Important Systems Flashcards

1
Q

How long are the 250 VDC Plant Batteries expected to last during a Loss of Off-site Power?

A

3 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How long are the 250 VDC Plant Batteries expected to last during a Station Blackout?

A

4 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If the CRID is being powered from CRP-3, what’s the status of the CRID Bus?

A

Inoperable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the bus and Trains for the CRIDs?

A

CRID 1 - C
CRID 2 - D
CRID 3 - A
CRID 4 - B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What does it mean when the NSYNC Light goes out?

A

The alt source of power is gone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the normal power supply to the CRIDs?

A

250 V DC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the autostarts for the MDAFPs?

A

Both MFPs Trip (w control switch in auto)

AMSAC

Loadshed

Lo-Lo SG Level (1 SG)

SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the TDAFP Auto Stared?

A

Undervoltage on RCP Bus

SG Lo-Lo (2 SGs)

AMSAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does the AMSAC Signal do?

A

Trips the Turbine and Starts all AFW pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the TS Minimum and Basis of the CST?

A

182,000 gals (44%)

Maintains plant in hot standby for 9 hours onPORVs w LOOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the 3 autostarts of the CCW Pumps?

A

SI

Loadshed

Low discharge pressure (80#)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What does a high rad signal do for CCW?

A

Auto closes surge tank vent valve CRV-412

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

On an SI, what flow do the RHR Hx CCW Outlet valves throttle to?

A

3000-3500 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What CCW Systems isolate on a Phase A?

A

SFP Hx

Excess LD

Rx Support Cooler

NBAE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the ESF Loads for CCS?

A
RHR Hx
RHR pp Seal Hx
CTS pp Seal Hx
SI pp LO 
SI pp Seal Hx
CCP LO Cooler
CCP Speed Increaser
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Does the control air compressor have a loadshed trip?

A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What are the key pressures of the plant and control air systems?

A

100 # - Normal

95# - Standy PAC Stars

90# - CAC Starts (sensed in wet air receiver)

85# - PA Hdr Isolation Valves Close

80# - Manual Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Which Rad monitors will close the 100 series valves (inside containment) and trip the IR Purge supply fan?

A

Train A 00 Odd Rad Monitors (ex: 1300)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Which Rad Monitors will close the 200 series valves (outside containment) and trip the majority of the ventilation supply fans?

A

Train B- Even Rad Monitors (Ex: 1400)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What are the Tech Spec Limits for upper and Lower Containment?

A

Upper: 60-100*F

Lower: 60-120*F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What are the Tech Spec Pressure limits for containment? And what must be done if outside limits?

A
  • 1.5 to +0.3 psig

* Restore within limits within 1 hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What signal stats the CTS Pumps?

A

Phase B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What signal opens the CTS Pump Discharge valves and the SAT Outlet Valves?

A

CTS Signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What are the key levels and associated actions of QLC-451 for the VCT?

