Condensers & Cooling Towers Flashcards
Wet bulb is actual temp felt, dry bulb is what’s measured on a __________
thermometer
Cooling towers are heat ______. They do not condense refrigerant so they are not considered condensers
rejecters
Plate Heat Exchanger Condensers:
- ______ capacity design
- not mechanically _______
- also used as ________
smaller, cleanable, evaporators
Fouling (Scaling Resistance)
- Fouling is the build up of ______ on tube surfaces depends on the quality of water
- Lower water velocities result in higher _______ rates
- deposits
2. fouling
Condenser Pass Arrangements:
One pass of tubing = low pressure drop ___ rise
Two pass of tubing = med pressure drop, ____ rise
- low
2. medium
Air Cooled Condensers:
- No condenser water _____ and piping
- Ease of ________
- pump
2. maintenance
Approximate Design Air-Cooled Condensing Temperature:
Design air inlet temp 95F
air rise 15F
leaving difference 15F
what is the refrigerant condensing temp?
125F
Subcooling circuit:
- ensures proper operation of liquid _______ device
- Adds 0.5% to total system _______ per degree of sub cooling
- metering
2. capacity
In air conditioning an air in vs air out is just a range it is NOT a ___
TD
Entering Wet Bulb Temperature:
- entering wet bulb temp is the lowest temp that water can theoretically reach by _________
- entering ___ bulb temp is the most important parameter in tower selection
- For most areas in North ________ an entering wet bulb temp of 78F is common
- evaporation
- wet
- America
Cooling Tower Approach:
- Approach is the difference between the water leaving the tower and the entering wet bulb temp of the ____
- A 7F approach is common in HVAC systems with 78F entering wet bulb and 85F water leaving the _____
(85F - 78F = 7F)
- air
2. tower
Cooling Tower Range:
- Range is the ________in the temp of water entering and leaving the tower
- AN approx 9.4F - 10F range is most common in _____ applications
- difference
2. HVAC
Total Heat of Rejection:
- This is the amount of heat to be ______ from the circulating water within the tower
- It is equal to the refrigeration effect plus the work of _________
- For water-cooled chillers (THR = (1.15 to 1.18) * cooling tons
- removed
2. compression
Drift (Windage)
- Drift water that gets entrained in the airflow and discharged to the _______
- Drift can vary widely and does not include water lost by _________
- drift is very small and can usually be _______ in most calculations for make up
- drift is approx 0.001 to 0.002% of the tower ppm
- atmosphere
- evaporation
- neglected
Evaporation:
- For each pound of water that a cooling tower evaporates, it removes about 1050 btu from the _____ that remains
- A lower entering wet bulb creates a ______ evaporator effect
- Evaporation rate equals approx 1% of tower ___
- water
- greater
- GPM
Blow Down (Bleed Off)
- Water contains impurities and when it is evaporated these _______ are left behind
- If no action is taken the concentration of impurities will build up ______
- Bleeding off some of the water is continuously required to _____ this build up
- impurities
- rapidly
- limit
Makeup:
Make up is the amount of water required to replace normal losses caused by ____, evaporation, and blow-down
drift
Cooling Tower Fill:
- Fill helps the water gain maximum exposure to the ______
- airflow
Induced-draft Crossflow-double inlet
- Air passes through building on side horizontal to water flow
- both
Induced-draft Single inlet:
- Induced draft with crossflow but only __ air inlet
- one
Forced - Draft Blow - Thru
- Fan _____ air through tower
- Uses centrifugal fans with ____ hp and _____ static pressure
- High entrance ______
- Applications would be HVAC ______
- forces
- high, high
- velocity
- hvac chillers
Placement of Cooling Towers:
- When selecting the location, sufficient clearance should be allowed for the ___ flow of air to the inlet of the tower. Insufficient clearance would necessitate a single inlet tower in this application
- Obstructions will reduce airflow causing a reduction in _______
- A 2F recirculation can equal up to a 19% reduction in _____
- free
- capacity
- capacity
Cooling Tower Discharge Concern:
- Avoid placement where air discharge could cause _________ or wetting on nearby surface
- condensation
Where do fluids enter in a centrifugal compressor?
through the centre
Effect of Reduced Cooling Tower Water Temperature:
As a rule of thumb, water-cooled equipment efficiency is increased approximately 2% for every _F decrease in entering condenser water temp
1F
Water Treatment:
Problems a water treatment specialist can prevent: name 4. Acronym is SCSM
- Scaling
- Corrosion
- Sludge
- Micro-biological contamination