Fire Alarms, Fir Doors, Fire Dampers Flashcards

0
Q

How frequently should Fire Alarm Audibility tests be carried out?

A

Weekly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

The Fire Alarm Standard, BS 5839 requires the person responsible for the system to be identified in which document?

A

The Fire Alarm System Log Book.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where does BS5839 require fire alarm remedial actions to be recorded?

A

In the Fire Alarm Log Book (as an absolute minimum)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How often should smoke and heat detectors be tested by the application of smoke or heat?

A

All devices must be tested every 12 months. Records must be kept to prove it.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How often must break-glass units be tested?

A

All break glass units must be tested every 12 months. A testing program can be incorporated in the weekly sounder test program. Records must be kept to prove it.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fire Doors. At what frequency must fire doors be inspected?

A

Every 6 months.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Can fire doors be repaired?

A

Yes but only with the approval of the manufacturer. This includes changing door closers, glazing, hinges and intumescent seals/brushes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fire Dampers are required to be serviced, inspected and operated at what frequency?

A

Electrically operated dampers require testing every 6 months. Mechanical, spring operated dampers require testing every 12 months.
Records of each damper and when it is tested need to be kept to prove it has been done.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How frequently are fire extinguishers to be inspected?

A

Every 12 months

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where are service records kept for a fire extinguisher?

A

On the label stuck on the extinguisher.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How often should fire dry-risers be pressure tested?

A

Annually dry risers should be pressure tested with water and if possible flow tested from the highest hydrant.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly