LNG Storage Tanks Flashcards

1
Q

What is the working capacity of the two (2) double-wall/full containment LNG Storage Tanks (T-10001/2)?

A

200,000 M3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the designed normal operating pressure of the LNG tanks?

A

0.7 PSIG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the design temperature of the LNG tanks?

A

-150/-274 degrees fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Explain LNG rollover.

A

The rapid release of vapors causes stratifications

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the set relief point on PSV’s-100001A/B/C/D?

A

4 PSIG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

PC-100245A/B controls pressure of LNG tanks, and is set to open and close at what pressures?

A

open 0.15 close 0.25

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

During holding mode, LNG rundown from LTS to both tanks for peak LNG case are?

A

80 % to one tank 20% to the other

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the design pressure of the LNG Storage Tanks?

A

4 psig internal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The LNG Storage Tanks store LNG from what sources?

A

bog, pumps, psv’s from jetties, circulations line

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Five LNG pumps are used during loading operations to achieve a loading rate of?

A

12,000 M3/Hr

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

LALL-100009, low-low level alarm on Tank 1 and 2 is set at?

A

4.5 %

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

LAHH-100009, high-high level on Tank 1 and 2 shutdown is set at? And closes what valves?

A

98.5 closes sdv-100028 sdv-100032

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

ESD

A

ESD 0 - PLANT SHUT DOWN
ESD 1- LNG TANK ISOLATION
ESD 2- TANK PSI HH,LL - PZT-100014 A/B/C
TANK LEVEL HH, LL - LT-100009 A/B/C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

SIS-1012-1016
TRIPS PUMPS

A

ESD-0
ESD-1
LL TANK PSI
LL TANK LEVEL
ESD FROM JETTYS 1,2,3
GAS DETECTED
HIGH VIBRATION
LNG LOADING HDR 1 & 2
FLOWRATE LIMIT INTERLOCK

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

SIS-100010-100032
CLOSES ON:

A

ESD-0
ESD-1
HH- TANK PSI
HH- TANK LEVEL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

T-10001

A

200,000 M^3
DESIGN PSI 0.145 - 4
DESIGN TEMP- 150 F - -274 F
.7 NOP