Maintenance (General) Flashcards

1
Q

Stacker 44 doesn’t have a micro limit switch to show the brake released on the long travel brakes. What does it have instead?

A

It has a current sensor instead. The current sensor in 44 shows if current is drawn or not, and if that matches the setting of the current put into the device (the device is the current sensor itself; it has a current setting).

This current being drawn doesn’t always mean the brake is drawn in. It just means current is there.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

To test if a motor is phase reversed…

A

Put a clamp on meter around 1 of the 3 conductors and see if current being drawn is more than on a conductor of another motor (can test and reverse phases at breaker of the motor itself).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When hanging up a laminated single line diagram to the wall, what materials do we use?

A

Silicone on the back of the poster, and duct tape on the edges.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Visually, how is a dc and ac motor distinguishable?

A

Dc motors do not have the exterior fins (slots on motor housing itself). Ac will (unless small ac motor).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The red handle holding the safety cable for lockout should be closest to the ground or highest lockout point?

A

Highest for easier access.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Transfer tower 1 has a magnet. Explain how to lock it out.

A

Lock out the conveyors 1A and 1B. (2A and 2B is not necessary unless going into that danger zone; those conveyors’ tail ends are at the bottom, with their head being at TT2).

Then, climb the TT itself. De energize the control circuit that controls the positioning aspect of the magnet. Also de energize the trolley in the 600V cabinet. Leave the breaker for the magnet itself energized if needed. Then, lock out the cabinet.

(Ensure to not lock out the magnet in the sub unless explicitly directed to do so).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Under what conditions is a bypass suggested over a force on?

A

If the device is turned off due to malfunction and a bypass is suggested and explicitly approved, a bypass is recommended.

A force is suggested if the device is turned off but healthy and the system needs it to run.

For example, if a magnet is still energized, but there’s a system fault due to the magnet being out of position and the trolley/positioning control circuit is deenergized, force on the input bit for the magnet position to make the output happy, allowing the conveyor, for instance, to run as needed, without the magnet being in position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

On the e300, which two lights should be solid to ensure it works?

A

MS and NS.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is an e300? What are its components?

A

It’s an electronic (smart) overload relay.

The e300 consists of

1) a communication module. This sends info via Ethernet to control architecture (plc bits for instance).

2) a sensing module. This has ability to detect ground faults, voltage of the system, and current flowing in the system.

3) a control module. This contains terminal blocks and Ethernet ports.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the megger process?

A

Firstly, de energize the bucket to be meggered. Then, check with your voltmeter if there is any voltage (as long as bucket isn’t over 600 or 1000v; verify how much meter can handle btw!).

For voltage check, check to ground from each cable.

Then, loosen the wires at the easiest point (breaker or terminal block etc).

Then, connect the black megger lead (negative) to ground. Take the red to each phase one at a time, and test each phase to ground. (Use the right amount of voltage coming from the megger; then hold the test button).

For a healthy motor, want to see high resistance (giga ohms preferably).

Prior to doing the megger test, can check continuity from each phase to ground as well. If the fault is bad enough, you’ll see continuity.

Afterwards, once megger test is done, you can use voltmeter and test each phase to one another via your ohmeter selection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Why is it important to tighten the screws that lock the cabinet doors?

A

They’re arc flash rated; they need to be tightened enough to withstand an explosion.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What’s the procedure for pullcord pm’s and inspecting and repairing?

A

Check to see if turnbuckles are tensioned correctly, and taped. Check to see if station resets well (lubricate it always). Check to see red bulbs work.

If in the field, ensure a gentle enough pull trips the pull cord. Adjust the tension by turning the turnbuckle (one way it’ll turn left to tighten, other way it’ll turn right, so turning one way will tighten in both directions).

If the pull cord station isn’t resetting, hold the pull cord station in reset position and adjust tension (loosen or tighten) until the pull cord station catches and resets.

Tape up the turn buckles to ensure they don’t loosen by themselves.

If in the sub, ensure the trip is shown in the plc, hmi, and that the pull cord relays change positions (have to press b88 if they latch).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How does the temperature gauge work on the transformer?

A

A metal rod sticks out the back of the faceplate housing that juts into the transformer. The front guage reads according to the bar’s temp.

To test it, loosen the one nut closest to faceplate, pull entire apparatus out, and heat up the bar to the setting where the contacts on the switch (part of temp guage switch) close.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How does the gas pressure gauge on a transformer work? And how do you test it?

