Important Systems Flashcards

1
Q

How long are the 250 VDC Plant Batteries expected to last during a Loss of Off-site Power?

A

3 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How long are the 250 VDC Plant Batteries expected to last during a Station Blackout?

A

4 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the bus and Trains for the CRIDs?

A

CRID 1 - C
CRID 2 - D
CRID 3 - A
CRID 4 - B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal power supply to the CRIDs?

A

250 V DC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the autostarts for the MDAFPs?

A

Both MFPs Trip (w control switch in auto)

AMSAC

Loadshed

Lo-Lo SG Level (1 SG)

SI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the TDAFP Auto Stared?

A

Undervoltage on RCP Bus

SG Lo-Lo (2 SGs)

AMSAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does the AMSAC Signal do?

A

Trips the Turbine and Starts all AFW pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the 3 autostarts of the CCW Pumps?

A

SI

Loadshed

Low discharge pressure (80#)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

On an SI, what flow do the RHR Hx CCW Outlet valves throttle to?

A

3000-3500 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What CCW Systems isolate on a Phase A?

A

SFP Hx

Excess LD

Rx Support Cooler

NBAE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the ESF Loads for CCS?

A
RHR Hx
RHR pp Seal Hx
CTS pp Seal Hx
SI pp LO 
SI pp Seal Hx
CCP LO Cooler
CCP Speed Increaser
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Does the control air compressor have a loadshed trip?

A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the key pressures of the plant and control air systems?

A

100 # - Normal

95# - Standy PAC Stars

90# - CAC Starts (sensed in wet air receiver)

85# - PA Hdr Isolation Valves Close

80# - Manual Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What signal stats the CTS Pumps?

A

Phase B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What signal opens the CTS Pump Discharge valves and the SAT Outlet Valves?

A

CTS Signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the key levels and associated actions of QLC-451 for the VCT?

A

2.5% - Low-Low Alarm and half RWS signal

14% - Auto Makeup Starts + Low Alarm + MU Not in Auto Alarm

24% - Auto Makeup Stops

87% - Divert Trips Open + High Alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What are the key levels and associated actions of QLC-452 for the VCT?

A

2.5% - VCT LO-LO Alarm + 1/2 of RWS signal

7% - Low Alarm

78% Divert Starts

87% Divert Stops

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

WHat happens in the SVCS on a SI Signal?

A

Charging Hdr Iso Valves Close
CCW to LD Hx Closes
CCP Recircs Close and throttle based on pressure

CCP Suction realigns to RWST

BIT Valves Open

CCP Starts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the pressure input for QMO-225, East CCP ELO?

A

NPP-155

1812-1825#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What is the pressure input for the West CCP ELO?

A

NPP-153

1812-1825#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the ECCS Acceptance Criteria?

A

Peak Clad Temp - < 2200*F

Max Cladding Oxidation - < 17%

H2 Generation - < 1%

Core maintains a coolable geometry

Long term abundant cooling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What are the EDG Trips when needed for a SI or a LOOP with 250 VDC available?

A

Generator Phase Differential

Electronic Overspeed

Manual Push Button

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What are the EDG Trips without 250 VDC available?

A

Manual Fuel Valve on the Worthington module

Mechanical Overspeed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

If the EDG Electronic governor fails high, what happens?

A

EDG Speed will rise and machine will be controlled by the mechanical governor eventually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What is the status of the EDG during surveillance testing and why?

A

Inoperable bc it will not generate a loadshed signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

What happens if control air is lost to the EDG?

A

Throttle control cycle deer extends, forcing the fuel racks closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

What is the normal status of breaker BD?

A

OPEN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

125 VDC supplies what?

A

Breaker / control power for the switchyard. EACH YARD HAS ITS OWN 125 VDC SUPPLY

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

What is TR-12-EP-1 designed to handle?

A

CTS in 1 unit and SBO in both units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

What is the SDG sized for?

A

1 train of RCS Inventory Control in 1 unit

ESW, CCW, CCP, AFW, NESW, CAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

What does the anti-pumping circuit do?

