EO1 B2 MAIN GEN Flashcards

1
Q

During a Turbine/Generator startup, which ONE of the following actions should be taken AFTER
increasing generator output voltage to 25 KV?

A. CLOSE the Exciter Field Breaker

B. CLOSE the Main Generator Field Breaker

C. Raise Main Generator loading to 50 MWE.

D. CLOSE the Main Generator Output Breakers (34560/34561)

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Per the Generator and Exciter Operating procedure, generator output breakers 34560 and 34561 should
be re-closed within one hour of being opened to

A. minimize pressure on seal components in the operating mechanism

B. minimize the potential for inadvertent main generator reenergization

C. avoid having to start an RCS cooldown within one hour

D. avoid reliance on disconnect switches for isolation

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The following plant conditions exist:

  • The plant is operating at 100% power
  • Switchyard voltage is 365 Kv
  • Main Generator MVars is O

The load dispatcher requests us to lower voltage. What actions should be taken?

A. Inform the Load Dispatcher that we are at minimum MVars and cannot lower voltage.

B. Inform the Load Dispatcher we are operating within the requirements of the voltage schedule and
maintain our current voltage.

C. Lower voltage as requested to the maximum Mvars IN allowed by the generator capability curve or
the voltage requirements of C1/D1 Busses.

D. Lower voltage to the maximum MVars OUT allowed by the generator capability curve or the voltage
limits of the C1/D1 Buses.

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If reverse power of 5.2 MW is detected on the Main Generator, it will trip

A. immediately

B. after 2-3 seconds

C. after 25-30 seconds

D. only if the turbine stop valves are closed

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The plant is at 100% power.

The following event occurs:

  • Annunciator 16-4-B, VOLTAGE REG TRBL, is in alarm
  • Generator Field Volts = O
  • Generator Field Bkr Control Switch green light is ON
  • Exciter Field Bkr control switch red light is ON

Assuming NO AUTOMATIC or OPERATOR actions occur, which ONE of the following conditions will result?

A. The Main Generator will fall out of synchronization with the Grid, resulting in slipping a pole.

B. An unbalanced loading between the three phase windings of the Main Generator.

C. An underfrequency condition, resulting in excessive temperatures being generated in the last
stages of the Low Pressure Turbines.

D. Oscillating current flows through the stator windings of the Main Generator resulting in
insulation breakdown.

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The following plant conditions exist:

  • The plant has commenced a power reduction.
  • Main Generator loading is 800 MWe.
  • Both isophase bus fans have tripped on overcurrent.
  • Zone II operator reports local isophase bus temperatures are 106 °C and rising.

Which one of the following is the maximum Main Generator stator amperage limit imposed?
A. 24600 amps

B. 18200 amps

C. 12400 amps

D. 6600 amps

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Given the following conditions for the Main Turbine/ Main Generator:

  • 700 MWe
  • 60 Hz
  • 1800 Rpm
  • EHC is in MANUAL

Describe the effect on the Main Generator if the EHC INCREASE LOAD pushbutton is depressed, with no
operator action.

A. MVARs rise

B. MWe rise

C. Excitation Voltage lowers

D. Frequency rises

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The following plant conditions exist:

  • 700 MWe
  • 60 Hz@ 1800 RPM
  • EHC in MANUAL

The AUTO VOLTAGE REGULATOR is turned in the LOWER direction. What are the effects on the Main
Generator?

A. KVARs will LOWER or go towards LEADING pf

B. KVARs will NOT change

C. KVARs will INCREASE or more lagging pf

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

5 MC The Main Generator is being paralleled and connected to the grid with the following
conditions:
* Generator Frequency 60.1 Hz

  • Grid Frequency: 59.9 Hz
  • Generator voltage: 345.5 KV
  • Grid Voltage: 344.8 KV

When the Main Generator output breaker is closed, the generator will:

A. acquire real load and reactive load

B. acquire real load, but become a reactive load to the grid

C. become a real load to the grid, but acquire reactive load

D. become a real load and a reactive load to the grid

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

6 MC The Main Generator is being paralleled to the grid.

  • Generator voltage and grid voltage are matched.
  • Generator frequency is 60.1 Hz.
  • Grid frequency is 60.0 Hz.

