
Bathtubs shall have a waste outlet of not less than _________ in diameter.
1 1/2 inches
P 409.2
Bathtubs shall be provided with an approved stopper or _____________.
strainer
P 409.2
Lavatories shall not have a waste outlet less than __________ in diameter.
1 1/4 inches
P 407.5
Lavatories shall be provided with an approved stopper or _____________.
strainer
P 407.5
Only _________ diameter vents going through the roof. Nothing smaller. For frost or snow closure.
2 inch
P 906.7
Any change in diameter for a vent going through the roof shall be made inside the building not less than ____________ below the roof in an insulated space.
12 inches
P 906.7
The diameter of an individual vent shall be not less than ___________, nor less than _____ the diameter of the drain it serves.
1 1/4 inches
1/2
P 904.1
Mot more than ________ of the total permitted length of a minimum sized vent shall be installed in a horizontal position.
1/3
P 904.2
Vents shall be _________ above the flood level rim of the fixture served before offsetting horizontally.
6 inches
P 905.3
Vent pipes shall terminate _______ from or not less than _________ above an openable window, door, opening, or air intake.
10 feet
3 feet
P 906.2
A branch of the waste system exceeding __________ in length shall be separately vented.
15 feet
P 910.3
2 fixtures shall be permitted to be served by a common vertical vent where each such fixture wastes separately into approved double fitting having inlet openings at the what?
same level
P 905.6
Vertical wet-vented fixtures shall be within the same ________, fixtures that discharge into a wet vent shall be on the same _______.
story
story
P 908.1
Vents shall be ________ or shall be graded to allow drip back by gravity to the drainage pipe it serves.
level
P 905.1
Vents shall terminate vertically not less than ________ above the roof.
12 inches
P 906.3
Where vents connect to a horizontal drainpipe, each vent pipe shall have its invert taken off above the drainage centerline _____________ of the trap being served.
downstream
P 905.2
Vent pipes shall extend undiminished in _______ above and through the roof.
size
P 905.4
An accessible clean out shall be installed in each _______ for the waste and vent system. Clean outs are not required on a wet vented branch serving a single trap where the fixture tailpiece is not less than __________ and you have access to clean through the trap.
vent
2 inches
P 910.6
2 fixtures set back-to-back, or side by side shall be permitted to be served by a single vertical drainage pipe provided that each fixture wastes ____________ into a double fixture fitting having inlet openings at the same ________.
separately
level
P 704.2
1 ¼” pipe diameter, ______ minimum and _____ maximum trap to vent.
1 ½” pipe diameter, _____ minimum and ______ maximum trap to vent.
2” pipe diameter, ______ minimum and ______ maximum trap to vent.
3” pipe diameter, _______ minimum and ______ maximum trap to vent.
2 1/2” - 30”
3” - 42”
4” - 60”
6” - 72”
P Table 1002.2
Fixtures on floor levels above the next upstream manhole and do not need a ___________ ________, shall not discharge through the ___________ ________.
backwater valve
P 710.1
Cleanouts for drains that pass through a backwater valve shall be clearly identified with a permanent label saying, “__________ _______ ______________”.
backwater valve downstream
P 710.1
A vent installed upstream of a backwater valve that obstructs the free flow of air shall not be used for meeting the ______________ _______ venting requirements.
cross-sectional area
P 904.1
Clean outs must be what?
accessible
P 707.8
Cleanouts shall be watertight and _________.
gastight
P 707.3
Each clean out shall be installed to allow cleaning in the direction of what?
flow
P 707.5
Clean outs in piping 2” or less must have clearance of not less than ______ by ______ in front. Piping larger than 2” must have a clearance of not less than ______ by ______.
18” by 18”
24” by 24”
P 707.9
A cleanout shall not be required on a pipe or piping that is above the _________ ________ _________, except kitchen sinks, urinals, and the building drain.
lowest floor level
P 707.4 Exception #3
A 2-way cleanout fitting installed on the building sewer drain either inside or outside up to grade, shall be permitted to be substituted for a what?
upper terminal cleanout
P 707.4 Exception #4
Cannot glue ABS (black) to PVC (white) pipe together or any other plastic pipe. Must be a what?
listed connector
P 705.10.3
PVC and ABS piping must be supported _______ on center horizontally and supported at each horizontal branch connection.
48 inches
P Table 313.3
Long sweep 90 elbow is used for __________ change in direction in drainage pipe, or upper _________ to ________, medium sweep elbow is used for __________ from horizontal to vertical downward.
horizontal
vertical
horizontal
dumping
P 706.1, 706.2, 706.3, and 706.4
Voids around piping passing through concrete floors must be what?
sealed
P 312.1
Piping shall be installed so that piping or connections will not be subject to undue stress and provisions shall be made for __________, _____________, and structural __________.
expansion
contraction
settlement
P 312.1
Laundry box drain must be _____ minimum, ______ maximum. The trap for a clothes washer shall be not less than ______ but not more than ______ above the floor.
