LNG Storage Tanks Flashcards
What is the working capacity of the two (2) double-wall/full containment LNG Storage Tanks (T-10001/2)?
200,000 M3
What is the designed normal operating pressure of the LNG tanks?
0.7 PSIG
What is the design temperature of the LNG tanks?
-150/-274 degrees fahrenheit
Explain LNG rollover.
The rapid release of vapors causes stratifications
What is the set relief point on PSV’s-100001A/B/C/D?
4 PSIG
PC-100245A/B controls pressure of LNG tanks, and is set to open and close at what pressures?
open 0.15 close 0.25
During holding mode, LNG rundown from LTS to both tanks for peak LNG case are?
80 % to one tank 20% to the other
What is the design pressure of the LNG Storage Tanks?
4 psig internal
The LNG Storage Tanks store LNG from what sources?
bog, pumps, psv’s from jetties, circulations line
Five LNG pumps are used during loading operations to achieve a loading rate of?
12,000 M3/Hr
LALL-100009, low-low level alarm on Tank 1 and 2 is set at?
4.5 %
LAHH-100009, high-high level on Tank 1 and 2 shutdown is set at? And closes what valves?
98.5 closes sdv-100028 sdv-100032
ESD
ESD 0 - PLANT SHUT DOWN
ESD 1- LNG TANK ISOLATION
ESD 2- TANK PSI HH,LL - PZT-100014 A/B/C
TANK LEVEL HH, LL - LT-100009 A/B/C
SIS-1012-1016
TRIPS PUMPS
ESD-0
ESD-1
LL TANK PSI
LL TANK LEVEL
ESD FROM JETTYS 1,2,3
GAS DETECTED
HIGH VIBRATION
LNG LOADING HDR 1 & 2
FLOWRATE LIMIT INTERLOCK
SIS-100010-100032
CLOSES ON:
ESD-0
ESD-1
HH- TANK PSI
HH- TANK LEVEL