Closing the generator output breaker will

A. cause the generator to immediately pick up load

B. cause generator voltage to rise

C. cause a reverse power trip

D. cause the turbine to overspeed

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which ONE of the following is NOT a purpose of the Main Generator Exciter System?

A. To control Main Generator Terminal Voltage during Turbine Generator startup.

B. To control megawatt output of the main generator.

C. To control reactive loading on the Main Generator.

D. To supply DC current to the Main Generator Rotor.

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

2 MC The purpose of the Main Generator is to

A. Ensure power to C1 and D1 during a loss of offsite power

B. Control reactor power during plant operations

C. Convert mechanical energy of the turbine to electrical energy

D. Prevent the Main Turbine from overspeeding during a partial loss of load

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

4 MC The Main Generator converts the energy of the Main Turbine to energy for commercial sales.

A. thermal; rotational

B. mechanical; electrical

C. chemical; thermal

D. hydraulic; electrical

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

4 MC The Main Generator converts the energy of the Main Turbine to energy for commercial sales.

A. thermal; rotational

B. mechanical; electrical

C. chemical; thermal

D. hydraulic; electrical

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Which ONE of the following describes the purpose of the Main Generator Under-excited Reactive
Ampere Limiter (URAL)?

A. Establishes a MINIMUM megawatt output (loading) for the main generator to prevent a reverse
power condition.

B. Establishes a MINIMUM LAGGING Power Factor to maintain grid stability.

C. Prevents voltage Regulator output from RAISING to a level which would cause excessive armature
heating.

D. Prevents the Voltage Regulator output from LOWERING to a level which could cause the Main
Generator to drop out of synchronization with the grid.

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Which ONE of the following will cause the Main Generator Voltage Regulator to transfer from
AUTO to MANUAL?

A. Stator Coolant flow LOWERS

B. Generator Field Breaker OPENS

C. Main Generator Hydrogen pressure LOWERS

D. Main Generator Output Breakers (34560 & 34561) OPEN.

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Which ONE of the following is an indication that the Main Generator Under- excited Reactive Ampere Limiter (URAL) is affecting voltage regulation control?

A. Excitation current cannot be increased manually.

B. The voltage regulator is not responsive to commands to lower excitation (both manual and
automatic).

C. In AUTO outgoing VAR load cannot be changed (increased or decreased).

D. The Voltage Regulator transfers from auto to manual.

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Which ONE of the following describes the effect of the URAL circuit on the voltage regulator if the voltage regulator is in MANUAL?

A. In MANUAL control the URAL has NO EFFECT

B. Main Generator MVAR loading cannot be changed (increased or decreased)

C. Attempts to increase incoming MVARs become less effective

D. The voltage regulator will automatically transfer to AUTO control.

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Which ONE of the following Main Generator components is the one into which terminal voltage is
induced?

A. Rotor windings

B. Stator Bars

C. Isolated phase bus

D. High voltage bushing

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

9 MC Which ONE of the following could be utilized to determine the stator winding temperatures of
the Main Generator?

A. Temperature meter in the Control Room.

B. Temperature readout located in “A” Switchgear Room.

C. Temperature readout located on Generator skirt.

D. Temperature readout located near Auxiliary Boiler.

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

11 MC Which ONE of the following describes the function of the Main Generator Stator?

A. Supplies the magnetic field

B. Has the output voltage induced into it

C. Cools the Main Generator Core

D. Connects the Main Generator to the Auxiliary Transformer

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Which ONE of the following describes the FUNCTION of the Main Generator Rotor?

A. Supplies the magnetic field

B. Has the output voltage induced onto it

C. Contains stator cooling slots for cooling

D. Converts thermal energy to rotational motion

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Which ONE of the following indicates the normal speed at full power of the Main Generator Exciter?

A. 900 RPM

B. 1200 RPM

C. 1800 RPM

D. 3600 RPM

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Which ONE of the following is the function of the Main Generator Exciter Rectifiers?

A. Convert the Exciter DC to AC for the Main Generator Field.

B. Convert the Exciter AC to DC for the Main Generator Field.

C. Convert Main Generator field AC for use in the Exciter.

D. Couple Exciter AC and Main Generator Field to maintain 60 Hz.

A

B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Which ONE of the following describes the location of the Alternator Exciter Field Breaker?