18”
32”
6”
18”
P 804.1
Indirect waste pipes exceeding _________ but less than _________ in length shall be directly trapped, but such traps need not be vented.
5 feet
15 feet
P 803.3
Angles and changes of direction in indirect waste pipes shall be provided with what to permit flushing and cleaning?
cleanouts
P 803.3
What shall be equipped with an approved backwater valve, have a drain inlet in full view, and be trapped and vented?
floor drains
P 1006.1
Maximum run lengths without insulation on hot water piping are as follows:
¾” hot water piping = ______ uninsulated max
½” hot water piping = ______ uninsulated max
>3/4” hot water piping = ______ uninsulated max
10’
20’
5’
RE 403.4.2 and Table 403.4.2
PEX piping 1” and smaller must be supported horizontally every _______, vertically, base and each floor. PEX piping 1 ¼” and larger must be supported every _______ horizontally, and mid-story guides vertically.
32”
4’
P Table 313.3
Copper piping 1 ½” and smaller must be supported every ______ horizontally, and each floor not to exceed ________ vertically.
6 feet
10 feet
P Table 313.3
Copper water tubing can not be strapped to exposed ________ _______ or __________ _______ for corrosion.
metal steel ducts
aluminum
FG 403.8
Sumps shall be ______ in diameter, and _______ in depth, and provided with a fitted cover. The discharge for the sump shall not be less than ________ in diameter.
15 inches
18 inches
1 1/2”
P 1101.6.2
Radon vent pipe must be a perforated pipe of drain tile connected with a T fitting with __________ of drain tile connected either side, or one _________ long piece.
10 feet
20 feet
MN 1303.2402
Radon vent pipe must be insulated with a minimum of ______ insulation and be located _______ above the roof, and _______ away from any window or opening.
R-4
12 inches
10 feet
MN 1303.2402
The space required around the radon vent pipe shall be ___________ from the center of the pipe for future installation of a fan.
24 inches
MN 1303.2402
The radon vent pipe shall be labeled where?
on each story
MN 1303.2402
Shall be unlawful to conceal imperfections by __________, or __________. Or using wax, tar, or some other sealant or repair agent.
welding
soldering
P 309.2
No water, soil, or waste pipe shall be in attics, crawl spaces, or exterior walls unless what?
protected from freezing
P 312.6
Stainless steel pipe shall not be installed _____________ and shall be kept at least ________ above ground.
underground
6 inches
P 701.2 #5
Vitrified clay pipe shall not be used _____________ and shall not be pressurized. It shall be not less than _________ below ground.
above ground
12 inches
P 701.2 #3
Galvanized wrought iron and galvanized steel pipe shall not be used _____________ and shall be kept ______ above ground.
underground
6”
P 701.2 #1
No under-floor cleanout shall be located exceeding ___________ from an access door, trap door, or crawl hole.
5 feet
P 707.9
Manometer test must equal ______ either side or ________ total for 15 minutes. Disconnect the line and see if air blows back.
0.5
1.0
P 712.5
Must run dishwasher drain line _______ _______ and secure.
high loop
P 807.3
Shower must have minimum vertical clearance from the shower drain outlet to _________ above.
70 inches
P 408.6
The finished curb or threshold for only a shower room shall have a threshold not less than ______ and not more than ________. Unless curated for accessibility purposes.
2 inches
9 inches
P 408.5
Doors or thresholds to a shower shall not be less than ___________ for means of egress. Unless curated for accessibility purposes.
22 inches
P 408.5
The maximum hot water temperature discharging from a freestanding bathtub with two handles and a whirlpool bathtub filler with two handles, shall be limited to _________ degrees with a __________ _________ or a limiting device conforming to ASSE 1070, ASME A112.1070, CSA B125.70 or CSA B125.3.
120 degrees
mixing valve
P 409.4
Waste outlets for bathtubs shall be provided with an approved _________ or _________.
stopper
strainer
P 409.2
The water supply to a bathtub and whirlpool bathtub filler shall be protected by a what?
air gap
P 409.5
Water heater relief lines shall terminate to a safe area, typically into or near a floor drain. Must terminate to a maximum of ________ above the finished floor.
18 inches
P 608.5 and M 1006.6
Water heaters installed in residential garages shall be ___________ above the floor unless listed as flammable vapor ignition resistant and shall be protected from vehicle damage.
18 inches
P 507.13 and 507.13.1
How many inches of copper or metallic piping, is minimum on all water lines connected to and coming from the water heater?