A

2.5% - Low-Low Alarm and half RWS signal

14% - Auto Makeup Starts + Low Alarm + MU Not in Auto Alarm

24% - Auto Makeup Stops

87% - Divert Trips Open + High Alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
What are the key levels and associated actions of QLC-452 for the VCT?
2.5% - VCT LO-LO Alarm + 1/2 of RWS signal 7% - Low Alarm 78% Divert Starts 87% Divert Stops
26
What happens in the CVCS on a phase A Signal?
LD Orifice Valves CLose LD CIVs Close Seal Return Valves CLose CCW to XS LD Hx
27
WHat happens in the SVCS on a SI Signal?
Charging Hdr Iso Valves Close CCW to LD Hx Closes CCP Recircs Close and throttle based on pressure CCP Suction realigns to RWST BIT Valves Open CCP Starts
28
During an Emergency Boration, what must be done with the BAT Pumps?
Manually shifted to FAST Speed
29
What is the pressure input for QMO-225, East CCP ELO?
NPP-155 1812-1825#
30
What is the pressure input for the West CCP ELO?
NPP-153 1812-1825#
31
What must be done if your SDM is outside the COLR limits?
M2 w Keff <1 M2-5 Borate to restore in 15 mins
32
What are the Tech Spec Limits for the RWST?
375,500 gals 2400-2600 ppm boron 70-100*F
33
What is the ECCS Acceptance Criteria?
Peak Clad Temp - < 2200*F Max Cladding Oxidation - < 17% H2 Generation - < 1% Core maintains a coolable geometry Long term abundant cooling
34
What are the EDG Trips when needed for a SI or a LOOP with 250 VDC available?
Generator Phase Differential Electronic Overspeed Manual Push Button
35
What are the EDG Trips without 250 VDC available?
Manual Fuel Valve on the Worthington module Mechanical Overspeed
36
If the EDG Electronic governor fails high, what happens?
EDG Speed will rise and machine will be controlled by the mechanical governor eventually
37
What is the status of the EDG during surveillance testing and why?
Inoperable bc it will not generate a loadshed signal
38
What happens if control air is lost to the EDG?
Throttle control cycle deer extends, forcing the fuel racks closed
39
What is the normal status of breaker BD?
OPEN
40
What does TR-5 supply?
Train B reserve feed for both units
41
What does TR-9 supply?
Train A Reserve Feed for both units
42
125 VDC supplies what?
Breaker / control power for the switchyard. EACH YARD HAS ITS OWN 125 VDC SUPPLY
43
What is TR-12-EP-1 designed to handle?
CTS in 1 unit and SBO in both units
44
What is the SDG sized for?
1 train of RCS Inventory Control in 1 unit ESW, CCW, CCP, AFW, NESW, CAC
45
What does the anti-pumping circuit do?
Prevents breaker from attempting a second closure w a standing close signal when the first attempt was followed by a trip open signal
46
Explain degraded bus voltage.
2/3 T busses sensed 113 V (ONLY sensed on A + D busses) 9 sec delay w SI / SG LO-LO opens T buse feeders + 90 sec auto transfer to RATS +21 secs open T bus Feeders Train Specific Opens BOTH RCP Bus Ties for associated train
47
Explain Load Shed (UV)
2/3 sensed on EACH T-bus @ 94 (93) volts 2 second delay and bus specific
48
What are the ESW pump auto starts
SI (either unit, train specific Load shed Low hdr pressure - 40# (auto only)
49
What do the ESW from CCW Hx valves throttle to on a SI
~5500 gpm Adjustments can be made after the valves throttle if necessary
50
What are the MFP Trips
Manual Rx Trip SI Hi Hi SG Level IPS Thrust Bearing Wear
51
What do the instrument power fuses power? When do they trip?
Instrument Power Supplies Always trip unless bypassed or blocked
52
What do Control Power fuses power? And when do they cause a trip?
Bistables Always unless blocked
53
What kind of detectors are the SR Detectors?
BF3 Proportional Counters
54
What kinda of detectors are the IR Detectors?
Compensated Ion Chamber
55
What kind of detectors are the PR detectors?
Uncompensated Ion Chamber
56
What kind of detectors are the gammametrics?
Fission Chamber (U235)
57
Where can N-23, SR Gammametrics be read? What powers it?
Control Room or LSI-4 Opposite Units CRID 3
58
What happens if your IR Detector is undercompensated?
Gives a false High Indication. Can cause IR current to stay above the P6 setpoint when coming down in power, which will prevent the SR Detectors from Auto energizing
59
What must be done if your AFD is not within Target band?
Restore within 15 mins If not met, restore to within upper limit (90%) within 15 mins
60
What must be done if you’re outside the acceptable band at 80% power?
Reduce to 50% power in 30 mins
61
What are the normal parameters of the PRT?
100*F 83% Level 3 #
62
PORV Cold Overpressure: NRV-152 is controlled by?
NPS-122 (Loop 1 WR)
