How should piping in a trench be supported?
Throughout its entirety
How much cover should be placed over piping in a trench?
12” (300mm)
What is the industry standard for spacing between pipes and the foundation/footing or wall to allow for movement?
6”
Can copper DWV tubing be used underground?
No
What type of copper tube may be used for underground drainage?
Types K and L hard temper
What is the minimum hanger spacing for copper tube less than 1”?
3m (10’)
What is the minimum hanger spacing for copper tube greater than or equal to 1”?
2.5m (8’)
When installing a clevis hanger where should the yoke be located?
On the outside of the U-strap
What form of backflow protection is acceptable on a branch?
Normally closed back water valve
If a pump provides a flow of 10 imperial gallons per minute into a building drain, how many fixture units must you asign to the pump?
10 imp gallons/min x 4.54 litres/imp gallon = 45.4 litres/min
(45. 4 litres/min) / 60 sec/min = 0.76 l/sec
0. 76 litres/sec x 31.7 FU/litre/sec = 24 FU
IF PUMPING INTO COMBINED BUILDING SEWER MULTIPLY BY 900
What is the minimum pressure for a smoke test on DWV?
1” WC
What is the minimum pressure test requirment on potable water in a residential application?
100psi for 2 hours
What is the maximum operating pressure for PVC pipe?
140°F (60°C)
What is the minimum SCH PVC that may be threaded?
SCH80
What is the minimum weight(crush strength) for a cast iron soil pipe used in alberta?
18kN (4000lb)