A minimum of ___ work area outlets with ___ 4-pair cables shall be provided for each work area and should be designed to accommodate moves, adds, and changes (MACs)
2 ; 2
The maximum horizontal cable length shall be ___ m (___ft)
90m ; 295ft
In either the Telco closet or work area, the length of jumpers (including cross-connects) and patch cords should not exceed ___ m or ___ ft.
5m ; 16ft
The “total” length allowed for patch cords and jumpers shall not exceed ___ m (___ ft)
10m ; 33ft
Pair count for backbone/riser cables will be determined by service requirements but shall always include a minimum of ___ % spare pairs.
50 %
Installation standards shall be in accordance with _____ ____ series
ANSI/TIA-568
Preferred method of cable routing will be via ___ ___ / ____ ____ for major cable paths.
cable tray / ladder racks
The default cable routing for minor cable paths will be via ______ capable of supporting ___ lbs at a a maximum of __ ft.
J-Hooks ; 2.2 lbs ; 5 ft
A minor cable path is defined as paths consisting of __ individual __- pair cables or less.
16 ; 4-pair
Patch panels may be ___ or ___ port configurations
24 or 48
What is the only installation that braided cable is authorized for punch down block termination?
Speak cable associated with PA installation
What is the pin configuration for 8-position WAOs supporting universal T568-A standards?
P1: WG/G
P2: WO/BL
P3: WBL/O
P4: WBR/BR
Due to technical advances, what should be considered the primary solution over copper for new campuses?
Fiber-to-the-Desktop (FTTD)
ST or SC duplex connector panels supporting 12 strands per panel are used for shore-side _________________ installations.
UNCLASSIFIED
LC keyed and color-coded panels are required for all shore-side ____________ installations.
CLASSIFIED
The ________ and _________ strands are NOT terminated at both ends and shall be left at length (not cut back) as spares.
white and slate
A minor fiber cable pathway is defined as those paths consisting of ___ individual cables or less.
7
Fiber panels should be limited to ___ ports maximum.
72
A minimum of ___ permanent links shall be provided for each work area.
two