63
PORV Cold Overpressure: NRV-153 is controlled by?
NPS-121, Loop 2 WR
64
When do the PRZ Backup Heaters trip?
Loadshed PRZ Low Level at 17% (hot cal) Over current
65
What is the PRZ Pressure Safety Limit?
2735 psig
66
What happens if a PRZ Level Control Channel Fails Low?
QRV-251 throttles open to increase level LD Isolates (QRV-112 + all orifices) PRZ Htrs Off Rx Trips at 92%
67
What happens if PRZ Level Bistable channel fails Low?
LD Isolates (QRV-111) PRZ Htrs Off PR Pressure Decreases due to heaters being off Actual level increases, charging to min Rx Trips at 92%
68
What happens if the PRZ Level control channel fails high?
QRV-251 throttles closed to lower level PRZ Htrs com on (+5% deviation) Actual Level decreases and at 17%, Orific isolation valves close, QRV-111 closes, and heaters turn off Actual Level increases (min charging w no let down) Rx Trips at 92%
69
What happens if PRZ Level Bistable channel fails high?
NOTHING!
70
What happens if PRZ Pressure Controlling channel fails high?
All PRZ Htrs Off Sprays full open 1/2 signal for NRV-152 present Actual PRZ Pressure decreases
71
WHat happens if PRZ Pressure Controlling channel fails low?
Backup eaters in auto will turn on Cycling Htrs full on Actual PRZ Pressure rises NRV-152 is inoperable If channel 3 was in control. ALL PORVS inoperable
72
What happens if the PRZ Pressure bistable channel fails high?
1/2 actuation signals present for NRV-151 and 153 present
73
What happens if the PRZ Pressure bistable channel fails low?
NRV-151 + 153 inoperable If channel 4 was the bistable, then ALL PORVs are inoperable
74
What are the interlocks for starting a RCP?
Bearing Lift Pump running Bearing Lift Oil Pressure 510#
75
What are the RCP Power supplies?
1 - B 2 - C 3- D 4 - A
76
Assuming 8 gpm Seal Injection, what is the seal injection flowpath?
5 gpm flows down RCP Shaft into the RCS 3 gpm flows up thru #1 seal 3 gpm flows up thru #2 seal 100 cc/hr flows up thru #3 seal
77
What is the RCP Seal Return Flowpath?
#1 Seal - Seal Water Hx to CCP Suction #2 Seal - RCP Standpipe and to RCDT #3 Seal - RCDT
78
Which RVLIS is used when filling and venting the RCS with the RCP Bump Method?
Upper Plenum, with RCPs off
79
What is used for the Subcooling Meter Calc?
Auctioneered HI CETCs or WR RTD Temps Auctioneered LO RVLIS Pressure (used bc outside containment)
80
What is the heat up limit?
60*F per hour
81
What is the Cooldown limit?
100*F / hr
82
What are the interlocks to open ICM-305/306, RHR Suction from the Recirc Sump?
IMO-310, RHR Suction Valves - Closed IMO-215, RWST to CTS Pump - Closed
83
What are the interlocks to open IMO-340, RHR to CCP / SI Suction?
ICM-305, RHR Suction from Recirc Sump - Open IMO-252 or IMO-263, SI Recirc to RWST - Closed
84
What are the interlocks to Open IMO-330, RHR to Upper Spray?
ICM-305, RHR Suction from Recirc - OPEN
85
What are the interlocks to open IMO-310, RHR Suction Valves?
ICM-305, RHR Suction from Recirc Sump - Closed IMO-340, RHR to CCP / SI Suction - Closed IMO-330, RHR to upper Spray - Closed
86
What happens on a high rad on R-5 or VRS-5005/5006, SFP Area Rad Monitors?
Trips AFS Fans Puts AFX Fan in charcoal mode
87
What happens on a high rad on R-19 + R-24, Blowdown Rad monitor?
Closes Blowdown DCRs Closes BD Sample DCRs Closes DRV-350 Trips BD Treatment pump (R-24 ONLY)
88
What happens on a high rad on the liquid effluent Rad Monitor RRS-1001?
Closes RRV-285 Monitor Tank Pumps Trip WECT Pumps Trip
89
What does a high alarm on the SJAE and GSLO rad monitors mean?
Possible SGTR on EITHER unit (based on which unit is supplying aux steam)
90
What happens on a high rad signal on the vent effluent Rad Monitor VRS-1500/2500?
RRV-306 closes (low range 1505)
91
What happens on a High Rad on the CR Area rad monitors ERS-7401 / 8401?
Starts THAT UNIT Control Room Pressurization Fan Dampers realign
92
How many SG PORV Rad Monitors and Detectors are there?
2 Monitors, 4 detectors
93
A logic cabinet urgent failure effects which rods?
ALL Rods
94
A Power cabinet Urgent Failure affects which Rods?
Groups for that specific cabinet
95
While restoring a mis-aligned Rod, while will a urgent failure be generated?
In other bank of rods in that power cabinet due to all lifetime coil disconnect switches being open for that entire group
96
Loss of redundant power to power or logic cabinets for control rods is what kind of failure?
Non Urgent
97
What powers Rod Bottom Lights?
CRP-3
98
How fast do rods move in manual?
48 spam
99
How fast do rods move in auto?
8-72 spm Error 1/5*-3*F, 8 spm Error 3-5*F, 32 steps per degree +8