A. Exciter house, 623’ elev.

B. 13.8 KVA “A” bus, 585’ elev.

C. Control Room cabinet area, 623’ elev.

D. Voltage regulator cabinet, 603’ elev.

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

Which ONE of the following describes the location of the Alternator Exciter Rectifier disconnects?

A. Exciter housing, 623’

B. 13.8 KVA “A” bus, 585’

C. Control Room cabinet area

D. Voltage regulator cabinet, 603’

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Which ONE of the following components applies the Direct Current directly to the Main Generator Field Windings?

A. brushes and collector rings

B. high voltage bushings

C. exciter field rectifiers

D. rotor retaining rings

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

In accordance with OB-OP-06301, which of the following values is the maximum value that can
be applied to the Generator Field?

A. 500 VAC
B. 400 VAC
E. 250 VAC
D. 120 VAC

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

4 MC Which ONE of the following combinations describes the field current of the Main Generator?
The current passes through the field breaker, then is supplied to the Main Generator
field windings via exciter brushes.

A. DC; generator

B. DC; exciter

C. AC; generator

D. AC; exciter

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

ONE purpose of the lsophase Bus Cooling System is to cool the

A. Main Generator rotor

B. Main Generator stator

C. Power Rectifier cabinets

D. Main Generator High Voltage bushings

A

D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

Which ONE of the following sequences describes the flow path of air through the lsophase Bus
Cooling System?

A. fan, B phase duct, A and C phase ducts, cooling coil, fan

B. fan, cooling coil, B phase duct, A and C phase ducts, fan

C. fan, cooling coil, B phase duct, A and C phase ducts, outside air damper

D. fan, A phase duct, B phase duct, C phase duct, cooling coil, fan

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

Which ONE of the following combinations correctly arranges the Isolated Phase Bus Cooling System flowpath starting at the fan?

  1. Cooling coils
  2. De-ionizing
  3. “B” phased
  4. “A” and “C”

A. 1, 4, 3, 2

B. 2,3, 1, 4

C. 3, 2,4, 1

D. 4,3,2, 1

A

C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

Which ONE of the following conditions is indicated if the Main Generator Core Monitor alarms?

A. Stator winding overheating

B. Power Rectifiers overheating

C. Exciter Rectifiers overheating

D. Rotor winding overheating

A

A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

4 MC Thirty minutes ago the plant tripped from 100% power:

  • Air Break Switch 34620 has not yet been opened
  • The ring bus has not been reestablished

A flashover occurs on the “B” phase of ACB 34561.

  • Five minutes later annunciator 16-2-D, CORE MONITOR ALARM alarms.
  • The Zone 2 operator reports that the reading for the Core Monitor is reading 10%.
    Which ONE of the following conditions would cause this indication to appear on the Core Monitor?

A. A phase to phase short in the Main Generator.

B. A failure of the Main Generator Field Breaker to open after the Reactor trip.

C. Low Hydrogen gas flow through the core monitor.

D. An overvoltage condition through the Generator stator windings.

A

C

35
Q

Which ONE of the following will cause Control Room annunciator 16-2-D, CORE MONITOR ALARM to
alarm?

A. Loss of power to monitor

B. Low Generator gas temperature

C. High TPCW cooling water flow

D. Hi / Low Generator gas pressure

A

A

36
Q

Which ONE of the following describes the function of the Main Generator Core Monitor?

A. Provides indication of Main Generator pressure

B. Provides warning of Stator Coolant leaks into the Main Generator core

C. Provides warning of Main Generator core hydrogen flow imbalance

D. Provides indication of Main Generator overheating

A

D

37
Q

3 MC Which ONE of the following annunciators normally comes into alarm following a Main
Turbine/Generator trip?
(Assume the T/G trip is due to a reactor trip).

A. VOLTAGE REG TRBL,

B. FIELD CURRENT HI,

C. VOLTS/HZ HI,

D. EXCITER RECT TEMP HI,

A

A

38
Q

Which ONE of the following conditions would cause the “VOLTAGE REG TRBL” annunciator to come into alarm in the Control Room?

A. The Control Room Operator transferring the Voltage Regulator from Auto to Manual.

B. A high temperature condition for any bank of Power Rectifiers.

C. The Generator Field Breaker tripping open.

D. The Voltage Regulator reaching the URAL (Underexcited Reactive Ampere Limiter) limit.

A

C

39
Q

Which ONE of the following conditions is indicated by annunciator 16-4-B, VOLTAGE REG TRBL?

