Fuel tanks, float switches, and supervisory signals for interstitial spaces are not required to be tested on an annual basis.
True
Vertical Turbine pumps are to be tested _____
Annually
An impeller obstruction may the cause of pressure drop when attempting to draw a large amount of water
True
A listed check valve or backflow preventer is required to be installed on the pump discharge assembly.
True
Steel tank interiors with corrosion protection shall be internally inspected every _____ yrs
5
Low water temperature alarms monitoring a water storage tank must be tested _____
Monthly
True or False.
Tanks with heating systems W/O a supervised low-temperature alarm shall be inspected daily during the heating season
True
When the water temperature of a tank is below 32f it is an _____
Impairment
Wooden tanks hoops ang grillage shall be inspected _____
Annually
A fire protection water storage tank serving a warehouse shall have its level indicator tested for accuracy and freedom of movement _____
Annually
Catwalks and ladder on tanks shall be inspected _____
Quarterly
Expansion joints must be inspected how often
Annually
Anti-Vortex plates shall be inspected for _____ while performing an internal inspection
Deterioration or blockages
Embankment-Supported Coated Fabric Suction Tanks are required to have their exposed surfaces repainted every _____ yrs
2
Painted and coated surfaces on tank supports shall be inspected _____
Annually