100
How fast do rods move for shutdown banks in manual?
62 spm
101
If a PR NI fails high, what is the effect on rods?
Power Rate of change causes rods to step in, but rod stop C2 will prevent rods from stepping back out on the temperature error in both auto and manual
102
How will a PR NI low failure affect rods?
No effect unless affected instrument was previously the auctioneered high
103
How will MPC-253 failing high affect Rods?
Power Rate of change and Tavg < Tref causes rods to step out
104
How will MPC-253 failing low affect Rod?
Power Rate of change and Tavg > T ref causes rods to step in
105
How will Tavg failing high affect Rods?
Tavg > Tref causes rods to step in
106
Will cross-tying SFP Cooling thru the purification piping prevent boiling?
No, it will delay it
107
For SSPS, loss of both 15 VDC OR both 48 VDC power supplies does what?
Generated Rx Trip
108
CRID 1 supplies which train of slave relays?
A
109
CRID 4 supplies which train of slave relays?
B
110
A loss of CRIDs 1 or 4 prevents what?
Actuation of ESF equipment on that associated train
111
For SSPS Bistable Test Switches, what does it do for the logic?
Gives SSPS the trip signal
112
What is unique with CTS Bistables?
Bypassed instead of placed in test, to ensure we don’t have an inadvertent CTS
113
When the RPS Bypass switches are in bypass, what happens?
Never get a trip signal
114
Do RX Trip Bypass breakers have Shunt coils?
NO
115
How do the Rx Trip Breakers Trip Coils work?
Energized to trip
116
How do the Rx Trip Breakers UV Coils work?
De-Energized to Trip (48 VDC from SSPS) Do NOT Need control power
117
How do the Rx Trip Breakers Shunt Coils work?
Energize to Trip
118
What are the inputs for OT delta T?
Delta T Tave AFD PRZ Press
119
What does OT Delta T Protect from?
DNB
120
What are the inputs for OP delta T?
Delta T Tave
121
What does OP delta T protect from?
KW/ft
122
What is the turbine trip / load rejection steam dump controlled based on?
Auctioneered high Tavg
123
What is C-7A?
10% load rejection on MPC-254
124
What is C-7B?
30% Load rejection on MPC-254
125
What is C-8?
TT Arming Signal 4/4 MT SV Closed OR 2/3 Oil Pressure switches below 800 psig
126
What is C-9?
Blocking Signal: 1 CW Pump CRID 2 3/3 Condensers >20.6” hg
127
What is P-12?
Blocking Signal 2/4 Tavg < 541*F Blocks steam dump until placed in Bypass Interlock
128
What does Steam Dump Bypass Interlock do?
Allows group 1 operation below P-12
129
For the TT Controller, what are the temperature differences for each group to be tripped open?
10*F - 1 group 20*F - 2 groups
130
What is T no load?
547*F
131
How many groups of steam dumps will you get maximum on a turbine trip?
2 groups
132
How many groups of steam dumps will you get maximum on a Load Rejection?
3 groups
133
What is C-20?
2/2 Turbine Impulse Pressures > 40%
134
What is needed for an AMSAC Actuation?
3/4 FF < 25%
135
What is SG Shrink caused by?
Reduction in Steam flow
136
What is SG Swell Caused by?
Raised Steam Flow
137
What are the operational Modes based on?
Keff % Rated Thermal Power RCS Tavg
138
WHat are the 6 modes of operation?
1 - Power Operation. Keff >/= 0.99, >5% Thermal Power 2- Startup. Keff >/= 0.99, =5% Thermal Power 3- Hot Standby. Keff <0.99, Tavg >/= 350*F 4- Hot Shutdown. Keff <0.99, Tave between 200-350*F 5- Cold Shutdown. Keff <0.99, Tavg =200*F 6- Refueling.
139
What are the auto-starts for an AES Fan?
ECCS/CTS Pump Start | SI
140
What will happen on a loss of BOTH Unit 1 AX Fans?
12-RRV-306 closes
141
What starts the CCW Pump Fans?
Manual Load Cons
142
What will place the AES Charcoal Filter I/S?
Phase B (either Train) AES Fan C/S in Stop (that fan only) Loss of power to EITHER AES Fan Loss of Control Air
143
What will place the AFX Charcoal Filter I/S?
SFP High Rad / Airborne Loss of power to EITHER fain Loss of Control air
144
What fans trip on Phase B?
CLVs CRDM Fans PRZ Fans Rx Cavity Fans
145
What will start ALL CRP Fans?
SI in either unit
146
What will the CRP fan damper positions be for a cable vault fire?
CRAC Outside Supply 1/1A- Closed CREV Outside Supply 2/2A- Part Open for 1, other is closed CR Recirc 3 - Closed
147
What will be affected if a PR detector fails low?
OTDT setpoint will lower
148
Will a high rad signal place an AES Fan charcoal filter in service?
No. This must be done manually
149
If a 1 RCS Loop flow lowers in comparison to all others, what would the result be?
Reactor core margin to DNB will be lower
150
If the EDG Emergency Trip pushbutton is inadvertently pressed in the control room while the EDG is actually needed, how must you restart it?
