What are the power supplies for the Circulating Water pumps?
N71-C001A 4160v Bus A
N71-C001B 4160v Bus B
What causes Condenser Room Flooding logic to initiate? What actions happen as a result of this?
3” water above the floor
What is the time delay associated with restarting Circ Water pumps after a trip? What happens when the pump starts?
Pump cannot be restarted until 90s TDR has timed out after pump trip. (Disch valve does not have to be closed to restart pump, just need 90-sec TDR timed out)
When the pump is restarted, the pump discharge valve will OPEN.
What are the T.S. safety limits? What actions are required if they are violated?
If any violated:
2 hr, restore compliance with all SLs
AND
Insert all insertable control rods.
What are the various Modes for Rx operations, and what are the switch/temperature/head bolt requirements of each?
1 - Power Operation - Mode switch: Run - Temp: N/A
2 - Startup - Mode switch: Refuel(a) or Startup/Hot
Standby - Temp: N/A
3 - Hot Shutdown(a) - Mode switch: Shutdown - Temp: > 212
4 - Cold Shutdown(a) - Mode switch: Shutdown - Temp: ≤ 212
5 - Refueling(b) - Mode switch: Shutdown or Refuel - Temp: N/A
(a) - All reactor vessel head closure bolts fully tensioned.
(b) - One or more reactor vessel head closure bolts less than fully tensioned.
What are the requirements for LLS to be armed?
Which valves are LLS valves for Unit 2/Unit 1? When do they open/close to control pressure?
Unit 2: (B)e (G)ood (F)or (D)ad - BGFD
OPEN CLOSE (15,15,9) B 997 851 G 1012 866 F 1027 881 D 1036 890
Unit 1: (H)ave (A) (G)ood (C)hristmas - HAGC
OPEN CLOSE (15,15,10) H 993 847 A 1008 862 G 1023 877 C 1033 887
What are the power supplies for ADS logic “A” and “B”? Which valves on each unit are ADS valves?
ADS Logic “A”
NORM - 125VDC “A” R25-S001
ALT - NONE
ADS Logic “B”
NORM - 125VDC “A” R25-S001
ALT - 125VDC “B” R25-S002
U2: MACK/HEL
U1: KLFD/JEB
What signals are required for ADS to blow down?
DRAW the logic, ADS will not blowdown unless Rx water level is less the -101 (right leg of logic will prevent)
• CS 152#, RHR >127#]
(timer still times w/o this)
What are all of the SRV electrical/mechanical lift setpoints? Which ones have controls at the RSDP? What is lost if control is transferred to RSDP?
SRVs-U2 • B,G,F,D 1120psig • MACK 1130psig • HEL 1140psig • Mech OP 1150psig
SRVs-U1 • H,A,G,C 1120psig • KLFD 1130psig • JEB 1140psig • Mech OP 1150psig
B & F (C & G) have controls on RSDP – LLS logic disabled.