Electrical Flashcards
Which of the following installations is UNSAFE?
a) NM wire in a detached garage
b) 8 gauge wire on a 30 amp circuit
c) 12 gauge/2 conductor wire servicing a baseboard heater
d) NM wire under a sandbox
e) knob-and-tube wire joined to new wiring in a junction box
D@
All of the breakers in a service panel are white, except one, which is black. You should be checking
a. that the black breaker is correctly sized for the wire.
b. that the black breaker is suitable for use in the panel, if this is determinable.
c. that the black breaker isn’t loose.
d. All of the above
D
you should check that the breaker is properly sized and is compatible with this panel. you should make sure that it was a professionally installed (and not forced into place) and that the breaker isn’t loose.
Problems with aluminum wiring include all of the following EXCEPT that
a. it tends to creep.
b. it lacked a ground wire.
c. the aluminum oxide is not a good conductor of electricity.
d. aluminum is softer than copper and easier to damage.
B@
Lacking a ground wire is not a common problem with aluminum wire.
Which type of wire is rated for underground use?
a) UF or NMWU
b) NMW
c) NMDU
d) BXU
e) UUDW
A@
Electrical ground wires may attach to all of these, EXCEPT:
a. Ground rods
b. Water supply pipe
c. Buried footing
d. Floor joist
D
Extension cords are typically
a. stranded wire.
b. solid wire.
c. designed to be held in place with staples.
d. best protected if run under carpets.
A@
Extension cords are typically stranded wire. This is so they will be more flexible than solid wire.
The end of the neutral wire from a 3-conductor cable is overheating. The reason for this could be any of these except
a) the wire is loose
b) the circuit breakers are undersized
c) both sides of the multi-wire circuit are drawing from the same bus
d) the wire is nicked
e) the wire is aluminum
B!
Water stains on the soffit around the hole where service mast passes through is most likely the result of
a. improper flashing where the mast penetrates the roof.
b. a lack of a drip loop.
c. a lack of caulking between the soffit and the mast.
d. a cracked masthead.
A!
Water stains on the soffit, where the mast goes through the roof, usually indicate a flashing problem.
Which of the following would least likely to be found on a dedicated circuit?
a) baseboard heater.
b) furnace
c) ceiling fan
d) dishwasher.
e) food waste disposal (disposer)
C@
Is it permissible to use an aluminum grounding wire?
A) Only if it is at least #3 AWG.
B) Yes.
C) Only in some provinces and states.
D) Only in dry environments in the United States.
D!
During an inspection you find 20 blown 15-amp fuses beside the panel. You might tell your client
A) it’s likely that there is at least one overloaded circuit in the panel.
B) the 15 amp fuses should be replaced with a larger fuse size that will not blow.
C) there must have been several defective fuses purchased, perhaps from one bad lot.
D) it’s likely that there is a defect in the panel.
A@
Which is the least common type of connection for branch circuit wiring seen in a new house?
a) bayonet
b) Marr®
c) screw
d) soldered
e) twist-on
D@
Overloading the neutral wire on a multi-wire branch circuit
A) means that the neutral wire was undersized.
B) indicates a short in the circuit.
C) is the result of failing to fuse the neutral.
D) is likely if the black and red wires are powered from the same bus.
D@
What factor determines the electrical service size to a house?
a. The size of the drip loop
b. The size of the meter
c. How close the house is to the transformer
d. The size of the service entrance wires
D
Ohm’s Law, the relationship between voltage, current, and resistance in a simple circuit, states that
a. V=lR.
b. l=VR.
c. R = IlV.
d. V=UR.
A!
V=IR.
All of the following are panel wire problems EXCEPT
a. overheating.
b. wires crossing bus bars.
c. sheathing removed.
d. abandoned wires.
C
Sheathing that has been removed on the panel wires is not a problem.
Attic wires should not ordinarily be run on top of ceiling joists unless
a) the headroom is less than 40 inches
b) plywood covers them
c) insulation covers them
d) they are visible
e) it is certain that animals won’t gain access
A@
Special grease on aluminum wires is
a. found on number 12-gauge and 10-gauge wires.
b. found on stranded wires.
c. found on service entrance wires only.
d. used to control creep.
B@
The special grease on aluminum wires is typically used on stranded wires.
These are all possible causes for an inoperative light, EXCEPT:
a. Bulb burned out
b. Faulty light fixture
c. Poor connection in box
d. Missing grounding wire
D
A special grease is applied to larger gauge aluminum wires to
a) reduce slippage
b) improve conveyance
c) help identify the wire as aluminum
d) inhibit corrosion
e) dissipate heat.
