Island Vents Vent Stacks and Yoke Vents Between DWV Stacks 060301c Flashcards

1
Q

What is the purpose of a vent stack?

A

Limit pressure differentials

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When is a vent stack required?

A

Every soil or waste stack that receives discharge from more than 4 storeys

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the maximum amount of fixture units that may drain into a vent stack?

A

8 fixture units permitted that at least one fixture is connected to a vertical portion of the vent stack upstream of any other fixture

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where must fixtures draining into a vent stack be located?

A

All fixtures must be located in the lowest storey served by the vent stack

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What fixture must be tied in downstream of all other fixtures when drained into a vent stack?

A

Toilet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the minimum size a vent stack may be?

A

Shall not be less than one half the size of the soil or waste stack at its base

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What 2 vents does a yoke vent connect?

A

Soil or waste stack to a vent stack

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When is a yoke vent required on a DWV system?

A

Where a soil or waste stack receives the discharge from fixtures on MORE than 11 storeys

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where are yoke vents installed on a system requiring yoke vents?

A

For each section of 5 storeys counted from the top down OR immediately above each offset or double offset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What distance above floor level must a yoke vent connect to the vent stack?

A

No less than 1 meter above floor level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does the code state concerning fixtures that tie into the vertical portion of a circuit vent, additional circuit vent, offset relief vent or yoke vent?

A

Maximum of 2 fixtures may connect to the vertical section as long as fixtures have a minimum hydraulic load of 1 1/2 FU’s and must be connected symmetricaly by means of a double TY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When is an offset relief vent required in a plumbing system?

A

When the upper vertical section of a soil or waste stack passes through more than 2 storeys and receives a hydraulic load of more than 100 fixture units and has an offset of more than 1.5m

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How must a stack be sized when it has an offset greater than 1.5m?

A

Must be sized as a branch or a building drain

How well did you know this?
1
Not at all
2
3
4
5
Perfectly