ITM Dry Systems Flashcards
True or False.
A hydropnuematic pump is used to check for air leaks on a dry pipe system
False
Dry pipe valves must have a full trip test every ____ yrs
5 Years
Air pressure maintenance devices must be tested every ____ yrs with the dry pipe trip test
1
the air supply must be able to refill the system within ____ minutes
30 Minutes
True or False.
Records of trip times must be kept for a minimum of 1 yrs after the next test.
False
After testing a dry pipe valve a tag shall be attached that has what information?
-Company name
-Testers Name
-Date of test
When pressure testing a dry pipe system, a loss of ____ psi is acceptable over the duration of the test
3 PSI
The interior of a dry pipe valve must be inspected every ____ yrs
1
Dry sprinklers that have been service for _____ yrs shall be replaced or tested
10 Years
Retesting of dry sprinklers shall occur at _____ yr intervals
10 Years
_____ can be used to prevent issues with condensation
Nitrogen