D@
If two 60-W light bulb branch circuits are wired in parallel, and another parallel 60-W light bulb branch circuit is added
a. the bulb closest to the voltage source will be brightest.
b. each bulb will have the same brightness.
c. the total current in the circuit stays the same.
d. the current in each branch will decrease.
B!
In a parallel circuit, any bulbs that you add will have the same brightness, so long as the circuit is not overloaded.
What is the correct fuse or breaker size for 8 gauge AWG copper wire?
a. 15 amps
b. 20 amps
c. 30 amps
d. 40 amps
D
Overheated wires may have resulted from all of the following EXCEPT
a) underfusing
b) a loose connection
c) a nicked wire
d) an undersized wire
e) proximity to a water heater vent
E@
Knob-and-tube wiring issues include all of the following EXCEPT
a. connections to modern wire not in boxes.
b. wires buried in insulation.
c. brittle wire, insulation, or sheathing.
d. overheated neutrals on multiwire branch circuits.
D@
Overheated neutrals on multiwire branch circuits are not specific to knob and tube wiring. Multiwire branch circuits are, in fact, very rare on knob and tube wiring.
The electrical force that is available in a home electrical system is known as:
a. Current
b. Resistance
c. Voltage
d. Power
C
What is a brief definition of an amp?
(a) An amp is a measure of how much electrical current is flowing (I=V/R).
(b) An amp is a measure of how much water is flowing (I=V/R).
(c) An amp is a measure of how much electrical current is resisting (I=V/R).
(d) An amp is a measure of how much electrical volume is flowing (I=V/R).
A
All of these are common branch circuit problems EXCEPT
a. NMD wires run through floor joists without tubes or grommets.
b. damaged wires.
c. open splices
d. undersized wire.
A@
NMD wires run through floor joists without tubes or grommets are not a problem.
The main fuses or breakers are most likely to trip
a) during cold weather
b) during hot weather
c) after 11:00 pm
d) when many large appliances are on
e) when most of the lights are on
D
Common switch problems include all of the following except
A) switches for garbage disposals on the front of base cabinets.
B) damaged switches.
C) dimmer switches with a positive shut off.
D) inoperative switches.
C@
Which one of the following is NOT a possible cause of the service mast, conduit, or cable letting water in?
a. Movement of the components
b. Deterioration of materials over time
c. Conduit undersized
d. Building settlement
C!
Undersized conduit can’t be the cause of water getting into the electrical system.
A kitchen split receptacle is a
a. switched circuit operating a wall receptacle.
b. receptacle with a test button required near kitchen sinks.
c. circuit servicing a separate cooktop and oven.
d. receptacle with the top and bottom halves on different circuits.
D!
A kitchen split receptacle is a duplex receptacle with the top and bottom halves on different circuits.
What is linking?
a. Linking ensures that light switches only operate the fixtures installed in the same room.
b. Linking is the same as bonding.
c. Linking ensures that two fuses or circuit breakers are disconnected at the same time.
d. Linking refers to connections made in a junction box.
C!
Linking ensures that two fuses or circuit breakers are disconnected at the same time. This is important on 240-volt circuits or multiwire branch circuits.
How many wires (conductors) are there from the street into a house in a 240-volt system?
a. 1
b. 2
c. 3
d. 4
C
The reasons for dedicated circuits are
a) the circuit uses so much electricity, or the circuit is so important
b) the circuit is so important, and you can’t hook high-demand circuits up in series
c) we want to avoid nuisance tripping, and the appliances are near a wet location
d) the high start-surge is a problem, and the high operating temperatures of furnaces and boilers may overheat the wire
A@
Most electrical codes don’t require a bottom-of-the-stairs light switch in a basement if
a) the basement is unfinished
b) there is another switch elsewhere in the basement
c) the basement is under 500 square feet
d) the ceiling height is under 7 feet
e) the basement is only one room
A@
The exterior sides and bottom of the service box are rusting. The interior of the service box is not affected. There is a water stain on the foundation wall below the service box. The box is below grade. Your best conclusion from these clues is
a) plumbing leakage; check for a pipe above
b) no sealant between the wires and the inside of the conduit
c) defective service cap (weatherhead)
d) no drip loop
e) leakage at the foundation wall conduit hole
E!
A 1500 square foot house has an electric stove, electric dryer, central air conditioning (FLA = 18 amps), and a recent basement renovation that included the installation of a 3000 watt sauna. If it has a 60A service, you should report that
a) the existing service is adequate
b) the existing service will support additional loads
c) the service should be upgraded
d) additional loads should be upgraded,
otherwise the service is okay
e) the sauna should be used in winter only
C!
Disadvantages of pigtailing aluminum to copper wire are
a. the two metals are not compatible.
b. it adds more connections and leads to overcrowding boxes.
c. you can’t pigtail different sized wire gauges together.
d. the solder isn’t likely to be effective.
B@
Pigtailed connections with aluminum wire add more connections to the box and may lend to overcrowding.
Assuming copper, standard wire type, and normal temperature rating, what is the typical conductor size (in AWG) for a 60-A service?
a. #10
b. #6
c. #4
d. #3
6-gauge wire is adequate for 60-amp service.
B!
How far should wires be kept from the metal vent connector on a gas appliance?
a. One inch.
b. Six inches
c. Nine inches
d. Eighteen inches
B@
Wires should be kept six inches away from metal vent connectors on a gas appliance.
All of these typically have a three-pronged plugs, EXCEPT:
a. Table lamps
b. Refrigerator
c. Washing machine
d. Microwave oven
A
All of the following are common receptacle problems EXCEPT
a. worn receptacles.
b. a pin that has broken in the receptacle.
c. the receptacle being too close to the basin.
d. bathroom outlets that are too far from basins.
C@
The receptacle that is too close to the basin is not a problem.
What is the most important reason an overhead wire from the house to the garage is stranded?
a) stranded wires can carry more current
b) they have thicker insulation to handle the weather
c) they are stronger than solid wires
d) there is less likelihood of height restrictions
e) stranded wires are more flexible
E@
A properly polarized circuit
a. has the black wire connected to the silver screw on the receptacle.
b. has the neutral and ground connections bonded-together at the receptacle
c. will always be grounded.
d. will result in the threaded collar of a lamp being neutral.
D@
A properly polarized circuit has the lamp collar connected to the neutral.
Of the GFls that you find in a house, which ones must be tested?
a. All of them
b. Those at the panel
c. Exterior GFIs
d. Kitchen GFls and exterior GFIs
A@
All GFIs must be tested.
Which of the following is not an approved grounding method?
a. Metallic underground water piping
b. Metal frame of a building
c. Ground rods
d. Gas piping
D!
Gas piping is not an approved grounding method.
NMD cable is
a. rigid.
b. armored.
c. suitable for dry indoor use.
d. suitable for outdoor use but not underground.
C@
NMD cable is suitable for dry indoor use.
Almost all abandoned wires
a) are live
b) are dead
c) should be removed
d) are brittle.
e) are for future use.
C@
Putting the fuses upstream of the disconnect switch in the service box
a. makes it dangerous to change the fuses even when the house power is shut off.
b. may cause a short circuit through the fuses.
c. is a result of connecting the service conductors to the line side, rather than the load side.
d. is a result of installing the box upside-down.
A
Putting fuses upstream of the disconnected switch in the service box makes it more dangerous to change the fuses. Even when the house power is shut off, there will be power to the fuse terminals.
Implications of an undersized service include
a) shock hazard
b) fire hazard
c) shock and fire hazard
d) melting insulation
e) nuisance tripping of the main fuses or breakers
E
The standard house voltage is
a. 100 A.
b. 120 v.
c. 120/208 v.
d. 120/240 v.
D!
The standard house voltage is 120/240 V.
What is the frequency (cycles/second) of household electricity?
a. 60 Hz
b. 50 Hz
c. 30 Hz
d. 66MHz
A
Household electricity is 60 Hertz.
A false ground reading on a circuit tester may be the result of
a) a ground created by accident
b) a double insulated device
c) ground wires attached to plastic water piping
d) a missing jumper wire
e) the panel not being bonded to the neutral wire
C@
When you find three-slot receptacles on ungrounded circuits, you might recommend any of the following EXCEPT
a) replace the circuit with a grounded circuit
b) run a ground wire to a metal supply-plumbing pipe that runs back to the ground
c) fill the ground hole with epoxy, if permitted by authority
d) replace the receptacle with a GFCI
e) label the circuit at the panel “ungrounded”
E@
When replacing the panel cover, it’s hard to get it back on without pinching or compressing the wires inside the box. You should conclude that
a. the panel is overcrowded.
b. the panel cover is too small for the panel.
c. the wires are probably larger than is necessary.
d. both a and c are true.
A!
The panel is overcrowded if you can’t get the cover back on without pinching wires.
Of all the different characteristics of aluminum wiring, the one that contributes the most to the overheating problem is its
a) softness.
b) fragility
c) oxidation tendency
d) lower conduction ability
e) rate of thermal expansion.
C@
What is a type P fuse?
A) A gfci fuse
B) A heat sensitive fuse
C) A “power” fuse, for 30A or more loads
D) A time-delay fuse
B!
The top end of an service entrance cable service
a. should be bent into a U-shaped drip loop before removing the cable sheathing.
b. should not be clamped within 36 inches of the top.
c. should have a gooseneck before the splice.
d. must be spliced to the service drop at least 3 feet from the side of the house.
C
The top end of a service entrance cable should have a gooseneck before the splice.
Your hand-held electrical tester (the one with three lights) won’t tell you if
a) there is an open hot wire
b) there is an open neutral wire
c) there is a false ground
d) a receptacle is properly wired
e) a receptacle is grounded
C@
After entering the service box, the neutral service entrance conductor should
a. connect to the terminal with the grounding electrode conductor and the service neutral.
b. connect to the main breaker.
c. go directly to the distribution panel.
d. connect to the main fuses on the line side.
A!
The neutral service entrance conductor should connect to the terminal with the grounding conductor and the service neutral.
Common copper wire sizes for an electric water heater are
a. #12 and#10.
b. #16 and #8.
c. #16 and#18.
d. #10and#8.
A
Common wire sizes from water heaters are 12-guage and 10-guage.
Service entrance cable must be securely clamped to the house
a. using brass clamps and screws.
b. every 12 inches, using rustproof fasteners.
c. every 6 feet.
d. every 30 inches, generally.
D
Service entrance cable should be clamped to the house ever 30 inches, generally.
You plug your circuit tester into an outlet that has a washing machine plugged in. Your tester shows the outlet is properly wired and grounded. How could you improve this inspection process?
A) Use a circuit tester with a GFI test button
B) Use a voltage tester
C) Turn the washing machine on before doing your test
D) Unplug the washing machine
D@
The term service drop defines
a. the underground wires from the utility, to the point of connection, to the house.
b. the wires that connect the meter to the service box.
c. the wires that run down the outside of the house into the meter.
d. the overhead wires coming from the utility pole, to the point of connection, to the house.
D!
The service drop refers to the overhead wires coming from the utility pole to the house.
Circuit breakers
A) protect inhabitants by limiting shock duration.
B) regulate power to the attached equipment.
C) protect the wire from an electrical overload.
D) measure the current in a circuit.
C
Assuming copper, standard wire type, and normal temperature rating, what is the typical conductor size (in AWG) for a 200-A service in the United States?
a. #2
b. 1/0
c. 2/0
d. 3/0
C
A 200-amp service must have 2/0-gauge wire in the United States.
What is the definition of an ohm?
(a) An ohm is a measure of a conductor or insulator (R=V/I).
(b) An ohm is a measure of energy to electrical flow in a conductor or insulator (R=V/I).
(c) An ohm is a measure of resistance to electrical flow in a conductor or insulator (R=V/I).
(d) An ohm is a measure of resistance to electrical resistance in a conductor or insulator (R=V/I).
C
The grounded plugs (three-prong plugs) became standard for all branch circuits in the
a) 1930s
b) 1940s
c) early 1950s
d) early 1960s
D
White wires can sometimes act as black wires
a. in 240-volt circuits.
b. in multiwire branch circuits.
c. by design on a reverse polarity circuit.
d. on a dedicated circuit for a clothes dryer.
A@
White wires can sometimes act as black wires in 240-volt circuits.
A house has service entrance conductors designed for 100 amps and a main disconnect rated at 100 amps. Which of these conditions is unsafe?
A) The distribution panel is rated at 125 amps.
B) The service box is rated at 125 amps.
C) The service box is rated at 75 amps.
D) The distribution panel is rated at 200 amps.
C
What is the MINIMUM electrical service drop clearance from a residential driveway?
A) 12 feet
B) 13 feet
C) 15 feet
D) 18 feet
A
What are the I (current) and R (resistance) values for a circuit with four 60-watt light bulbs and a 360-watt television?
a) I=5A, R=600 ohms
b) I=12A, R=72 ohms
c) I=24A, R=5 ohms
d) I=2.5A, R=48 ohms
e) I=5A, R=24 ohms
E!
