Identify and Classify ITM Deficiencies Flashcards
A defective air pressure gauge on the supply air of a dry pipe system is considered a _____
Critical deficiency
True or False.
An obstructed sprinkler is not an example of a critical deficiency
False
True or False.
Closed valves are the primary cause of failure for water based fire protection systems
True
A small leak inside a stairwell during a hydrostatic test on a manual standpipe is a _____.
Non-Critical deficiency
When performing a hydrostatic test and inspecting the standpipe, there is a hose rack that only swings out 60 degrees. This is a _____
Non-Critical deficiency
A 15% decrease in full flow pressure is found during a quarterly main drain test on a standpipe.
Critical deficiency
An anti-vortex plate showing signs of deterioration is an example of a/an _____
Critical deficiency
A water level indicator that has not been tested in 6 years is an example of a/an _____
Critical deficiency
An inoperative heating system with water temperatures below 40f is an example of a/an _____
Critical deficiency
A water storage tanks low water temperature alarm failed inspection this would be a/an _____
Critical deficiency
A slow drip from exposed piping on a fire service main is a/an _____
Critical deficiency
A condition that does not affect the systems functionality is a/an
Non-Critical deficiency
A standpipe missing the hydraulic information sign is a/an _____
Non-Critical deficiency
A low priming water level is a/an _____
Critical deficiency
Recessed escutcheons that have been glued on are a/an _____
Critical deficiency