Reset the HEA Relay in the control room
151
The primary function of the Ice Condenser is to ____________ to less than the design limit following a ________ or a _______
Limit peak pressure following a LOCA or a Steam Line Break
152
What does the TDAFP Discharge Flow High Alarm mean?
AFW Flow Retention has actuated
153
If control power is lost to a closed in pump breaker, can you trip the breaker from the control room? Will automatic trip functions work?
NO! Only tripped locally Automatic trips are NOT overable
154
Where does the PRT vent to and what is the interlock?
Waste Gas Header Pressure must be < 10 psig
155
What modes must 4 accumulators be operable?
M1 and M2 M3 > 1000#
156
What are the Tech Spec limits for Accumulator volume, pressure and boron?
Volume - 921-751 cubic feet Pressure - 585-658 psig Boron - 2400-2600 ppm
157
Why do operators care about the SAT LO-LO Level alarm during a LOCA?
The spray add tank outlet valves and educator supply valves may not have closed automatically. This could cause damage to the CTS Pumps due to the resulting gas addition
158
What’s the flow path that would detect a SG tube leak thru Gland Steam Condenser Vent Rad monitor?
A PORTION of the fission products will be monitored before being transmitted to atmosphere, as only a sample flow passes thru SRA-1800
159
Can the Backup Plant Air Compressor feed both unit’s control air headers?
Yes, it wil discharge to both unit’s CA Systems
160
With refueling in progress, SR audible count rate has became inoperable in both containment and in the control room. What is the TS action required for these conditions?
IMMEDIATELY initiate actions to isolate unborated water sources to the RCS
161
What will cause a monitor tank pump to trip during a liquid release?
RRS-1001, Hi Rad RRS-1000, Failure RFS-1010/1011, High / Low Rad Monitor Sample Flow Low Monitor Tank Level, if selected
162
What is the power supply for H2 Recombiners?
Recombiner 1: 11B (21B) | Recombiner 2: 11C (21C)
163
What are the Tech Spec Parameters for the RWST? Volume, Boron concentration, and Temp
Volume - 375,500 gals Boron - 2400-2600 ppm Temp - 70-100*F
164
Do both reactor trip breakers and reactor trip bypass breakers have shut coils?
NO- Only Rx Trip Breakers do
165
What are the key numbers for Generator frequency?
>59 Hz, unlimited operating time < 59 Hz but > 58.2 Hz, reduce power to approx. 50 MWe within 30 mins and open generator output breakers = 58.2 Hz, Immediately Trip the Rx
166
What will trip closed 12-RRV-306
- Loss of both U1 Aux Bldg Exhaust Fans | - High Rad on U1 or U2 Vent Stack Rad Monitors VRS-1500/2500
167
What happens if during poer escalation, you exceed 60% power (and 626 MW) with only 1 FP I/S?
When you exceed 626 MW, a runback will initiate
168
Is the CCW thermal barrier isolation valve common to all RCPs? Or does each have its own?
Common to ALL
169
If CCW to the RCP thermal barrier is lost, must you trip the affected RCPs?
NO, as long as it has seal injection maintained
170
To calculate MFP DP, what are the inputs used?
Highest of the low pressure (steam) and Lowest of the high pressure (FW)
171
What can force a MFP to speed control?
Both MS Press Xmitters Fail Both MFP Hdr Press Xmitters Fail MFP dP Setpoint Xmitter Fails Other MFP Trips when > 60% Power MFP Speed > 5220 (5300) rpm
172
What is the Tech Spec limit for the EDG Day Tank Level?
101.4 gallons
173
If you receive a high alarm on VRS-1505, AB Ventilation Noble Gas Activity Monitor while containment Purge System is in Ventilation Mode, what must be done?
Stop Purge and talk w RP Auto isolation signals are blocked while in ventilation mode
174
How do the RHR Hx Outlet valves (IRV-320 and IRV-310) fail on a loss of air?
Open! This raises flow thru the Hx, raising the cooldown rate
175
If CRID 1 is lost, what happens?
Train A SSPS output relays won’t work. Manual red switches will not work to actuate SI.
176
When an RCP Trips, how do Thot and Tcold respond in that loop?
Reverse flow causes Thot to drop to the Tcold value or slightly below T cold remains about the same at low power
177
Which CRID does NOT supply power to the Steam Dump System?
CRID 3
178
What would cause a load cons signal to be generated for the CD EDG?
Train A SI with a LOOP/Loadshed
179
What will cause 12-RRV-285 to trip?
RRS-1001 Hi Rad RRS-1000 Failure High & Low Radiation Monitor Sample Flow (RFS-1010, RFS-1011)
180
What will cause RRV-286/287 to trip?
NO Circ Water Pumps are running in associated unit