A

The gas pressure gauge contains a diaphragm and an internal relay. The relay responds to oil pressure that rises slowly, causing the gauge to increase. The diaphragm responds to a quick rise in pressure (oil doesn’t empty through pinhole fast enough into compartment, causing diaphragm to fill and push outwards).

To test, turn off the oil valve (part of pipe going into back of the device; it allows oil to cycle through device basically). Then, loosen schroder valve. Take a pump and push air into the piece. This tests the oil pressure alarm. It should trip.

Then, loosen the little cap inside shroder valve, and take it out completely. Then, loosen the spring valve up top. Air should come out, as well as oil at the bottom. This should trip the low oil alarm.

Then, close shroder valve, and the valve for oil. Let it run until oil comes out spring valve. Then close spring valve when guage reading is good.

The shroder valve connects to the diaphragm directly. Loosening it drains oil from diaphragm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If the shiploader at berth 1 (SL1) goes down, and is in need of a reset (not at the sub 6 feed to it), how is it reset?

A

At the transformer on ship loader 1. Press ack/reset, and then okay once the error message pops up. (The yellow tripped light will be on).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How are the breakers at SR 44 reset?

A

If the drive is in the open position, flick up the metal sliding door at the bottom of breaker device. Rack it in, and then, once it is at the farthest it can go, you charge the breaker itself by cranking the plastic handle in the middle of the breaker. Then, the breaker will say charged. Close it at that point.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

How does maintenance mode work on the breakers at SR44?

A

You turn on maintenance mode UPSTREAM of the breakers you are going to turn off (the upstream maintenance mode gives a higher protection level by tripping faster for faults) by switching the switch to maintenance mode enabled.

Do this before switching off breakers. Turn maintenance mode off after reenergization.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

How does the ultrasonic sensor we installed on conveyer 2 A/ 2 B work?

A

It’s an ultrasonic. It measures the distance between itself and the conveyor, detecting large chunks before they hit the TT.

It can act as a switch too. A sensor high will cut off the conveyor in the plc.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

At a cell, such as the one in sub 5, the local/remote switch does what?

A

The local setting allows the contactot to be pulled in locally BUT this setting may not be put in as a part of the plc program. This may cause a fault or alarm (not necessarily severe) in the plc as the control circuit of the cell (consisting of physical limit switches and the like) may send signals such as “closed” to the plc, causing a “fail to open” alarm potentially.

In another scenario, local switch may not be doing anything, depending on if it’s a physical switch or a control circuit switch.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What does the trip/closed switch on a cell, such as in sub 5, control?

A

The trip opens the contractor (green will show open). Red shows closed. This is used to test the contractor once the umbilical cord is plugged in.

The contractor shouldn’t be racked in at this point. But even if it was, the conveyor wouldn’t start (whether because of the vfd or the coupler not being engaged).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Why does an across the line starter (such as the case with the breaker for conveyor 10B in sub 5) not immediately start the conveyor when racked in?

A

Because the contactor is to be closed remotely via HMI.

Even if the contactor was closed locally, the conveyor would still not start as the coupler would not be engaged.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

On the cells (such as in sub 5), the L1-L2-L3 lights are lit up by which mechanism? And do they indicate the load or line sode?

A

They indicate the load side. The contactor is racked in, power bleeds through capacitors in the contactor itself, and the current which is leaked into the capacitor is then sent to the LED’s indicating power. They show power in contactor; not the line side.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

For a lockout at the cells in Sub 5 for example, how is the cell actually locked out?

A

Once the contactor is racked out, the red tag line goes through the black cover where the racking out tool is put in, AND through the door itself.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Should the handles of the cells in sub 5 be left in remote or local?

A

Remote.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What does the breaker control switch on the transformer feed cells (such as in sub 5) control?

A

It controls the opening and closing of the breaker (not a contactor).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

If trouble shooting shiploader 1, and the forward permissive is faulted, what’s a possible troubleshooting solution?

A

Move it the other way if the reverse permissive is happy, and then see if forward permissive resets itself.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

What are four ways of verifying power is dead?

A

1) the lights on the actual cells
2) verifying knives are out of the shudders and not attached to bus bar
3) opening the bucket and verifying dead power with meter (only on up to 1000v)
4) pressing the local station

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

To lockout a conveyor, like at sub 5, and there is no E stop on the cell, before racking out, what can you do?

