Describe the automatic interlocks of CDN-LV-075, Condenser Hotwell Level Control draw-off valve.

A
  • closes automatically on:
    • high cation conductivity in any how well half
    • low MFP suction pressure
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the basis for operating the Hotwell at 41”?

A
  • the condensate pumps may trip on low level (30”) if a heater drain pump trips
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe the operation of VDN-PDIC-195, Condensate Polishing Demineralizer bypass valve.

A
  • reverse acting: 0% output means valve is fully open.
  • auto opens at 55 psid in manual or auto
  • auto opens if either the demon inlet or outlet valves are closed