A. The generator field breaker has TRIPPED

B. The voltage regulator is transferred from MANUAL to AUTO

C. A ground has been detected on the exciter field

D. Main generator stator voltage is LOW

A

A

40
Q

The plant is at 100% power when the Control Room Operator notices the following plant conditions:

Annunciator 16-4-B, VOLTAGE REG TRBL, is in alarm Generator Field Volts = 0
Generator Field Bkr Control Switch “Green” light ON Exciter Field Bkr control switch “Red” light ON
Assuming NO AUTOMATIC or OPERATOR actions occur, which ONE of the following conditions will result?

A. The Main Generator will fall out of synchronization with the Grid, resulting in slipping a pole.

B. An unbalanced loading between the three phase windings of the Main Generator.

C. An underfrequency condition, resulting in excessive temperatures being generated in the last stages of the Low Pressure Turbines.

D. Oscillating current flows through the stator windings of the Main Generator resulting in insulation breakdown.

A

A

41
Q

The plant is at 58% power. The following plant conditions exist:
Main Generator loading = 502 MWe
Voltage Regulator in Manual
Main Generator Reactive loading= 55 MVARs

The load Dispatcher requests the Control Room to decrease MVAR loading another 20 MVARs. The
Control Operator notices that as he is lowering MVARs the rate of decrease slows and eventually
stops.
Which ONE of the following conditions would explain the most likely cause of the above indication?

A. The Voltage Regulator has reached the Maximum Excitation limiter.

B. The Voltage Regulator Integral Controller has become saturated.

C. The Main Turbine high load limiter has actuated.

D. The Voltage Regulator has reached the URAL (Under-excited Reactive Load Limiter) setting.

A

D

42
Q

Which ONE of the following conditions would be detected by the Negative Phase Sequence relay
(46) actuating for the Main Generator.

A. Unbalanced loading between the three phase windings of the Main Generator stator.

B. Reverse current flow through the Main Generator stator windings.

C. A ground detected in the Main Generator rotor windings.

D. A difference in power output between the Main Generator and the Main Transformer.

A

A

43
Q

Which ONE of the following main generator relays is normally actuated following a Main Turbine trip?

A. Unit Differential Current (87 x 11)

B. Generator Ground (64G)

C. Generator Reverse Power (32)

D. Under Frequency (81 U1)

A

C

44
Q

Which ONE of the following Main Generator relays is NORMALLY actuated following a Main Turbine trip?

A. Unit Differential Current (87x11)
B. Generator Ground (64G)
C. Generator Reverse Power (32)
D. Loss of Field (40)

A

C

45
Q

Turbine speed has decreased to 1500 RPM. Which ONE of the following Control Room alarms
would be expected?

A. GEN UNDER FREQUENCY TRIP (16-1-D)
B. ESOP ON (16-1-H)
C. FIELD VOLTAGE HI (16-3-B)
D. VOLTS/HZ HI (16-5-B)

A

A

46
Q

The plant is at 79% RTP with a power increase in progress. A Main Generator lockout occurs due to the activation of the 51V relay (overcurrent).

Which ONE of the following lists the breakers which will automatically trip open as a result of
this condition?

  1. ACB 34560 and ACB 34561 (Main Generator Output Breakers)
  2. ABS 34620 (Main Generator Disconnect)
  3. Main Generator Field Breaker
  4. HX01A, HX02B (SU XFMR 01/02 Output)
  5. HX11A, HX11B (X11 XFMR Output)

A. 1, 2, 3

B. 1, 2, 5

C. 1, 3, 4

D. 1, 3, 5

A

D

47
Q

Which ONE of the following conditions will allow the Control Room operator to manually open the Exciter Field Breaker?

A. The Main Generator Field Breaker OPEN

B. Both Main Generator Output Breakers (ACB 34560, ACB 34561) OPEN

C. The Main Generator Voltage Regulator in MANUAL (DC) control

D. The Main Generator Ground Switch (34645) being OPEN.

A

A

48
Q

Which ONE of the following conditions will allow the Control Room operator to manually trip
open the Main Generator Field Breaker?

