The purpose of the _____ system is to remove heat from the main generator windings and exciter rectifiers.
A. Hydrogen
B. Stator Cooling Water
C. Generator Seal Oil
D. lsophase Bus Cooling
B
Proper operation of the Stator Cooling Water system ensures __
A. exciter stator winding insulation integrity and cooling of the exciter rectifiers
B. exciter stator winding insulation integrity and cooling of the high voltage bushing connectors
C. main generator stator winding insulation integrity and cooling of the exciter rectifiers
D. main generator stator winding insulation integrity and cooling of the high voltage bushing connectors
C
Which ONE of the following identifies correct flowpath order of Stator Cooling Water system components during NORMAL operations?
Start at the Storage Tank Outlet.
- Temperature Control Valve
- Pressure Control Valve
- Storage Tank Debubbler
- Stator Cooling Water Pump
- Stator Cooling Water Heat Exchanger
A. 3, 4, 5, 2, 1
B. 4,5, 1,2,3
C. 4,5,2, 1,3
D. 5,2, 1,3,4
B
The Stator Cooling Water system is provided with a Pressure Regulator which has MINIMUM and MAXIMUM stops on it. The 37 psig CLOSED mechanical stop (1 ) and the 55 psig OPEN mechanical stop (2).
A. (1) prevents a complete loss of cooling flow
(2) reduces the potential for leakage into the Generator.
B. (1) reduces the potential for leakage into the Generator
(2) prevents a complete loss of cooling flow.
C. (1) prevents a complete loss of Service Water cooling
(2) prevents overpressurization.
D. (1) prevents a complete loss of cooling flow
(2) ensures at least 8 psig pressure differential from Hydrogen gas pressure.
A
The Stator Cooling Water Skid Pressure Control Valve (PDV 2495) functions to maintain Stator Coolant Water pressure ____ than Generator Hydrogen gas pressure.
A. 3 psi HIGHER
B. 8 psi HIGHER
C. 3 psi LOWER
D. 8 psi LOWER
C
Which ONE of the following statements describes Stator Cooling Water system indications available to the Control Room operator? (Excluding computer points).
A. ONLY annunciators are provided in the Control Room. NO parameter indicators are available.
B. Control Room indicators are available for the same parameters which are provided with local indicators.
C. Besides Control Room annunciators, the ONLY Control Room indicator available is Stator Cooling Water pump discharge pressure.
D. No Annunciators or parameter indications for the Stator Cooling Water System are located in the Control Room.
A
The Main Turbine will trip during a Loss of Stator Cooling Water runback if generator load is NOT less than ___ % within ____ minutes from the start of the runback.
A. 80, 2.0
B. 40, 2.5
C. 20, 3.5
D. 24, 2.0
A
The plant is operating at 100% power.
Which ONE of the following sets of annunciators will be in alarm on a loss of BOTH Stator Cooling Water Pumps?
- 14-6-D, ICS IN TRACK
- 15-4-B, EHC CABINET TRBL
- 15-5-B, EHC CTRL PANEL TRBL
- 16-1-G, STAT-CLNT LOSS T-G RNBK
- 16-2-B, FIELD CURRENT HIGH
- 16-2-F, STAT-CLNT INLET FLOW LO
A. 1, 2, 5
B. 1,4,6
C. 2, 3, 6
D. 3,4, 5
B
The Stator Cooling Water System three-way temperature control valve has lost its instrument air signal. How will the valve fail?
A. “As is”
B. Full flow thru the heat exchanger
C. Full bypass flow
D. Closed. Stop all flow
B
The plant is operating at 100% power The following conditions are observed: Annunciators
* STAT-CLNT CNDCT >0.5, 16-6-F in alarm
* STAT-CLNT CNDCT >9.9, 16-5-F in alarm
The Zone 2 Operator reports CIT 2463, Stator Winding Inlet Conductance and CIT 2464, Stator Winding Outlet Conductance are both indicating greater than 9.9 µS/cm
Which ONE of the following actions is correct, given these conditions?
A. Trip the Turbine
Go to DB-OP-02500, Turbine Trip
B. Verify makeup water is isolated
Refer to DB-OP-06209, Stator Cooling Water System Operating Procedure
C. Start a rapid shutdown
Go to DB-OP-02504, Rapid Shutdown
D. Trip the Reactor
Go to DB-OP-02000, RPS, SFAS, SFRCS Trip or SG Tube Rupture
C
The following plant conditions exist:
* Reactor power is 100%.
* All systems are in a normal lineup.
The following indication is observed
PS2476D, MN TURB GEN CASING (INLET WATER) TURBINE RUNBACK, has failed low.
Which one of the following is the expected plant response to this condition?
A. No effect on the plant because the turbine runback requires 2 out of 3 logic for low pressure
B. No effect on the plant because the runback is caused by low flow switches.
C. Turbine load will be reduced to less than 24% due to a single failure causing a runback.
D. Turbine will trip after 5 minutes due to the runback being blocked by the 2 out of 3 logic.
A
The purpose of using Hydrogen in the Main Generator is to transfer the heat generated in the
internals of the
A. Exciter to the Stator Cooling Water System
B. Exciter to the Turbine Plant Cooling Water System
C. Main Generator to the Component Cooling Water System
D. Main Generator to the Turbine Plant Cooling Water System
D
The purpose of the Carbon Diox
A. remove heat from the Main
B. allow an onsite source of C
C. provide a CO₂ fire suppression system for the Main Generator Seal Oil Room
D. provide a means for safely scavenging or filling the generator casing with hydrogen or air
D
During purging operations in preparations for maintenance on the Main Generator, Hydrogen
A. enters the top, CO₂ leaves the bottom
B. leaves the top, CO₂ enters the bottom
C. enters the bottom, CO₂ leaves the top
D. leaves the bottom, CO₂ enters the top
B
Which ONE of the following is correct concerning the hydrogen reserve bottles?
A. The hydrogen reserve bottles are pressurized from the hydrogen trailer.
B. The hydrogen trailer is kept pressurized from the hydrogen reserve bottles.
C. The hydrogen reserve bottles are used as a surge volume for the Main Generator.
D. The hydrogen reserve bottles are floated on the hydrogen header to maintain system pressure
during temperature fluctuations.
A