Chapter 7 - Combustion Stability Flashcards

1
Q

What turndown ratio and port loading will a stable combustion system have?

A

It will have 6:1 turndown at least and be able to operate at port loadings of 10,000

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is turndown ratio

A

ratio of the maximum gas flow rate to minimum gas flow rate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Define port velocity

A

average velocity of the fuel/gas mix as it flows through and leaves the gas burner ports (ft/s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is port velocity a function of (what affects it?)

A

total port area
gas input rate
port loading
fuel/air ratio

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Define flame speed

A

speed of a burning flame front as it moves through a combustible gas/air mixture (ft/s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What affects flame speed?

A

varies with mixture temperature
fuel/air ratio
how well the fuel and air are mixed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

what is combustion stability

A
Describe by what it's not: It's not
flashback
lifting
shutdown pop
candling
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

what is flashback

A

flashback happens when the flame front moves through the burner ports and establishes itself at the exhaust face of the orifice.
happens when the flame speed in the combustible air/gas mix exceeds the port velocity of the air/gas mix exiting the burner ports

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

what is flashback an indicator of

A

lack of burner port stability

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

what is lifting

A

when 3 or more adjacent flame kernels on a gas burner lift and move away from the normal flame stabilization point
port velocity of air/gas mix is higher than the flame speed of the gas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is lifting an indicator of

A

lack of gas burner port stability

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

what is shutdown pop

A

slight explosion or “pop” that occurs during the shutdown transient on some gas burners or combustion systems
Instantaneous ignition of all the air/gas mixture that remains in the gas burner tube

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What causes shutdown pop

A

the flow of the air/gas mixture through the burner ports decreases as a result of the closing of the main gas valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is candling

A

small flame that burns right at the exit of the orifice immediately after shutdown
Is undesirable but not destructive to the appliance or humans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If the mixture velocity is greater than the flame speed which way will the flame front move?

A

In the direction of the mixture velocity

towards the fire

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

if the mixture velocity is less than the flame speed which way will the flame front move?

A

in the direction opposite the mixture velocity

towards the gas

17
Q

What are the 5 stabilization positions that occur frequently?

A
Lifting
soft
normal
hard
flashback
18
Q

What is port loading

A

parameter: gas input rate/total burner port area

[BTU/hr]/[in^2] = [BTU/hr in^2]

19
Q

What can port loading be used for

A

Estimating gas burner port sizes and number of ports
resolving field problems
understand if burners are over or under loaded
comparing burners to each other
general indication of port stability

20
Q

what is the dead zone

A

distance between the burner port and the bottom of the flame kernel (air gap)

21
Q

how does the dead zone compare to the port loading

A

proportional to the port loading

smaller dead zone - smaller port loading

22
Q

How does the dead zone affect the quality of burn

A

More dead zone indicates less primary aeration than with a smaller dead zone. Greater chance for impingement and dirty combustions

23
Q

Explain L/d ratio

A

L is the length of the burner port
d is the diameter of the gas burner port
L/d ratio spans from 1 to 10

24
Q

Ideal L/d ratio

A

Large L/d Ratios (6 and above) indicate stable burner ports

2 and less indicate potential lack of stability

25
Q

What do large L/d ratios indicate

A

gas burner will be resistant to flashback and shutdown pop

has a higher pressure drop across the gas burner ports

26
Q

What do low L/d ratios indicate

A

poor resistance to flashback and shutdown pop

27
Q

Design benefits of large L/d ratios

A

Can operate at lower port loadings
Can operate at higher primary aeration rates
Cleaner combustions
Higher turndown ratios
Increased resistance to flashback, shutdown pop and resonance
Reduced chance of candling
Increased efficiency

28
Q

What is quench diameter

A

largest diameter burner ports can have and still resist flashback

29
Q

What is quench diameter a function of

A

the gas type being used

30
Q

How is quench diameter affected by flame speed

A

Fuels with faster flame speeds will have smaller quench diameters