A. The Main Generator Ground Switch 34645 being closed.

B. The Main Generator Motor Operated disconnect (ABS 34620) being open.

C. Either Main Generator Output Breaker (ACB 34560, ACB 34561) open.

D. Both Main Generator Output Breakers (ACB 34560, ACB 34561) closed.

A

B

49
Q

Which ONE of the following conditions will automatically transfer the main generator voltage
regulator from AUTO to MANUAL?

A. Exciter Field Breaker

B. The Voltage Regulator reaching the URAL (Under
Excited Reactive Ampere Limiter) setting.

C. Main Generator Field Breaker OPENING

D. Both Main Generator output breakers (ACB 34560, 34561) OPENING

A

C

50
Q

Which ONE of the following conditions will allow the Control Room operator to manually trip open the Main Generator Field Breaker?

A. The Main Generator Ground Switch 34645 being CLOSED.

B. Main Generator Motor Operated disconnect (ABS 34620) being OPEN.

C. Either Main Generator Output Breaker (ACB 34560, ACB 34561) OPEN.

D. Both Main Generator Output Breakers (ACB 34560, ACB 34561) CLOSED.

A

B

51
Q

The plant is at 35% Rated Thermal Power.

o The Main Turbine is manually tripped due to HIGH vibration on the #5 bearing Which ONE of the following relays would actuate the Main Generator Trip FIRST following the actuation of the Turbine Trip?

A. CAD Trip confirm (23 CX)
B. Reverse Power (32)
C. Turbine Trip (01X)
D. Underfrequency (81)

A

B

52
Q

The plant is at 100% power.
Which ONE of the following actions will NOT occur as a result of an overcurrent (51 V Relay) condition being sensed by the Main Generator Protective Relays?

A. Main Turbine speed will INCREASE to ~105%.
B. The Generator Field Breaker will OPEN.
C. The Main Generator output breakers (34560 & 34561) will OPEN.
D. A and B bus will be energized via the Startup Transformers.

A

A

53
Q

Which ONE of the following will occur if the EXCITER FIELD GROUND DETECTOR senses a ground?

A. The Exciter Field Breaker OPENS, and a CTRM annunciator alarms.

B. The Main Generator Field Breaker OPENS, and a CTRM annunciator alarm.

C. The Main Generator Output Breakers (34560/34561) OPEN, and a CTRM annunciator alarms.

D. A CTRM annunciator ALARMS only.

A

D

54
Q

Which ONE of the following occurs if the Generator Field Ground Detector senses a ground?

A. A CTRM annunciator ALARMS.

B. The Main Generator Field Breaker OPENS.

C. A Main Generator Exciter Field Breaker OPENS.

D. The Main Generator Lockout occurs.

A

A

55
Q

Which ONE of the following conditions is indicated if the Main Generator Core Monitor alarms?

A. Stator winding overheating

B. Power Rectifiers overheating

C. Exciter Rectifiers overheating

D. Rotor winding overheating

A

A

56
Q

Thirty minutes ago the plant tripped from 100% power:

  • Air Break Switch 34620 has not yet been opened
  • The ring bus has not been reestablished

A flashover occurs on the “B” phase of ACB 34561.

  • Five minutes later annunciator 16-2-D, CORE MONITOR ALARM alarms.
  • The Zone 2 operator reports that the reading for the Core Monitor is reading 10%.

Which ONE of the following conditions would cause this indication to appear on the Core Monitor?

A. A phase to phase short in the Main Generator.

B. A failure of the Main Generator Field Breaker to open after the Reactor trip.

C. Low Hydrogen gas flow through the core monitor.

D. An overvoltage condition through the Generator stator windings.

A

C

57
Q

Which ONE of the following Main Generator Component’s temperature is monitored by resistance
temperature detectors AND thermocouples?

A. Stator

B. Rotor

C. lsophase Bus

D. Power Rectifier

A

A

58
Q

Which ONE of the following could be utilized to determine the stator winding temperatures of
the Main Generator?

A. Temperature meter in the Control Room.

B. Temperature readout located in “A” Switchgear Room.

C. Temperature readout located on Generator skirt.

D. Temperature readout located near Auxiliary Boiler.

A

D

59
Q

Which ONE of the following is the purpose of the Shaft Grounding Device on the Main Turbine/Generator?

