Chapter 7: Maintenance, Testing & Trouble shooting Flashcards
When would you need to go for recertification for CCC?
in 5 years
- membership is renewed every year
a 3 valve differential pressure gauges needs what?
1) 15 psid gauge differential pressure gauge
2) needs to be tested annually
3) Low pressure side hose needs to be needle valves
What does a 5 valve pressure gauge include:
1) low side bleed valve
2) high side bleed valve
3) 2 air bleed valves
What is used to test backflow preventers that have a leaky shut off 1?
Bleed - off valve
What does the sight tube method need? (size of tube)
36” tube –> allows to fill 28” = 1 psi
What size is most common for an adaptor fitting?
1/4”
If a backflow preventer is removed does a jumper wire need to be supplied?
Yes
What is the min psi needed for an acceptable Buffer when testing an RP?
3psi (20.7 kPa)
What is the relief required operating pressure when testing an RP?
2 psi (13.8 kPa)
What is the Air inlet required operating pressure when testing an PVB?
1 psi (6.9 kPa)
How many days do you have to submit your report to AHJ?
30 days
Personnel engaged in testing backflow prevention devices must be?
Adequately trained and certified
How often must certified testers pass a recertification exam?
Every 5 years
An approved differential pressure gauge for testing backflow preventers must read from — psid to — psid and in increments of — psid.
1) 0
2) 15
3) .1 - .2
List 3 accessories which can often be found in testers kits and state what they would be used for.
Bleed off valve: bleed off excess water passing through a leaky
shutoff valve (establishing static conditions)
Water Column Sight Tube: establish a pressure based on a column of water to provide force against check valves or air inlet valves to determine their proper operation, or to bring a low mounted test cock to the highest
point of the assembly
Test Cock Hose Adapter fittings: Allow for connections of the gauge to the test cocks in the event that the adapters on the assembly to be tested have
been removed or damaged
Who has the responsibility to ensure that backflow preventers are maintained in good working condition?
The owner of the building/premise (the owner of the assembly).
Why would a jumper wire be necessary for a bypass when removing a backflow preventer from a water service?
To allow any current-to-ground that may be in existence.
Why is removal of a backflow assembly for testing or repair unnecessary?
Because to gain certification they must be “in-line testable” and serviceable
When are backflow preventers required to be tested?
1) after install
2) Annually
3) Backflow preventer relocated
4) Supply line piping is altered
5) Routine maintenance
6) Backflow repaired
7) Backflows installed prior to CCC program
8) AHJ requested
9) Detector type backflow preventer (RPDA or DVDA)
What 2 things is a tester required to fill out after performing a test and whose responsibility is it to pay for testing / repairs or maintenance?
The tester is required to fill out the Testing and Inspection Report (sent to the CCCP administrator) and the test tag (affixed to the unit tested). The
owner of the device is responsible for the costs of testing, overhaul and
maintenance.