AO Block 4 Remediation Flashcards
What are the Control Room Annunciator’s for essential TRANSFORMERS CE1-1, CE1-2, DF1-1, DF1-2?
CE1-1, CE1-2, DF1-1, DF1-2 Fault
CE1-1, CE1-2, DF1-1, DF1-2 Trouble
What are the Control Room Annunciator’s for essential BUS E1 and F1?
BUS E1 Trouble and F1 Trouble
Which NONESSENTIAL 480v BUS has a Control Room Annunciator alarm and what kind of alarm is it?
BUS F7 Trouble
What conditions will cause Control Room Annunciator’s for a 480v essential transformer FAULT alarm to come in?
Feeder Overcurrent or Ground
What conditions will cause Control Room Annunciator’s for a 480v essential TRANSFORMER TROUBLE alarm to come in?
Low liquid level 17.5”
High liquid temp 90deg C
Pressure Vac Switch +5.5# or -5.5#
Pressure Relief Operation 5#
What conditions will cause Control Room Annunciator’s for a 480v essential BUS TROUBLE alarm to come in?
Breakers out of normal position
Ground Fault
Loss of power to Panalarm Annunciator
What conditions will cause Control Room Annunciator’s for a 480v nonessential BUS TROUBLE alarm to come in?
Bus F7
Breakers out of normal position
Undervoltage
Loss of DC Control Power
What alarm condition(s) do the Control Room Annunciator’s for 480v essential and nonessential F7 BUS trouble alarms share?
Breakers out of normal position
How do alarm condition(s) for the Control Room Annunciator’s for 480v essential and nonessential F7 BUS trouble alarms differ?
E1 and F1: Ground Faults, Low of Power to Panalarm Annunciator
F7: Undervoltage and Loss of DC Control Power
What are the 250VDC loads for DCMCC 1?
RCP Backup Oil Lift Pump 1-1 and 2-2
MFPT 1 Emergency Bearing Oil Pump
RC Makeup Pump 1 Auxiliary Oil Pump
TG Emergency Bearing Oil Pump
Emergency Lighting Xfer Switch 1 and 3
UPS Inverter YVA for YAU
What are the 250VDC loads for DCMCC 2?
RCP Backup Oil Lift Pump 1-2 and 2-1
MFPT 2 Emergency Bearing Oil Pump
RC Makeup Pump 2 Auxiliary Oil Pump
TG Hydrogen Emergency Seal Oil Pump
Emergency Lighting Xfer Switch 2 and 4
UPS Inverter YVB for YBU
What are the +125VDC loads for DCMCC 1?
HPI Pump 1-1 DC Lube Oil Pump
AFP 1 Disch to SG 1 Valve(D1PA)
D1P
D2P(Alternate)
What are the -125VDC loads for DCMCC 1?
AFPT 1 Main Steam Line 1 Iso Valve
D1N
D2N(alternate)
What are the +125VDC loads for DCMCC 2?
HPI Pump 1-2 DC Lube Oil Pump
D2P
D1P(alternate)
What are the Control Room Annunciators for the Instrument AC system?
INV YV1 and YV3 Trouble
INV YV2 and YV4 Trouble
INV YVA Trouble
INV YVB Trouble
BUS YAR Voltage Lo
BUS YBR Voltage Lo
What conditions will bring in Control Room Annunciators for inverters YV1, YV2, YV3, and YV4?
Low DC in 108v
Low AC out 108v
Hi AC out 83A
Over Temperature
Out of Sync
Static Switch Transfer
Rectifier AC Power Failure
Fan Failure
Blown Power Fuse
What conditions will bring in Control Room Annunciators for inverters YVA and YVB?
Low DC Voltage 216v
Low AC Voltage 108v
Hi AC Current Out 400a
Hi Temperature
Out of Sync
Static Switch Transfer
Fan Failure
Power Fuse Blown
What voltage brings in the Annunciators for YAR and YBR Voltage Lo?
105v
What are the Power Supply’s for BUS’s YAR and YBR?
E23a and F23a through regulated transformers
What Control Room Indications are there for the Instrument AC system?
Essential panel volts
Regulated bus volts
UPS volts
Indicating lights for power arrangement
What Control Room Indications are there for the DC system?
Battery Charger Output Amps
Battery Amps
Essential DC Volts
250VDC Bus Volts
Disconnect/Switch indicating lights
What is the max voltage in the handheld for rounds on the 480v ESSENTIAL Bus Transformer High Resistance Ground Detectors?
10v
In the SCI-UPS system, what are the two power supplies for BUS E43?
BUS E4 and the Miscellaneous Diesel Generator
In the SCI-UPS system, what BUS supplies power for Battery Charger DBCSPN?
E43
In the SCI-UPS system, what are the two power supplies for inverter YVSA?
Battery Charger DBCSPN and Battery SB