Farm workshop and Machinery Shed Flashcards
The building shall be situated at least _________ from other buildings to reduce fire hazard,
to allow for future expansion, and maneuvering and parking of machinery
45 m
The minimum storage area for machinery shed shall be calculated by multiplying the
width plus _____ by length plus ______ for each machine
0.6 m, 0.6 m
For the approach aprons, the slope shall be ______ away from the building
3 % - 5 %
When the roof span is ____ or less, a beam shall be used
3 m
The minimum clear height from floor to truss shall be at least ______.
3 m
For machines higher than 3 m, the height shall be the sum of the machine height plus ______.
0.3 m
Minimum dimension of a doorway shall be ______ high and ______ wide
3 m, 3.7 m
The door height shall be provided with a clearance of at least _____ above the tallest
machinery
0.3 m
Workbenches shall be at least ______ high
1 m
The bench width shall be ______ and at least ______ long.
0.8 m, 3 m
For a welding area, a welding hood with a fan that will move air about _____________ shall be provided
28 m3/min , 57 m3/min
If vehicles are to be operated in the shop for a period of time, an exhaust hose through the wall or a small suction fan pulling exhaust through a tube from the exhaust pipe shall be
provided. The fan shall be capable of moving air about _______ per vehicle through the pipe.
7 m3/min
A 120-volt or 240-volt outlet shall preferably be installed every _____ along workbenches and every _____ along walls.
1.2 m , 3 m
(Lighting) General
200 lux
(Lighting) Bench
500 lux
(Lighting) Outside the shop and Active storage area
100 lux
(Lighting) Machine shed
50 lux