Containment Solutions Fiberglass Storage Tank Installation Instructions and Operating Guidlines Flashcards

1
Q

Can the truck driver delivering a Containment Solutions tank manually unload the tank by himself? (Containment Solutions, Section 2.1)

A

no

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How many of the lifting lugs on a tank must be used when the tank is lifted? (Containment
Solutions, Section 2.3)

A

The number of lugs listed on label adjacent to the lifting lugs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Under what circumstances can a tank be rolled? (Containment Solutions, Section 2.1)

A

For air and soap testing roll only on shipping pads, smooth surface free from thing that could harm tank like rocks or hard objects

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the only materials that can be used to replace all the native soil that has been excavated? (Containment Solutions, Section 3)

A

Specified backfill

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Who should certify that backfill meets all required specifications? (Containment Solutions, Section 3)

A

the suplier should supply written cerification and analysis to installer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the range of particle sizes allowed when gravel is used for a backfill material? When crushed stone is used? (Containment Solutions, Section 3)

A

Pea gravel 3/4 in with no more than 5% passing through a #8 sieve and crushed stone or gravel 1/2 inch with no more than 5% passing through a #8 sieve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the minimum dry gravel density permitted for Containment Solutions tank backfill? (Containment Solutions, Section 3)

A

a mininum of 95lb per cubic foot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the suggested recipe for a soapy water solution to use when soaping the tank in warm weather? (Containment Solutions, Section 4)

A

5 gallons of water 8ozs of household dish soap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When conducting a pre-installation air/soap test in freezing conditions, what is the
suggested recipe for the soap solution? (Containment Solutions, Section 4)

A

4 gallons of wate
8oz househould dish soap
1 gallon window washer fluid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What parts of the tank should be covered with the soap solution? (Containment Solutions, Section 4)

A

For single wall or dry annular tanks entire tank
for tanks with liquid filled annular space cover only accesories and fittings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What must be done if pre-installation testing uncovers a leak in a Containment Solutions tank? (Containment Solutions, Sections 4)

A

Discontinue installation and call field service for repair

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What must be done to fitting plugs prior to pressurizing the tank for the pre-installation air test? (Containment Solutions, Section 4)

A

They must be replaced with plugs compatible with the product stored in the tank

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the maximum test pressure allowed for four foot through 10 foot diameter tanks?
For 12 foot diameter tanks? (Containment Solutions, Section 4)

A

4 -10ft 5psig
12ft 3psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What device is recommended to prevent over-pressurizing the tank? (Containment
Solutions, Section 4)

A

Pressure relief device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How long should the test pressure be maintained? (Containment Solutions, Section 5)

A

30 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How large should the increments be on the air gauge used to monitor the pressure on the
tank? (Containment Solutions, Section 4)

A

Maximum full scale of 15 psig with 1/2 psig or smaller increments

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What parts of the tank should you keep your distance from while the tank is under pressure?
(Containment Solutions, Section 4)

A

endcaps, manways, or fittings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Should a tank be lifted while it is pressurized? (Containment Solutions, Section 4)

A

No lifting or hoisting while pressurized can cause death or serious injury

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Fittings, plugs, and gaskets should be tightened and retested when what are observed?
(Containment Solutions, Section 4.8)

A

Bubbles

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

How many air pressure gauges should be installed to monitor the pressure when testing a double-walled tank with a dry interstitial space? (Containment Solutions, Section 5.3)

A

2 to test manifold
and one to annular space gauge and valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

When pressurizing a double-walled tank with a dry annular space for the pre-installation air/soap test, to which type of tank fitting (primary tank fitting or monitoring fitting) should the hose from the air supply (compressor) be connected? (Containment Solutions,
Section 5.3)

A

Tank testing mainfold connected to the primary tank fitting

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What is the procedure for pressurizing the interstitial space of a double-walled tank with a dry annular space? (Containment Solutions, Section 5.3)

A

with the primary tank pressurized, disconect air supply then open valve between primary tank and annular space to pressurize the annular space using existing pressure, while under pressure soap fittings and manways and inspect, they close valve to annular and open valve to vent primary tank. Maintain pressure on annular space for 30 min for any loss of pressure.soap and watch for bubbles, after testing release pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What is the procedure for detecting leaks in the outer wall of a double-wall tank with a dry annular space? (Containment Solutions, Section 5.3)

A

Soaping and watching for bubbles and watching pressure gauge for drops in pressure

24
Q

Why should you not connect the air supply directly to the annular space monitoring fitting?
(Containment Solutions, Section 5.4)

A

Tank damage will result

25
Q

What should an individual look for when the plug from the reservoir fitting in a
hydrostatically monitored tank is removed? (Containment Solutions, Section 5.5)

A

green monitoring fluid

26
Q

How can a person tell if there is a leak in the outer wall of a hydrostatically monitored tank before it is installed? (Containment Solutions, Section 5.5)

27
Q

For a 12 foot diameter tank, what is the minimum clearance required between tank sides and ends and the banks of the excavation? (Containment Solutions, Section 6.1)