A. To detect ground faults in the Main Generator stator windings.

B. To detect failure of the Main Turbine shaft grounding straps.

C. To detect a flashover of the Main Generator field brushes and collector ring assemblies.

D. To prevent the removal of more than three sets of field brushes when the Generator field breaker
is closed.

A

B

60
Q

Which ONE of the following Main Generator indications CAN NOT be read in the Control Room?

A. Wattmeter

B. Temperature

C. Frequency

D. Megavar

A

B

61
Q

Which ONE of the following describes the function of the Main Generator Core Monitor?

A. Provides indication of Main Generator pressure

B. Provides warning of Stator Coolant leaks into the Main Generator core

C. Provides warning of Main Generator core hydrogen flow imbalance

D. Provides indication of Main Generator overheating

A

D

62
Q

The voltage regulator holds the Main Generator Field voltage constant

and the voltage regulator holds the Main Generator Terminal Voltage constant .

A. Droop, auto

B. Manual; auto

C. Auto; manual

D. Manual; droop

A

B

63
Q

Which one of the following will NOT cause the amber neon lamps on the main generator rectifier cabinet to illuminate?

A. Low voltage

B. Shorted diode

C. High SCR temperature

D. Blown fuse

A

C

64
Q

During your Zone 2 tour, you notice that the red indicating light on one of the power rectifier
cabinets is on.
Which ONE of the following explains why the light is on?

A. Low voltage
B. Shorted diode
C. Blown fuse
D. High SCR temperature

A

D

65
Q

The plant is operating at 100%.
During rounds the Zone 2 operator notices that the yellow neon lights associated with the #1 bank
of power rectifier assemblies on the exciter housing are ON.
Which ONE of the following would be the reason for this indication?

A. This is their NORMAL condition.

B. A fuse has BLOWN on the rectifier.

C. A rectifier diode has FAILED.

D. The generator field breaker has TRIPPED.

A

A

66
Q

MC Plant conditions are as follows:

The plant is at 100% reactor power
Generator gross MWe = 921
Generator terminal voltage = 24 KV
#1 and #2 Turbine Plant Cooling Water pumps are in service

While taking readings the Zone 2 operator reports that the RED light located on the #2 power rectifier bank door is lit.

Which ONE of the following could be a reason for this condition?

A. Stator cooling flow has been LOST to the #2 rectifier bank.

B. The disconnect for the #2 Rectifier Bank is NOT in the fully engaged position.

C. A diode circuit has FAILED in the #2 Rectifier Bank.

D. The Rectifier Bank is in service. This is a NORMAL indication.

A

A

67
Q

Which one of the following is correct regarding Main Generator operation when in PARALLEL with the
grid AND operating with a LAGGING power factor.

Real load is raised by and Reactive load is raised by

A. RAISING Main Turbine speed
LOWERING Main Generator field excitation

B. RAISING Main Turbine speed
RAISING Main Generator field excitation

C. RAISING Main Turbine torque
LOWERING Main Generator field excitation

D. RAISING Main Turbine torque
RAISING Main Generator field excitation.

A

D

68
Q

The following plant conditions exist:

  • The plant is at 90% power.
  • # 4 Control Valve slowly opens an additional 10%.
  • Main Generator Voltage Regulator is in AUTOMATIC.

Which one of the following sets of indications would occur? (Assuming NO Operator actions.)

A. Main Generator frequency will LOWER and Megawatt output will RAISE.

B. Main Generator frequency will remain CONSTANT and Megawatt output will LOWER.

C. Main Generator Megawatt output will RAISE and MVARs will remain CONSTANT.

D. Main Generator Megawatt output will RAISE and MVARs will RAISE.

A

C

69
Q

6 MC The frequency of the Main Generator is related to which of the following?

A. Turbine speed

B. Exciter field strength

C. Reactive Load

D. Combined intercept valve position

A

A

70
Q

Excessive AC generator currents CAN NOT be caused by operating the generator in an
condition.

