Chapter 5 - General Backflow Preventer install Requirements Flashcards

1
Q

Complete the following statement “all backflow preventers shall be installed…”

A

in a readily accessible location a/ adequate space to facilitate maintenance + testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

As a general rule, How much space should be provided for backflow preventers?

A

Above: 12”
In front: 30”
Behind: 3/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the max centerline height that any in-line testable backflow preventer may be installed above the flow or a permanent fixed platform?

A

Anything above 60” (5’)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Why is an RP the only in-line testable assembly which has a requirement for clearance below the device?

A

In order the the RV to be accessible for maintenance or repair

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

All backflow preventers w/ an air inlet, air vent or relief valve port are not permitted to be installed where?

A

Below the level in a pit, vault or trench –> vulnerable to flooding

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What can be done if a backflow preventer needs to be installed in a waterline containing temps which exceed the manufacturer’s recommended max temps?

A

Get a higher rated backflow preventer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If a backflow preventer is installed on the upstream side of a hot water tank, what may have to be considered?

A

Thermal expansion tank or thermal expansion RV

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What can be installed on the piping downstream of an RP to lessen the effects of water hammer?

A

Water hammer arresters
Surge protectors
-slowly opening or closing any valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What should be done to the waterline prior to installing any backflow preventer?

A

Flush the lines –> decreases damages to internal compounds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What procedure must be take if a strainer is to be installed upstream of a backflow preventer or a fire system?

A

Must be approved by AHJ or insurance underwriters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Installations that require uninterrupted 24 - hour service require what to be installed?

A

Parallel installations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Can you have a bypass line w/ a lower level of protection or smaller size installed around a backflow preventer for use during testing / maintenance of the primary backflow preventer?

A

No , should be the same size / combined capacity to maintain the flow rate of the service pipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13