Impairment Procedures Flashcards
When a fire protection system is out of service for more than ____ hrs at least one of the following shall be provided
-Evacuation of the building of section affected by the OOS system
-An approved fire watch
-Temporary water supply
-a program to eliminate ignition sources and limit the amount of fuel available to the fire
10 Hours
True or False.
When taking a sprinkler system out of service, the following are approved sources of a temporary water supply
-A hose from a fire hydrant to the FDC
-A portable tank and pump
-A standby fire department pumper
True
A 5% degradation in the water supply during a main drain test on an automatic wet standpipe, is considered a _____
Impairment
Impairment procedures for when an impairment will last longer than 10 hours are found in _____
NFPA 25 15.5
Leaking sprinklers is a/an
Impairment
An inadequate concentration of antifreeze is a/an _____
Impairment
A condition that can result in a fire protection system being rendered inoperative during a fire event is a/an _____
Impairment
An anti-vortex plate with a blockage is a/an _____
Impairment
An empty diesel fuel tank for a fire pump is a/an _____
Impairment
When shutting down a system for impairment you must hang a tag at _______
System control valve and the FDC
The minimum size of an impairment tag is _____ in.
4 x 6
When the water temperature of a tank is below 32f it is an _____
Impairment