A. overvoltage

B. undervoltage

C. overload

D. underload

A

D

71
Q

The Main Generator is operating on the grid with the following indications:

  • 500 MWe
  • 300 MVAR (VARs OUT)
  • 2,800 amps

If the Main Generator excitation is reduced slightly, amps will and MWe will

A. lower; lower

B. raise; lower

C. lower; remain the same

D. raise; remain the same

A

C

72
Q

Which ONE of the following combinations represent the NORMAL values for the Main Generator output
frequency and output voltage at full power?

A 60 Hz., 25 KVAC
B 30 Hz., 25 KVAC
C 60 Hz., 345 KVAC
D 30 Hz., 345 KVAC

A

A

73
Q

Which ONE of the following components is NOT required to be in operation for the Main Generator to
produce electrical power?

A. Generator Field Breaker

B. Exciter Field Breaker

C. Main Transformer

D. High Voltage Bushing

A

C

74
Q

Voltage (volts) can be defined in terms of

A. an electrical potential difference

B. the rate of doing electrical work

C. coulombs of charge

D. cycles per second

A

A

75
Q

Current can be defined in terms of

A. electrical work

B. cycles per second

C. coulombs per second

D. an electrical potential difference

A

C

76
Q

Frequency can be defined in terms of

A. electrical work

B. coulombs of charge

C. cycles per second

D. an electrical potential difference

A

C

77
Q

Reactive power is the portion of the apparent power that is

A. effectively returned to the source and is measured in KVARs

B. effectively returned to the source and is measured in KVAs

C. actually dissipated in the load and is measured in watts

D. obtained by multiplying applied voltage and line current and is measured in watts­ reactive

A

A

78
Q

True power is that portion of apparent power that is

A. effectively returned to the source and is measured in KVAs

B. actually dissipated in the load and is measured in watts

C. effectively returned to the source and is measured in KVARs

D. obtained by multiplying applied voltage and line current and is measured in watts­ reactive

A

B

79
Q

The Main Generator is about to be connected to the grid. The following conditions exist:

Generator frequency = 59.8 Hz
Grid frequency = 59.5 Hz
Generator Voltage = 348 kV
Grid voltage = 349 kV
When the generator output breaker is closed, the generator will initially

A. become a real load to the grid, but acquire reactive load

B. become a real load and a reactive load to the grid

C. acquire real load and reactive load

D. acquire real load but become a reactive load to the grid

A

D

80
Q

The Main Generator is being paralled to the grid. The following conditions exist:
* Main Generator frequency 59.9 Hz

  • Grid frequency 60 Hz

Which one of the following will occur when the first generator breaker is closed?

(Assume that NO generator protection relay actuates)

A. The generator will motorize.

B. The generator will accept to much load.

C. The voltage of the generator will lower to compensate for the frequency.

D. The entire connected system will operate at the frequency of the lowest frequency generator.

A

A

81
Q

The Main Generator is being paralleled to the grid.

The synchroscope is rotating slowly in the COUNTER-CLOCKWISE direction.

The generator output breaker is closed just prior to the synchroscope pointer reaching the 12 o’clock position.

The generator output breaker will close and

A. the generator will supply MWe to the grid

B. the synchroscope will begin rotating slowly in the CLOCKWISE direction

C. then open due to overcurrent

D. then open due to reverse power

A

D

82
Q

The following generator conditions exist:
* 18,000 volts
* 32,200 amps
* Positive 432 MVARS
* Power Factor of 0.903
The real power of the generator is MWe.

A. 100.3
B. 523.4
C. 579.6
D. 905.4

A

D

83
Q

The Main Generator is being paralled to the grid.

The following conditions exist:

  • Main Generator frequency indicates 60.1 Hz but is actually at 59.9 Hz due to instrument error
  • Grid frequency is at 60 Hz

Which one of the following will occur when the first generator breaker is closed?
Assume NO generator protection relay actuates.

A. The synchroscope will begin to rotate slowly in the slow direction.

B. The synchroscope will begin rotating fast in the fast direction.

C. The actual generator frequency will rise to match the grid frequency.

D. The frequency of the grid will lower to match the actual frequency of the generator.

A

C

84
Q

Reactor power is 100%.

The following conditions occur:

  • The Generator Condition Monitor (GCM) has a verified alarm indicating 50%.
    What action is required?

A. Remove the Generator from service

B. Have l&C check the GCM calibration

C. Lower Generator load to raise the GCM reading to 80%

D. Maintain current Generator load until engineering evaluations are completed

A

C