Hangers and Snubbers Flashcards
Describe the types of strain and movement experienced by Plant Piping systems
- weight of piping
- process fluid contained in piping
- system components
- pressure and temperature induced expansion and contraction
- movement caused by system flow changes and pressure surges
Purpose of pipe hangers
- support piping systems
- prevent damage by compensating for strains and movements
- standards are governed MSS, ANSI, ASME
Types of pipe hangers
Consideration for hanger construction:
-pipe size, piping config, location, structural points to attach to
Flexible Hangers: support piping systems to allow for vertical movement due to thermal expansion.
2 types: Constant and Variable Support (use spring)
Rigid Hangers- no vertical movement
2 types: Horizontal and Vertical
Snubbers: a special type of hanger that slows the movement of piping
Explain basic operation of mechanical snubber
Use a ball screen shaft and spring mechanism or rod and bearing assemblyto provide a braking action limiting the axial movement to maximum safely restrained acceleration
Mechanical snubbers limit ACCELERATION of movement
Hydraulic snubbers limit VELOCITY of movement
Explain basic operation of Hydraulic Snubbers
2 on each RCP and 2 on each SG, they are different types but operate the same
Below activation limit- hydraulic fluid is forced from one side of piston to the other via a control valve with an orifice cut into seat. Fluid reservoir maintains head on both sides of piston
Activation limit exceeded- motion in excess of lockup velocity closes the control valves creating hydraulic lock
Identify major components of hydraulic snubber
SG is a 650 KIP snubber. Hydraulic fluid is Fyrquel
RCP is an 850 KIP snubber, has a spring loaded reservoir and uses GE SF-1154 for its fluid
Common components are tube(houses piston), nameplate, piston rod, rod head chevron packing, bleed and drain plugs, control valves and reservoir
KIP=1000 lbs of compressive or tensile force
Activation level=amount of acceleration that causes snubber to resist movement
Normal inspection criteria for mechanical Snubbers
No visible damage.
After transient, normal visual inspection and can verify freedom of movement by removing one end pin and push or pull to verify free movement
Normal inspection criteria for hydraulic Snubbers
- no visible leaks(plugs, fittings, valves, seals, reservoir, tubing)
- hanger fasteners can support Snubber function
- hydraulic oil level adequate- reservoir level in SH and reservoir piston position on RCP
- hanger support structure and foundation intact
- no indication of deformation, physical damage or excess movement
- fasteners are not loose or missing
- proper installation/orientation
- no obstruction to movement
5 and 10 year STs
5 year- sample hydraulic fluid for water, viscosity and particulates. Replace fluid if necessary.
Control Room needs to be notified prior to sample due to potential alarm (RCP)
10 year- fluid sample, vendor functional test(bleedrate and lockup)
For RCP, replace chevron head packing, replace reservoir rod wiper
SG- replace chevron packing