Commezbank Zone (Cell) Flashcards

1
Q

Petrol Storage

A

Zone 0 in the headspace of the tank.

Zone 1 extending 1m in all directions from the tank vent.

Zone 2 from the extent of Zone 1 extending downward to the tank surface and in an outward direction to approximately 2m.

Any level indication equipment must be ATEX Certified.

All ATEX Certified equipment must be on a detailed asset list and should be subject to inspections at intervals no longer than 3 years.

Hazardous Area Classification drawings should be produced.

Zone extent diagram required on the outside of the area.

EX signage required on the tanks and surrounding area.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Diesel Storage

A

Zone 1 in the headspace of the tank.

Zone 2 extending 0.5m radius in all directions from the tank vent.

Any level indication equipment must be ATEX Certified.

All ATEX Certified equipment must be on a detailed asset list and should be subject to inspections at intervals no longer than 3 years.

Hazardous Area Classification drawings should be produced.

Zone extent diagram required on the outside of the area.

EX signage required on the tanks and surrounding area.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Storage of Flammable Liquids. Petroleum Store

A

Zone 1 for the entirety of the building

Larger Ex sign required on the main access doors.

New signage required on the rear exit/escape doors.

Hazardous Area Classification drawing required to identify the extent of the zone.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Storage of Flammable Liquids. Chemical Store

A

Zone 2 for the entirety of the Store

Ex sign required on the main access door.

Hazardous Area Classification drawing required to identify the extent of the zone.

ATEX Certified lighting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Storage of Flammable Solvents (Bulk) Solvent Store

A

Zone 2 for the entirety of the Store

Hazardous Area Classification drawing required to identify the extent of the zone.

New EX Signage showing Zone 2, current wording needs changing.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Supply of Natural Gas Main Isolator Points

A

Zone 2 for the entire inside of each enclosure.

Ex Zone 2 signage required on each enclosure.

Hazardous Area Classification drawings should be stored on record in a suitable DSEAR file not inside the enclosures

How well did you know this?
1
Not at all
2
3
4
5
Perfectly