A

Prevents breaker from attempting a second closure w a standing close signal when the first attempt was followed by a trip open signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

Explain degraded bus voltage.

A

2/3 T busses sensed 113 V (ONLY sensed on A + D busses)

9 sec delay w SI / SG LO-LO opens T buse feeders

+ 90 sec auto transfer to RATS

+21 secs open T bus Feeders

Train Specific

Opens BOTH RCP Bus Ties for associated train

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

Explain Load Shed (UV)

A

2/3 sensed on EACH T-bus @ 94 (93) volts

2 second delay and bus specific

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

What are the ESW pump auto starts

A

SI (either unit, train specific

Load shed

Low hdr pressure - 40# (auto only)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

What do the ESW from CCW Hx valves throttle to on a SI

A

~5500 gpm

Adjustments can be made after the valves throttle if necessary

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

What do the instrument power fuses power? When do they trip?

A

Instrument Power Supplies

Always trip unless bypassed or blocked

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q

What do Control Power fuses power? And when do they cause a trip?

A

Bistables

Always unless blocked

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q

What happens if your IR Detector is undercompensated?

A

Gives a false High Indication. Can cause IR current to stay above the P6 setpoint when coming down in power, which will prevent the SR Detectors from Auto energizing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

What are the normal parameters of the PRT?

A

100*F

83% Level

3 #

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
40
Q

PORV Cold Overpressure: NRV-152 is controlled by?

A

NPS-122 (Loop 1 WR)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
41
Q

When do the PRZ Backup Heaters trip?

A

Loadshed

PRZ Low Level at 17% (hot cal)

Over current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
42
Q

What is the PRZ Pressure Safety Limit?

A

2735 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
43
Q

What happens if a PRZ Level Control Channel Fails Low?

A

QRV-251 throttles open to increase level

LD Isolates (QRV-112 + all orifices)

PRZ Htrs Off

Rx Trips at 92%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
44
Q

What happens if PRZ Level Bistable channel fails Low?

A

LD Isolates (QRV-111)

PRZ Htrs Off

PR Pressure Decreases due to heaters being off

Actual level increases, charging to min

Rx Trips at 92%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
45
Q

What happens if the PRZ Level control channel fails high?

A

QRV-251 throttles closed to lower level

PRZ Htrs com on (+5% deviation)

Actual Level decreases and at 17%, Orific isolation valves close, QRV-111 closes, and heaters turn off

Actual Level increases (min charging w no let down)

Rx Trips at 92%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
46
Q

What happens if PRZ Level Bistable channel fails high?

A

NOTHING!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
47
Q

What happens if PRZ Pressure Controlling channel fails high?

A

All PRZ Htrs Off

Sprays full open

1/2 signal for NRV-152 present

Actual PRZ Pressure decreases

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
48
Q

WHat happens if PRZ Pressure Controlling channel fails low?

A

Backup eaters in auto will turn on

Cycling Htrs full on

Actual PRZ Pressure rises

NRV-152 is inoperable

If channel 3 was in control. ALL PORVS inoperable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
49
Q

What happens if the PRZ Pressure bistable channel fails high?

A

1/2 actuation signals present for NRV-151 and 153 present

50
Q

What happens if the PRZ Pressure bistable channel fails low?

A

NRV-151 + 153 inoperable

If channel 4 was the bistable, then ALL PORVs are inoperable

51
Q

What are the RCP Power supplies?

A

1 - B

2 - C

3- D

4 - A

52
Q

Assuming 8 gpm Seal Injection, what is the seal injection flowpath?

A

5 gpm flows down RCP Shaft into the RCS

3 gpm flows up thru #1 seal

3 gpm flows up thru #2 seal

100 cc/hr flows up thru #3 seal

53
Q

What is the RCP Seal Return Flowpath?

A

1 Seal - Seal Water Hx to CCP Suction

54
Q

What is used for the Subcooling Meter Calc?

A

Auctioneered HI CETCs or WR RTD Temps

Auctioneered LO RVLIS Pressure (used bc outside containment)

55
Q

What are the interlocks to open ICM-305/306, RHR Suction from the Recirc Sump?

