Condensate Flashcards
1
Q
Describe the automatic interlocks of CDN-LV-075, Condenser Hotwell Level Control draw-off valve.
A
- closes automatically on:
- high cation conductivity in any how well half
- low MFP suction pressure
2
Q
What is the basis for operating the Hotwell at 41”?
A
- the condensate pumps may trip on low level (30”) if a heater drain pump trips
3
Q
Describe the operation of VDN-PDIC-195, Condensate Polishing Demineralizer bypass valve.
A
- reverse acting: 0% output means valve is fully open.
- auto opens at 55 psid in manual or auto
- auto opens if either the demon inlet or outlet valves are closed