A

Trip the breaker by flipping the breaker control switch handle.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

If there is no E stop, and no way to open the contactor before locking out, what is another way to safely rack out without arcing?

A

Haven’t the conveyor verified as deselected by checking the hmi performs the same function.

Arcing only occurs in the presence of a load.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

How do the doors of the cell feeders function?

A

If the door is open, and you close the handle, it will lock into that position. Then, you must pull/push/adjust the bolt on the inside of the door which, when pressed against the contractor, releases the locked position of the handle.

31
Q

If you have cables connecting to the load side of a cell and the lugs don’t line up (ie two hole bracket of the cell for mounting is different size than available lugs), whats a possible solution to this situation?

A

You can drill and tap the load side of the cell to line up with lugs. The tapping isn’t even necessary (have seen it without it too).

Tapping may even be overkill (a bolt and nut with washers and lock washers is enough).

32
Q

Where is the peckerhead for the conveyor motors?

A

Usually atop the motor. The cover can be opened, and then the actual peckerhead can be removed by removing the bolts that mount it to the motor. Once those bolts are removed, you can lift the peckerhead, gently guiding the motor leads through the hole at the bottom.

(The peckerhead has a hole at the bottom. The removal of bolts allows the peckerhead to be lifted up. Bolts keep the hole flush to the motor itself).

33
Q

If opening a motor’s peckerhead, how should you leave everything so it’s protected?

A

If removing peckerhead, put a couple garbage bags over top

The leads of the motor and the power incoming to the motor’s leads should be taped (can put a latex or rubber glove underneath the tape too for extra protection).

34
Q

How come you can’t megger the load side leads of a cell (ie in sub 5) when the contactor is racked out without removing the leads themselves?

A

When the contactor is racked out, the load side of the cell is grounded via a grounding mechanism that rises up to meet the load side terminals/lugs/bus bars/ etc. This is in the front side of the cell, but the mechanism connects to the backside of the cell where the load side leads are. Thus, it’s necessary to completely remove the leads before meggering.

35
Q

What is the purpose of a megger?

A

To test insulation quality (each phase to ground, with the black clip being the ground clip).

For testing phase to phase, NEVER use a megger (that’s a dead short) UNLESS the megger has an Ohmeter Setting (no voltage being pushed through).

Otherwise, can use a voltage a little bit higher than what is actually going through the cables (use discretion).

36
Q

What’s the process for removing the contactor?

A

After racking out, open the door.

Align the cart and push in, seeing the odjustit toggle put into position.

Unplug the umbilical cord beneath it.

Then, push in the side handles at the front of the contactor inwards to loosen and pull the contactor out.

37
Q

The spot that the racking out tool pushes into, the collar of it, if the contactor is removed, how can you push the collar in?

A

The black plastic piece beside the collar can have a screw pushed into it to toggle the lock and unlock of the collar. Once the collar is pushed in, the contactor can slide along its own rails with the help of the racking in and out tool as it winds it up and down the rails.

The door has a metal piece that pushes into the black piece during normal racking in and out.

38
Q

How can you check the control circuit of a cell using a voltmeter?

A

You can put black to ground, and use the red to measure dc. It should read negative on negative side of the circuit and positive on the positive side.

A reading of zero shows an open.

This open can be physically jumpered on the control side of the cell with wire.

Refer to drawings for a better idea of everything.

39
Q

How is the E stop circuit hard wired?

A

The control circuit for the contactor or contactors on a particular system (ie conveyor 3B, feeders 1-8 on D31, etc) is wired through a normally closed e stop. When e stop is pressed, the control circuit opens, faulting out the control circuit and de energizing the coil on the contactor which is responsible for opening and closing the contactor (the e stop circuit is in the circuit which has the wiring for the coil of the contactor itself).

40
Q

How is the B88 circuit wired?

A

The B88 is parallel to the start button.

41
Q

How far out should you rack out?

A

Until the contactor or breaker hits the stopper at the door. Verify by checking for the sticker to show that the system is grounded (the ground makes contact with the load side bus bar in case of an emergency where the line side contacts the load side)

42
Q

How do you make the breakers or disconnects easier to rack out?

A

Grease the forks and the rails. You can use nolox for it I believe but verify with foreman.

43
Q

Where is the service factor of a motor located, and what does it help determine?

