Chapter 5 - General Backflow Preventer install Requirements Flashcards
Complete the following statement “all backflow preventers shall be installed…”
in a readily accessible location a/ adequate space to facilitate maintenance + testing
As a general rule, How much space should be provided for backflow preventers?
Above: 12”
In front: 30”
Behind: 3/4”
What is the max centerline height that any in-line testable backflow preventer may be installed above the flow or a permanent fixed platform?
Anything above 60” (5’)
Why is an RP the only in-line testable assembly which has a requirement for clearance below the device?
In order the the RV to be accessible for maintenance or repair
All backflow preventers w/ an air inlet, air vent or relief valve port are not permitted to be installed where?
Below the level in a pit, vault or trench –> vulnerable to flooding
What can be done if a backflow preventer needs to be installed in a waterline containing temps which exceed the manufacturer’s recommended max temps?
Get a higher rated backflow preventer
If a backflow preventer is installed on the upstream side of a hot water tank, what may have to be considered?
Thermal expansion tank or thermal expansion RV
What can be installed on the piping downstream of an RP to lessen the effects of water hammer?
Water hammer arresters
Surge protectors
-slowly opening or closing any valve
What should be done to the waterline prior to installing any backflow preventer?
Flush the lines –> decreases damages to internal compounds
What procedure must be take if a strainer is to be installed upstream of a backflow preventer or a fire system?
Must be approved by AHJ or insurance underwriters
Installations that require uninterrupted 24 - hour service require what to be installed?
Parallel installations
Can you have a bypass line w/ a lower level of protection or smaller size installed around a backflow preventer for use during testing / maintenance of the primary backflow preventer?
No , should be the same size / combined capacity to maintain the flow rate of the service pipe