Milking Parlor Flashcards
The milking parlor shall be located close to the confinement to optimize animal flow. The minimum distance of the milking parlor shall be ______ away from lactating barn and the maximum distance shall not exceed to _______ if the milking frequency is three times a day and _______ if it is two times a day.
30 m , 180 m , 275 m
For sanitation, it shall be at least _______ away from manure piles or wastewater pond.
100 m
The floor slope shall be ________ towards the drain.
2% - 4 %
Intersection with the walls shall be rounded with _______ radius.
50 mm - 60 mm
Intersection with wall to wall and floor to wall shall be shall be rounded with _______ radius.
50 mm - 60 mm
All wall tops and ledges shall slope at _______.
45 degree
Ceilings shall be at least ______ from the finished floor line
2.4 m
Window ledges shall be sloped about _________ to prevent the accumulation of dirt, water, or debris.
45 degree
Windowsill shall be at least ______ from the finish floor line
1 m
Doors shall have a minimum width of _________.
1.5 m
Holding area and wash pen shall be provided. It shall have a minimum space requirement of _______ m2 per animal.
2.23
Holding area shall be paved and rough finished and it shall slope _________ away from
the parlor.
2% - 4%
The width of the alley shall be _________ to keep the animals from turning around
0.7 m - 0.9 m
The slope of the alley shall not exceed _________.
5%
If specific circumstances require alleys shall be greater than 5%, install steps with _________.
150 mm rise and 460 mm run
The treads may be sloped no more than ______ to help achieve the required elevation change.
1.5%
For a back-out stall, ________ headroom shall be provided in front of the stall
0.9 m
For a walk-through, a space of _______ ahead of the stall shall be provided to enable the animals to exit the stalls and turn into next alley.
1.8 m
Milking stall shall be _______ wide when a bucket milking machine is used or when hand milking is practiced.
1 m – 1.1 m
If pipeline-milking system is practiced, ____________ shall
be provided.
0.7 m – 0.8 m
The stall length shall be at least ________ and the height shall be at least ________.
1.5 m , 1.2 m
Railings of the stall shall be made of at least 50 mm G.I. pipe and shall be spaced at
________.
0.4 m
The space for the milker/operator and milking equipment shall be _______ wide
0.6 m – 0.8 m
A milk tank should be installed with a capacity that is equivalent to a minimum of _______ days of milk production by the dairy animal herd during its peak production period.
2.5
(LIGHTING) Holding area/wash area
100 lux
(LIGHTING) General lighting
200 lux
(LIGHTING) Milker/Milking operator’s area
500 lux
Convenience outlet shall be waterproof type. It shall be installed ____________ high
depending on the position and height of milking machine.
1 m - 1.5 m