LOT 201.15 RCS Temperature Monitoring Flashcards

1
Q
  • LOT 201.15 RCS Temperature Monitoring*
    • *

What parameters feed into OT∆T?

A

Tavg

∆T

Thermal Power

RCS Flow

PZR Pressure

  • *∆I**
  • Only used when ∆I exceeds +8%*

∆I and PZR Pressure NOT used for OP∆T.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 201.15 RCS Temperature Monitoring*
    • *

What are the RCS NR temperature instruments used for?

A
  • Tavg:*
  • *OT∆T**
  • *OP∆T**
  • *FW Isolation**
  • P-4 w/ Tavg - Low (574 ˚F)*
  • *P-12**
  • < 563 ˚F [2/4] Blocks steam dumps*
  • Auctioneered High Tavg:*
  • *Rod Control**
  • Indication on CP005 is Auctioneered Low Tavg*
  • *Steam Dumps**
  • *PZR Level Control**
  • Auctioneered Low Tavg:*
  • *C-17**
  • Auctioneered High ∆T:*
  • *Rod Insertion Limit**

3 in HL (120˚ apart for laminar flow concerns) and 1 in CL per loop.

Also has 3 fast response RTDs in CL per loop.

  • Note:*
  • 3 HL RTDs are averaged together to give signal. If 1 fails the system will automatically kick it out.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.15 RCS Temperature Monitoring*
    • *

What are the RCS WR temperature instruments used for?

A

PAMS

  • *COMS**
  • Auctioneered Low Tc (PCV-656A) and TH (PCV-655A)*

H/U and C/D

Aux S/D Panel

1 in HL and 1 in CL per loop.

  • Note:*
  • Located on CP018 and ICS
  • ASP for TC only.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly