SIZING: DFU, WSFU, VENT, BTU Flashcards
Maximum units for 1-1/4” drainage piping if draining vertically
1 Unit
Maximum units for 1-1/4” drainage piping if draining horizontally
1 Unit
Maximum units for 1-1/2” drainage piping if draining vertically
2 units (Except sinks, urinals, and dishwashers exceeding 1 fixture unit)
Maximum units for 1-1/2” drainage piping if draining horizontally
1 unit
Maximum units for 2” drainage piping if draining vertically
16 units (except six-unit traps or water closets)
Maximum units for 2” drainage piping if draining horizontally
8 units (except six-unit traps or water closets)
Maximum units for 3” drainage piping if draining vertically
48 units (only 4 water closets or six-unit traps allowed on a vertical pipe or stack)
Maximum units for 3” drainage piping if draining horizontally
35 units (not to exceed 3 water closets or six-unit traps on a horizontal branch or drain)
Maximum units for 4” drainage piping if draining horizontally
216 units (based on 1/4” per foot slope. For 1/8” per foot slope, multiply fixture units by a factor of 0.8)
Maximum units for 4” drainage piping if draining vertically
256 units
True or False: There is no maximum length for drainage piping in a horizontal orientation.
True. Maximum horizontal length for drainage piping is unlimited.
What is the maximum length allowed for 1-1/4” drainage piping in a vertical orientation?
45 feet
What is the maximum length allowed for 1-1/2” drainage piping in a vertical orientation?
65 feet
What is the maximum length allowed for 2” drainage piping in a vertical orientation?
85 feet
What is the maximum length allowed for 3” drainage piping in a vertical orientation?
212 feet
What is the maximum length allowed for 4” drainage piping in a vertical orientation?
300 feet.
True or false?
In vent piping, both the horizontal and vertical carry the same values for maximum length and maximum units.
True.
Maximum venting units for 1-1/4” pipe?
1 unit
Maximum venting units for 1-1/2” pipe?
8 units. (Except six-unit traps or water closets)
Maximum venting units for 2” pipe?
24 units
Maximum venting units for 3” pipe?
84 units
Maximum venting units for 4” pipe?
256 units (same as the vertical drainage units for 4”)
Maximum length in feet for 1-1/4” vent piping
45 feet
Maximum length in feet for 1-1/2” vent piping
60 feet
Maximum length in feet for 2” vent piping
120 feet
Maximum length in feet for 3” vent piping
212 feet
Maximum length in feet for 4” vent piping
300 feet
Maximum DFU for a trap and trap arm in 1-1/4”
1unit
Maximum DFU for a trap and trap arm in 1-1/2”
3 units
Maximum DFU for a trap and trap arm in 2”
4 units
Maximum DFU for a trap and trap arm in 3”
6 units
Maximum DFU for a trap and trap arm in 4”
8 units
What is the equivalent fixture unit value for “Up to 7-1/2 GPM” in intermittent discharge capacity?
Equals 1 fixture unit
What is the equivalent fixture unit value for “greater than 7-1/2 to 15 GPM” in intermittent discharge capacity?
Equals 2 fixture units
What is the equivalent fixture unit value for “greater than 15 to 30 GPM” in intermittent discharge capacity?
Equals 4 fixture units
What is the equivalent fixture unit value for “greater than 30 to 50 GPM” in intermittent discharge capacity?
Equals 6 fixture units.
What is the minimum size trap and trap arm for a bathtub or combination bath/shower?
1-1/2”
What is the minimum size trap and trap arm for a clothes washer, domestic, standpipe?
2”
What is the minimum size trap and trap arm for a drinking fountain or water cooler?
1-1/4”
What is the minimum size trap and trap arm for a floor drain?
2”
What is the minimum size trap and trap arm for a shower?
2”
What is the minimum size trap and trap arm for a lavatory?
1-1/4”
What is the minimum size trap and trap arm for a bar sink?
1-1/2”
What is the minimum size trap and trap arm for a commercial sink with food waste?
1-1/2”