Chief 3 Flashcards
The flame sensing device which uses flame rectification to detect a main burner gas flame senses the alternating current which has been changed from direct currents by the heat of the burner flame
T
When applying a hydrostatic test to a boiler the test pressure must be held for 30 minutes
T
If a boiler operates at a pressure above 400 PSI that boiler must be provided with two water gauge glasses
T
Are siphon or loop is used on a steam gauge to protect it but it is not a requirement of the New York State boiler code
F
Y type globe valves are permitted in horizontal piping but not in vertical piping
F
When the tensile strength of steel shell plates is not known it shall be taken at 55,000 lb per square inch
T
Gate valves are not suitable for throttling with a valve partially open
T
Caustic embrittlement can be defined as a weakening of boiler steel as of result of inner crystalline cracks to the Shell
T
A flame sensing device that is sensitive to ultraviolet light will not sense the red raised emitted from hot refractory
T
A manhole gasket should not be thicker than 1/4 in
T
If a boiler has a maximum working pressure of 135 PSI a proper safety valve would not allow the boiler pressure to exceed 150 psi if the boiler malfunctioned and caused overfiring
F
The minimum size of pipes connecting the water column to the boiler Shall be 3/4-in
F
Hydrostatic test must be conducted with water at a temperature no lower than 70° f
T
The total head of a pump is calculated by adding the suction lift and the suction head
F
The freezing point of a solution used in a brine refrigeration system is about 10° f
F
If the capacity of a 1-in diameter pipe is 100 gallons per hour the capacity of a 5-in diameter pipe is about 500 gallons per hour
F
Asme code requires all boilers to be subjected to a hydrostatic test of the greater of 60 PSI or 1 1/2 times the working pressure
T
A 5-ft length of one and a quarter thin pipe will equal the square foot of EDR of a cast iron radiator whose dimensions are 8 and 3/4 wide 20 in high and 17 and 1/2 in Long
T
Common glass cannot be used in the manufacturer of ultraviolet tubes as glass will screen out the UV energy
T
if a successful accumulation test was conducted on a boiler whose safety valve was set at 50 psi the pressure during the test should never exceed 60 PSI
F
A “tuyere”is found used on certain types of coal-fired boilers
T
Single retort stoker’s are used with either screw feed or ram feed
T