A

On the nameplate. Helps determine the size of overload protection.

44
Q

What does a solid green light on a Cisco switch mean? What about blinking?

A

It means there’s connectivity through the system (things are connected fine). Blinking means there’s comms.

45
Q

What is a cam?

A

A cam is a lobe that turns with the cam shaft (shaft of the system). The cam will then make contact with another mechanical device, like a switch, which in turn can open or close a contact.

(Google camshaft limit switch if want).

46
Q

If the input bit on plc says I_0_01_7, what does that mean?

A

It means rack 0, slot 1, bit 7.

47
Q

In plc positioning for chassis, the first physical slot is numbered as…

A

Slot zero.

48
Q

In a solenoid, what is the spool?

A

The spool is the plunger that, once solenoid coil is energized, moves up or down depending on normal position. The coil attracts or repels the plunger.

49
Q

What is spring release?

A

It means the device has a spring that pushes it into its normal position. hydraulic or magnetic forces would be needed to have it act against that way. This device would be normally considered safe during power outage as magnetic force wouldn’t be there; the spring would then act and set the brake for instance.

50
Q

How does the b88 work?

A

It’s a plc bit.

Pressing the b88 can act as a reset for faults in the plc, faults who’s resetting is done in such a way that when a fault occurs, the rung itself has an almd box in it and the prog reset in that box says to press the sub master reset for instance, which is the b88.

In other instances, the master reset b88 bit acts as a start button almost. If a pump trips, and the trip is fixed, the rung will have to go through a b88 bit OR a pump ready bit. The pump ready bit corresponds to pump ready output but at the end of the rung. When b88 is pressed, rung energizes , output pump ready bit is energized, and the seal in happens via the pump ready input bit parallel to b88 bit.

51
Q

How do you do the schlepp?

A

You shuttle (via operator if spout unsafe spot and unclear visual to it), get slack, lift, slide pipes underneath. Then, use Allan keys to open up the side pieces. Theres an octagonal plastic cover, and Allan screws for the horizontal rung pieces. Take them out. Install new horizontal pieces or side pieces if needed. Re tighten.

52
Q

What is the function of the hydraulic take up system in the SR’s?

A

It moves the tripper so that it aligns over either the elevating car or the yard belt.

53
Q

How can you tell there’s a break in a wire if the megger shows no continuity to ground?

A

Use the motor genie (or a megger still) and test continuity at two ends of the cable (ie disconnecting it at motor and at nearest jb) and then hold two phases together and test continuity from one phase to the other phase at the end that isn’t tied together.

54
Q

How do the storm locks on the SR’s work?

A

The storm locks are activated when the boom is luffed into the park position.

To take them off, put the machine into maintenance mode (via sr operator). Then, go onto the apex, and luff the machine down AFTER releasing storm locks. Once the boom reaches a certain degree angle, you can release the storm locks jog release button (maybe 15 seconds after luffing down process is started).

Note: in plc, maintenance mode permission is needed for the storm locks. Then the storm locks have a jog release button. That releases storm locks. Sub 6 doesn’t have that button in the sub for example.

55
Q

Why use hasps when locking out the cell feeders?

A

Because if you use hasps, you can’t open the little sliding door that covers the racking mechanism. With just a rope, you can.

56
Q

How does the photo hunt in the dumpers work?

A

The photo hunt detects the wheel. Once it detects the wheel, the train moves back (via positioner) until it no longer detects it. Thats how it knows it’s lined up.

57
Q

What is the pendant dock at the dumper?

A

The pendant is the remote. The dock is the lever (it has an input bit to the plc that shows its lowered).

58
Q

What are the removable components of the schlepp?

A

The bars atop the schlepp runs are removed via Allen bolts.

The circles are linked together via a centrepiece which is removable via Allen bolts as well.

The circles have a twist lock.

If broken, unlock the middle piece first. Then, the bars bolts are loosened. Then, unlock and remove the circles.

Note: circles are 2 piecers, as in each piece consists of two circles and a middle locking bit.

59
Q

Where is the common upper probe located vs the entry probe?

A

It’s at top floor of the transfer tower at knee level, underneath a metal roof.

To change, loosen the bolts where the metal roof is on the outside and then twist the cover and take off. Then can change and edit things.

60
Q

Where is the common upper probe located vs the entry probe?

A

It’s at top floor of the transfer tower at knee level, underneath a metal roof.

