What is the definition of a computer room according to the IECC?

A

a room whose primary function is to house equipment for the processing and storage of electronic data that has a design total information technology equipment power density less than or equal to 20 watts per square foot or a design total ITE equipment load less than or equal to 10 kW

Ch 2 CE pg C-8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which of the following occupancies is considered a commercial building under the IECC?
A. two-story R-3 building
B. one-story R-4 building
C. four-story R-2 building
D. none of the above

A

C. four-story R-2 building

Ch 2 CE pg’s C-8 and C-11