Membrane & Steep-Slope Roof Systems Flashcards
What is the slope of a low-roof system?
3:12
The criterion for judging proper slope for drainage is that there be no ponding water on the roof ___ hours after a rain during conditions conducive to drying.
48 hours
Vertical alignment of cementitious wood fiber panels in excess of ____ inch in elevation difference is considered unacceptable in roofing.
1/8”
NRCA recommends steel roof decks be __-gauge or heavier and have a minimum G-___ galvanized coating.
22-gauge
G-90
When a design requires steel decks to be welded, what is the recommend puddle weld size and what is the maximum spacing?
Puddle welds of 1/2 of an inch or larger into steel washers
Spaced a maximum of 12 inches on center along every support
Steel deck side lap fastener spacing should not exceed?
3 feet
What are the two broad categories of vapor retarders in a membrane roof system?
Bituminous vapor retarders
Plastic Sheet or Film Vapor Retarders
What is the minimum thickness for tapered cellular-glass insulation (roofing)?
1-1/2 inches
What is the product standard for faced polyisocyanurate?
ASTM C1289
The U.S. product standard for asphalt used in roof system applications is ASTM____
ASTM D312
What is the softening point for hot-applied asphalt for built-up roof membranes - Type I?
135F Minimum
151 F Maximum
What is the softening point for hot-applied asphalt for built-up roof membranes - Type IV?
210F Minimum
225F Maximum
NRCA recommends asphalt be applied in the field within a +/- ____ temperature range from an asphalt’s indicated EVT.
25F
What are the three categories for roll roofing materials?
- base sheets
- ply sheets
-mineral-surfaces cap sheet
What is the minimum base flashing around an equipment roof curb?
8” minimum flashing height
When installing a loose-laid EPDM single-ply system, it will require the use of ______ to provide for the resistance against uplift forces.
ballasts
The maximum temperature mop application for Type IV asphalt is _______ F.
495F