To change, loosen the bolts where the metal roof is on the outside and then twist the cover and take off. Then can change and edit things.

61
Q

How do you verify that the cell feeders are racked in or out? How do you verify no power?

A

Check the stickers, as well as the open or closed lights on the door, or the racked in light on the panel board below the him. ( unsure if that would be called a him ).

Check the lights.

62
Q

What is hydraulic take up?

A

It’s a hydraulic take up of the conveyor belts (helps create tension).

In lieu of a counter weight.

63
Q

Some gates don’t have direction. How come?

A

Because in the ones that do have direction, there’s a pivot that can go 3 ways. Otherwise, if energized, the other version, it’ll just have it go one direction (like a funnel). And when it’s de energized, it goes back to the original position.

64
Q

Some gates don’t have direction. How come?

A

Because in the ones that do have direction, there’s a pivot that can go 3 ways. Otherwise, if energized, the other version, it’ll just have it go one direction (like a funnel). And when it’s de energized, it goes back to the original position.

65
Q

Which sr needs boom conveyor energized for run through?

A

Only sr 44. In the absence of a tripper, there is no hatch through which coal can fall cleanly through to the yard belt.

The boom conveyor needs to run in reverse to handle the residual coal that will fall on it.

Otherwise, can lockout everything on an sr and still run through.

66
Q

Which sr needs boom conveyor energized for run through?

A

Only sr 44. In the absence of a tripper, there is no hatch through which coal can fall cleanly through to the yard belt.

The boom conveyor needs to run in reverse to handle the residual coal that will fall on it.

67
Q

Does the input card or output card have a common hot?

A

The output card has a common hot (maybe a dc positive) which then goes through each output bit or “contact” to the device, which then comes back to a neutral.

That neutral may or may not be the same neutral as on the plc card. For example, if the plc output bit powers a relay which then closes contacts to power a higher voltage device (low v control), then the neutral of the relay should come back to the same neutral as the output card. The neutral of the device, however, will go back to a different neutral (same neutral as the circuit that IT is on).

The input card only has a common neutral terminal on it.

68
Q

The input card wire is on left side of the breaker or right? The output card wire goes to right or left?

A

Input wire from card will be on the right (as its load). The output wire will also be on the the left.

Line left, line top.

69
Q

How do you use 0.5A breakers to protect plc output cards?

A

Each output bit will have a breaker downstream of 0.5 amps. This will go to relay. The relay will control a higher voltage device.

70
Q

Red tie bars were seen on terminal blocks in the isam cabinet in sr 44. How do they work?

A

They tie in similar to regular joiners BUT there are certain spaces where the “teeth” of the red tie bars are missing, indicating that they have been popped out and so not tied in. The spots on the red tie bars where there ARENT missing “teeth” is connected.

71
Q

does polarity matter in ac?

A

Usually not.

72
Q

In sr44, describe the brake release and set indication system.

A

The brakes have their own breakers, current sensors (correct name is current monitor), as well as their own relays.

Power goes through breaker and activates the brake coil. Then, power travels through the current sensor. The current sensor sense the current (only if there is or not; no measurement). The current sensor then activates a relay (this relay is in series, but small chance it can be in paralllel).

This relay has aux contacts that then close. This sends a brake release input to the plc.

Power meanwhile goes back to neutral.

Note: the current sensor ONLY tells us if the brake coil is healthy. It tells us nothing about the armature health, or the health of the brake, or whether the coil is magnetized enough to pull in the armature. The current sensor is either a 1 (for current presence in brake coil) or 0 (for no current in brake coil). This means the brake can, in theory, not actually release and still show released in plc.

73
Q

In the sr’s, what’s best way to jumper out the brake and motor?

A

The motor breakers have an overload trip feature. That contact set can be taken out of the breaker and hung, so as not to show ol trip fault in plc. The breaker can then be turned off.

The brake can be jumpered out in the plc by bypassing, with a jumper, the brake release output bit.

The brake fault to release and fail to sets can be jumpered out in the same way in the plc on a rung which shows all the brakes, ending in an output but showing ALL brakes Released or set.

Basically, bypass the faults.

74
Q

What condition is likely if 2 phases of the motor have similar currents and the third phase is lower in currents?
What if one phase is extremely high?

A

It’s a shorter winding.

It’s one winding shorted to ground via the case of the motor.