A

IMO-310, RHR Suction Valves - Closed

IMO-215, RWST to CTS Pump - Closed

56
Q

What are the interlocks to open IMO-340, RHR to CCP / SI Suction?

A

ICM-305, RHR Suction from Recirc Sump - Open

IMO-252 or IMO-263, SI Recirc to RWST - Closed

57
Q

What are the interlocks to Open IMO-330, RHR to Upper Spray?

A

ICM-305, RHR Suction from Recirc - OPEN

58
Q

What are the interlocks to open IMO-310, RHR Suction Valves?

A

ICM-305, RHR Suction from Recirc Sump - Closed

IMO-340, RHR to CCP / SI Suction - Closed

IMO-330, RHR to upper Spray - Closed

59
Q

A logic cabinet urgent failure effects which rods?

A

ALL Rods

60
Q

A Power cabinet Urgent Failure affects which Rods?

A

Groups for that specific cabinet

61
Q

Loss of redundant power to power or logic cabinets for control rods is what kind of failure?

A

Non Urgent

62
Q

How fast do rods move in auto?

A

8-72 spm

Error 1/5-3F, 8 spm

Error 3-5*F, 32 steps per degree +8

63
Q

How fast do rods move for shutdown banks in manual?

A

62 spm

64
Q

If a PR NI fails high, what is the effect on rods?

A

Power Rate of change causes rods to step in, but rod stop C2 will prevent rods from stepping back out on the temperature error in both auto and manual

65
Q

How will a PR NI low failure affect rods?

A

No effect unless affected instrument was previously the auctioneered high

66
Q

How will MPC-253 failing high affect Rods?

A

Power Rate of change and Tavg < Tref causes rods to step out

67
Q

How will MPC-253 failing low affect Rod?

A

Power Rate of change and Tavg > T ref causes rods to step in

68
Q

How will Tavg failing high affect Rods?

A

Tavg > Tref causes rods to step in

69
Q

For SSPS, loss of both 15 VDC OR both 48 VDC power supplies does what?

A

Generated Rx Trip

70
Q

CRID 1 supplies which train of slave relays?

A

A

71
Q

CRID 4 supplies which train of slave relays?

A

B

72
Q

A loss of CRIDs 1 or 4 prevents what?

A

Actuation of ESF equipment on that associated train

73
Q

For SSPS Bistable Test Switches, what does it do for the logic?

A

Gives SSPS the trip signal

74
Q

What is unique with CTS Bistables?

A

Bypassed instead of placed in test, to ensure we don’t have an inadvertent CTS

75
Q

When the RPS Bypass switches are in bypass, what happens?

A

Never get a trip signal

76
Q

Do RX Trip Bypass breakers have Shunt coils?

A

NO

77
Q

How do the Rx Trip Breakers Trip Coils work?

A

Energized to trip

78
Q

How do the Rx Trip Breakers UV Coils work?

A

De-Energized to Trip (48 VDC from SSPS)

Do NOT Need control power

79
Q

How do the Rx Trip Breakers Shunt Coils work?

A

Energize to Trip

80
Q

What are the inputs for OT delta T?

A

Delta T

Tave

AFD

PRZ Press

81
Q

What does OT Delta T Protect from?

A

DNB

82
Q

What are the inputs for OP delta T?

A

Delta T

Tave

83
Q

What does OP delta T protect from?

A

KW/ft

84
Q

What is the turbine trip / load rejection steam dump controlled based on?

A

Auctioneered high Tavg

85
Q

What is C-7A?

A

10% load rejection on MPC-254

86
Q

What is C-7B?

A

30% Load rejection on MPC-254

87
Q

What is C-8?

A

TT Arming Signal

4/4 MT SV Closed

OR

2/3 Oil Pressure switches below 800 psig

88
Q

What is C-9?

A

Blocking Signal:

1 CW Pump

CRID 2

3/3 Condensers >20.6” hg

89
Q

What is P-12?

A

Blocking Signal

2/4 Tavg < 541*F

Blocks steam dump until placed in Bypass Interlock

90
Q

What does Steam Dump Bypass Interlock do?