A

the monitoring fluid will leave a green trace on the tank

28
Q

What types of soil are considered to be unstable? How are unstable soils technically defined?
(Containment Solutions, Section 6.2)

A

muck, bog ,peat, quick sand, area with flowing water or landfill
Soil less tahn 750lbs /sq ft cohesion per ASTM D2116, they have a beating capacity of less than 3500lbs/sq ft

29
Q

What is the minimum depth of the backfill bed for a tank in a dry hole? (Containment
Solutions, Section 8)

A

12-24inches

30
Q

When a concrete or asphalt pad is used at grade as part of the tank cover material, how far beyond the tank outline in all directions must the pad extend? (Containment Solutions,
Section 8)

A

At least 12inches beyond tank perimeter in all directions

31
Q

What is the maximum burial depth (measured from the tank top to grade) allowed for a fiberglass tank in both traffic and non-traffic conditions? (Containment Solutions, Section 8)

32
Q

What are two options for meeting the cover requirements of four through 10 foot diameter O/C tanks that do not have mechanical anchoring in non-traffic conditions? (Containment
Solutions, Section 8)

A

24 inches of backfill or 12inches backfill and 4inches reinforced concrete

33
Q

What does filter fabric do? (Containment Solutions, Section 7)

A

Allows for passage of water but prevents migration between backfill and native soil

34
Q

What are four soil conditions where Containment Solutions requires the use of filter fabric?
(Containment Solutions, Section 7)

A

Areas subject to tidal conditions, frequently changing ground water conditons, water conditions with Silty soil, Muck bog peat swap landfill type areas where soil is unstable

35
Q

Why is plastic not considered to be an effective filter fabric material? (Containment
Solutions, Section 7)

A

It may tear or degrade over time

36
Q

What is the purpose of anchoring a tank? (Containment Solutions, Section 9)

A

to prevent property damage and tank failures due to bouyant conditions ( flooding, water tables, and trapped water) and other weather hazards

37
Q

What are two common methods of mechanically anchoring a tank? (Containment Solutions,
Section 9)

A

Deadmen anchors and concrete anchor pad

38
Q

If water is likely to enter the tank hole, but you do not wish to mechanically anchor the tank, what alternative procedure can you use to keep four through 10 foot diameter Containment Solutions tanks from floating? (Containment Solutions, Section 10)

A

Ballasting

39
Q

What type of anchor straps are required for use with Containment Solutions tanks?
(Containment Solutions, Section 9.7)

A

Containment Solutions anchor straps

40
Q

What is the proper distance between anchor points when deadmen are used? When a concrete anchor pad is used? (Containment Solutions, Section 9.7)

A

For deadmen place inside edge of deadmen at tank shadow
For anchor pad position anchor points 6inches from tank shadow

41
Q

How closely must anchor points in concrete pads or deadmen line up with the anchor strap locations on the fiberglass tank? (Containment Solutions, Section 9.7)

42
Q

At what locations on a fiberglass tank must the anchor straps be placed? (Containment
Solutions, Section 9.7)

A

at the designated anchor ribs

43
Q

What dimension of the tank should be measured before and after tightening anchor straps to
see if anchor straps have been over tightened? (Containment Solutions, Section 9.7)

44
Q

What should be the dimensions (length and width) of a concrete anchor pad for an
Containment Solutions tank that is 25 feet long and eight feet in diameter? (Containment
Solutions, Section 9.14)

45
Q

What should be the height and width dimensions of deadmen used to anchor six through
eight foot diameter tanks with a minimum burial depth as specified by the manufacturer?
(Containment Solutions, Section 9.13)

46
Q

What must be done to the first and second 12-inch lifts of backfill placed around a fiberglass
tank? What is the recommended tool for doing this? (Containment Solutions, Section 11.3)

47
Q

At what point in the backfilling process should a tank be filled (ballasted) with water or
product? (Containment Solutions, Section 11.3)

48
Q

What is the minimum bedding thickness for a fiberglass tank installation in a wet hole?
(Containment Solutions, Figure 11-3)

49
Q

Fiberglass tanks must be vented so that the maximum pressure or vacuum in the tank does not exceed _______ psig. (Containment Solutions, Section 14)

50
Q

What must be independent of tank vents? (Containment Solutions, Section 14)

51
Q

If the monitoring cavity (interstitial space) of a double-walled tank is vented, how must this be accomplished? (Containment Solutions, Section 14)

52
Q

What should be installed on the tank and delivery truck if deliveries are to be pumped intoan underground fiberglass tank? (Containment Solutions, Section 15)

53
Q

What will happen to a fiberglass tank if it is overfilled during a pressurized delivery?
(Containment Solutions, Section 15)

54
Q

Is it necessary to vent the interstitial space (monitoring cavity) of a fiberglass tank with a hydrostatic (liquid filled interstitial space) monitoring system? (Containment Solutions,
Section 17)

55
Q

How can the joint between the containment collar and the sump be tested to see if it is liquid tight? (Containment Solutions, Section 18)