General Requirments Flashcards

1
Q

ABC

A

Alberta building code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

AFC

A

Alberta fire code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

AHJ

A

Authority having jurisdiction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

“Approved”

A

Acceptable to AHJ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

“Listed”

A

equipment, materials, or services included in NFPA in a list published by an organization.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Engineer approvals

A

Required in a building

Single-family residential - not required.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

valve closing time

A

valves shall not be able to be fully opened or closed in less than 5 seconds.

water hammer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

water flow alarm devices

A

should result in an audible alarm within 5 minutes of sensing flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

sizing of drain pipe

A

when drain connections for floor control valves are tied into a common drain riser, the drain riser shall be one pipe size larger downstream of each size drain connection tying into it.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

stubbing pipe through an exterior wall, where it could freeze

A

minimum 4ft in between drain valve and the exterior wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Auxillary drains

A

For removing trapped water.
> 50gallons - 1” valve + piping
5-50 gallons - 3/4 valve no pipe
<5 gallons - 1/2” plug

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

“Supervisory” vs “alarm”

A

Supervisory sends a signal to the monitoring company

Alarm will send a signal to both the monitoring company and the fire department

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A local water flow alarm must be installed on every sprinkler system having more than __ sprinklers

A

20 sprinklers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Paddle-type water flow alarms should only be installed on what type of systems?

A

Only on wet pipe systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

wet pipe sprinkler system installations shall be tested with a ____ test

A

hydrostatic test

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

hydrostatic test

A

no less than 200 psi with no pressure loss for 2 hours.

If working pressure is > 150 psi testing pressure will always be 50 psi higher

17
Q

testing modified areas (revisions to systems)

A

200 psi hydrostatic test is not required when there are less than 20 affected sprinklers.