A

Allows group 1 operation below P-12

91
Q

For the TT Controller, what are the temperature differences for each group to be tripped open?

A

10*F - 1 group

20*F - 2 groups

92
Q

How many groups of steam dumps will you get maximum on a turbine trip?

A

2 groups

93
Q

How many groups of steam dumps will you get maximum on a Load Rejection?

A

3 groups

94
Q

What is C-20?

A

2/2 Turbine Impulse Pressures > 40%

95
Q

What is needed for an AMSAC Actuation?

A

3/4 FF < 25%

96
Q

What are the auto-starts for an AES Fan?

A

ECCS/CTS Pump Start

SI

97
Q

What will happen on a loss of BOTH Unit 1 AX Fans?

A

12-RRV-306 closes

98
Q

What starts the CCW Pump Fans?

A

Manual

Load Cons

99
Q

What will place the AES Charcoal Filter I/S?

A

Phase B (either Train)

AES Fan C/S in Stop (that fan only)

Loss of power to EITHER AES Fan

Loss of Control Air

100
Q

What will place the AFX Charcoal Filter I/S?

A

SFP High Rad / Airborne

Loss of power to EITHER fain

Loss of Control air

101
Q

What fans trip on Phase B?

A

CLVs

CRDM Fans

PRZ Fans

Rx Cavity Fans

102
Q

What will start ALL CRP Fans?

A

SI in either unit

103
Q

What will the CRP fan damper positions be for a cable vault fire?

A

CRAC Outside Supply 1/1A- Closed

CREV Outside Supply 2/2A- Part Open for 1, other is closed

CR Recirc 3 - Closed

104
Q

What will be affected if a PR detector fails low?

A

OTDT setpoint will lower

105
Q

Will a high rad signal place an AES Fan charcoal filter in service?

A

No. This must be done manually

106
Q

If a 1 RCS Loop flow lowers in comparison to all others, what would the result be?

A

Reactor core margin to DNB will be lower

107
Q

If the EDG Emergency Trip pushbutton is inadvertently pressed in the control room while the EDG is actually needed, how must you restart it?

A

Reset the HEA Relay in the control room

108
Q

The primary function of the Ice Condenser is to ____________ to less than the design limit following a ________ or a _______

A

Limit peak pressure

following a LOCA or a Steam Line Break

109
Q

What does the TDAFP Discharge Flow High Alarm mean?

A

AFW Flow Retention has actuated

110
Q

Where does the PRT vent to and what is the interlock?

A

Waste Gas Header

Pressure must be < 10 psig

111
Q

Why do operators care about the SAT LO-LO Level alarm during a LOCA?

A

The spray add tank outlet valves and educator supply valves may not have closed automatically. This could cause damage to the CTS Pumps due to the resulting gas addition

112
Q

Can the Backup Plant Air Compressor feed both unit’s control air headers?

A

Yes, it wil discharge to both unit’s CA Systems

113
Q

Do both reactor trip breakers and reactor trip bypass breakers have shut coils?

A

NO- Only Rx Trip Breakers do

114
Q

Is the CCW thermal barrier isolation valve common to all RCPs? Or does each have its own?

A

Common to ALL

115
Q

If CCW to the RCP thermal barrier is lost, must you trip the affected RCPs?

A

NO, as long as it has seal injection maintained

116
Q

To calculate MFP DP, what are the inputs used?

A

Highest of the low pressure (steam) and Lowest of the high pressure (FW)

117
Q

How do the RHR Hx Outlet valves (IRV-320 and IRV-310) fail on a loss of air?

A

Open!

This raises flow thru the Hx, raising the cooldown rate

118
Q

If CRID 1 is lost, what happens?

A

Train A SSPS output relays won’t work.

Manual red switches will not work to actuate SI.

119
Q

When an RCP Trips, how do Thot and Tcold respond in that loop?

A

Reverse flow causes Thot to drop to the Tcold value or slightly below

T cold remains about the same at low power

120
Q

Which CRID does NOT supply power to the Steam Dump System?

A

CRID 3

121
Q

What would cause a load cons signal to be generated for the CD EDG?

A

Train A SI with a LOOP/Loadshed