Which of the following may indicate an amateurish wiring installation?
a) staples securing wire every 4 feet
b) standoffs used on metal studs.
c) staples missing where wires run through studs
d) staples where cables change direction
e) two wires secured under one staple
E@
These are all possible causes of an inoperative outlet, EXCEPT:
a. Reversed polarity
b. Outlet is defective
c. Blown fuse
d. Power is off
A
In a modern house, how far apart should be electrical outlets to be located?
a. 3 feet
b. 4 feet
c. 6 feet
d. 12 feet
D
A fire hazard may exist in all of the following scenarios EXCEPT
a) a 16 gauge extension cord on a 20 amp circuit
b) 14 gauge wire with a 30 amp fuse
c) two 10 amp appliances on a 15 amp breaker
d) a 30 amp fuse substituted on a 15 amp circuit
e) an extension cord stapled under a carpet
C@
Knob-and-tube wiring wouldn’t be anticipated in a house built much after
a) 1935
b) 1940
c) 1945
d) 1950
e) 1955
D@
You notice rust in the service panel. Which of the following may be the cause?
a. No drip loop
b. Undersized conduit
c. Damaged masthead
d. Both a and c.
D!
Undersized conduit can’t be the cause of water getting into the electrical system
If the service entrance conduit is 2 inches, what conclusions can you draw as to the size of the electrical service?
a. You would suspect a service greater than 100 A, but would have to confirm elsewhere.
b. The service is 200 A.
c. The service is 100 A.
d. The service conduit is oversized.
A!
The size of the conduit is not a reliable indicator of the service size. This would be common for a 200-amp service, but they could run smaller wires in the conduit.
The purpose of an isolating link on a pull chain light is to
a) prevent the fixture from overheating
b) allow multiple units to be installed on the same circuit
c) prevent the chain from conducting electricity
d) permit the fixture to operate at either 120 or 240 volts
e) allow the fixture to be operated with or without a wall switch
C@
Which of these wires is a home inspector required to inspect?
a. Telephone wiring
b. Security wiring
c. Cable television wiring
d. Wiring for a clock receptacle
D@
We are required to inspect the wiring for a clock receptacle.
Panels used with aluminum wire should
a. be circuit breaker rather than fuse-type.
b. contain at least 20 branch circuits.
c. be rated CUAL
d. be rated CO/ALR
C@
Panels used with aluminum wires should be ranted CUAL.
Number 10 gauge wires are typically used for all of these except
a) air conditioners.
b) clothes dryers
c) dishwashers.
d) cooktops
e) saunas.
C@
What is the definition of a volt?
(a) A volt is the measure of the energy in an electrical system (V=IxR)
(b) A volt is the measure of the force or potential energy in an electrical system (V=IxR)
(c) A volt is the measure of the resistance or potential energy in an electrical system (V=IxR)
(d) A volt is the measure of the flow or potential energy in an electrical system (V=IxR)
A
A quick way to check for aluminum wire is
a) look at the panel label for a CUAL designation
b) look at the ground wires in the panel
c) note the size of the sheathing (aluminum is thicker)
d) look for a stamp on the breaker
e) bend a cable (aluminum will bend more easily)
B@
Electrical receptacles in bathrooms should be
A) GFCI protected.
B) at least 3 feet away from showers and bathtubs.
C) not more than 2 feet from the vanity basin.
D) waterproofed.
A
Which of the following is a reliable way to identify the service size?
A) The distribution panel rating
B) The size of the service drop wires
C) The service entrance conduit size
D) The service entrance conductor size
D
GFCI receptacles
a) protect all of the receptacles upstream in the same circuit
b) are best tested with a circuit analyzer with a GFCI test button
c) only work on grounded circuits
d) are accepted as an alternative for grounding under some circumstances
e) perform exactly the same function as grounding
D@
These are all problems specific to fuses except
a) fuses bypassed
b) different fuse and panel manufacturer
c) fuses loose
d) fuse holder broken
e) no links on multi-wire circuit fuses
B!
A difference between fuse manufacturer and panel manufacture is not a problem.
The smallest gauge wire (copper) normally used in a house is
a) 3
b) 8
c) 10
d) 12
e)14
E@
As a general rule, how much clear space should be in front of the service box?
a. One foot
b. Three feet
c. Five feet
d. Six feet
B!
There should be three feet of clear space in front of a service box.