18 inches
P 604.13
Water heater relief valve shall not discharge into a what?
water heater pan
P 608.5 #7
Water heater relief valve shall not be smaller than the diameter of the relief outlet and shall be _________ and ___________.
reamed
unthreaded
M 1006.6
What must be built in or present on all exterior hose bibs?
vacuum breaker fittings
P 603.5.7
Water heater needs what type of unions at the connection of water piping to the water heater?
dielectric unions
P 605.15
Water heaters shall have what installed on the cold-water supply pipe?
ball valve
P 606.2
Water heaters shall be capable of being removed without first removing a permanent portion of the what?
building structure
M 1002.1
Every water softener must have an _________ _______, and a __________ __________ to allow it to be removed and serviced.
isolation valve
bypass valve
P 611.5
Valves, pipes, and fittings shall be installed in what direction?
direction of flow
P 310.7
Where a water heater is located in an attic, floor assembly, or floor sub-floor assembly where damage could result from a leaking water heater, it shall have a corrosion resistant pan that is ___________ in depth, with a __________ drain out of the pan to an approved location.
1 1/2 inches
3/4 inch
P 507.5
Where an equipment or appliance is installed in a space that could result in damage from condensate overflow, like furnaces, it shall have a ________ _______ ___________ device that will shut off the equipment, or be in a __________ ____________ ______ with a separate drain line, or an additional drain line that is higher than the primary.
water level detection
corrosion resistant pan
P814.2 #1 through #4
Sumps shall be _________ in diameter, and __________ in depth, and provided with a bolt and gasket type fitted cover that is watertight. The discharge for the sump shall not be less than ___________ in diameter.
15 inches
18 inches
1 1/2 inches
P 1101.6.2
PVC pipe serving the gas water heater as exhaust air must not be what type of pipe?
cellular core pipe
Installation Instructions (ASTM F891)
Construction for future installations shall be terminated with a what?
Plugged fitting or fittings
P 402.11
Water meters shall be supported, must be readily accessible and be a minimum of ______ above the finished floor.
12 inches
P 609.12
Copper water tubing can not be strapped to exposed metal ________ or _____________ ducts for corrosion (Galvanic Action).
steel
aluminum
FG 403.8
A total of ____________ in turns allowed on the trap arm to the vent. So, if the sink has a ______ to come out of the wall, that’s all the fittings. Except trap arms 3” and above are permitted 135 degrees.
90 degrees
90
P 1002.3
Not more than _______ approved slip joint fitting may be used on the outlet side of the trap.
one
P 1003.2
Not more than __________ trap shall be permitted on a trap arm.
one
P 1001.2
Unions must be installed within ___________ of regulating equipment such as water heaters, softeners, and similar equipment that requires service by removal or replacement.
12 inches
P 609.5
Flexible corrugated connectors of copper, copper alloy, or steel for fixture connectors are limited to ___________ and shall not exceed _____________ on water heaters.
30 inches
24 inches
P 604.12 and 604.13
A level working platform in minimum dimension __________ by _____________ shall be provided on the service side of the appliance.
30 inches
30 inches
P 508.4.3
The diameter of the inlet or outlet of a water heater, softener, filter or similar equipment shall not be less than the diameter of such water distribution piping to the fixtures served by the device. Water can not be ___________, then ______________ creating a pressure loss.
decreased
increased
P 610.2
Water softeners must have an approved air gap and must have a ________ air gap at openings near 1”, not less than ________ air gap no matter what.
2 inch
1 inch
P Table 603.3.1
¾” softener connection, up to _____-bathroom groups plus additional water closet and lavatory. 1” water softener connection, up to _____-bathroom groups served and shall be engineered for the specific installation.
2
4
P Table 611.4
Handheld showers, faucets, fixtures and bathtubs shall have a ___________ ____________ where they reach to the bottom floor or flood level. Must be stamped with either ASME A112.18.3 or ASSE 1014.
backflow preventer
P 417.3
Where a fixture meets the wall or floor, the joint between the fixture and the wall or floor shall be made what?
watertight
P 402.2
Lavatory waste outlets shall be provided with an approved what?
stopper or strainer
P 407.5
Fixtures with concealed slip joint connections shall be accessible with a working space not less than __________ in its least dimension.
12 inches
P 402.10
Indirect waste pipes shall not be smaller than ________ and shall not exceed ___________ in developed length.
1 inch
15 feet
P 803.3
No water, soil, or waste pipe shall be in attics, crawl spaces, or exterior walls unless what?
protected from freezing
P 312.6
Construction for future installations shall be terminated with what?
Plug fittings
P 402.11
Floor mounted, back outlet water closets shall have a soil pipe not less than how many inches?
3 inches
P 402.6.3
Drainage or vent piping shall not be ________ and ________ for the purpose of connections and no __________ pipe shall be threaded.
drilled
tapped
cast-iron
P 310.2
Water distribution systems shall provide a ________ ________ at the distribution manifold, or immediately ahead of each fixture being supplied and shall be __________ with the fixture being supplied. If the distribution manifold is not readily accessible, a _________ _______ shall be required immediately ahead of each fixture.
control valve
identified
control valve
P 606.5