Chapter 6 Basic Fittings for Hot Water Boilers Flashcards
1
Q
1.The temperature of the water in a hot water heating system with an open expansion tank is normally limited to: A. 150°C (302°F) B. 121°C (250°F) C. 99°C (210°F) D. 80°C (175°F) E. 60°C (140°F)
A
D. 80°C (175°F)
2
Q
2. The minimum size of the hot water heating boiler bottom blow off or drain connection shall be: A. 6 mm (¼ in.) B. 15 mm (½ in.) C. 19 mm (¾ in.) D. 25 mm (1 in.) E. 75 mm (3 in.)
A
C. 19 mm (¾ in.)
3
Q
3.The relief valve on hot water boilers with a working pressure of up to 414 kPa (60 psi) should open with in a variation of \_\_\_\_\_ below or above the setpoint. A. 10 kPa (1.5 psi) B. 5% C. 30 kPa (4.5 psi) D. 14% E. 20 kPa (3 psi)
A
E. 20 kPa (3 psi)
4
Q
4.The automatic fill valve is a \_\_\_\_\_ valve which keeps the system filled with water and maintains a set pressure in the system. A. Pressure reducing valve B. Air vent valve C. Back pressure valve D. Pressure control valve E. Temperature control valve
A
A. Pressure reducing valve
5
Q
5. When hot water boiler stop valves are over 51 mm (2 in.) it is recommended that \_\_\_\_\_ be used. A. OS & Y valves with rising spindles B. Gate valves C. Globe valves D. Diaphragm operated valves E. Solenoid operated valves
A
A. OS & Y valves with rising spindles
6
Q
6. The discharge piping from the relief valve should be piped to a safe point for disposal and can be: A. Connected to any drain B. Connected to any vent C. Connected to the deaerator D. Terminated above a floor drain E. Connected to the condensate tank
A
D. Terminated above a floor drain
7
Q
7.The highest pressure to which the scale on the pressure gauge of a hot water boiler may be graduated is \_\_\_\_\_ times the pressure at which the pressure relief valve is set. A. 1.5 B. 2 C. 2.5 D. 3 E. 3.5
A
E. 3.5
8
Q
- The purpose of the “expansion tank in a hot water” heating system is to:
A. Provide storage space for excess steam
B. Separate the water and steam produced
C. Provide space to store the returning condensate
D. Add make-up water to the system
E. Provide storage space for excess water
A
E. Provide storage space for “excess water”
9
Q
- The operating handle of the valve to the pressure gage on a hot water boiler must be of the:
A. Hand wheel type
B. Tee or lever handle design
C. Diaphragm type
D. Solenoid type
E. A valve is not permitted in this location
A
B. Tee or lever handle design
10
Q
10.The pressure relief valve is typically installed on the boiler or reasonably close to the boiler outlet with: A. A globe valve for isolation B. A gate valve for isolation C. No valve between D. A ball valve for isolation E. A plug valve for isolation
A
C. No valve between
11
Q
11.On a hot water boiler, the highest value on the graduated scale of the pressure gauge shall not be less than \_\_\_\_\_ times the pressure at which the pressure relief valve is set. A. 1.5 B. 2 C. 2.5 D. 3 E. 3.5
A
A. 1.5
12
Q
12.The wax filled sensor probe in a combination pressure-temperature relief valve will expand and open the valve by means of a piston at approximately: A. 50°C (122°F) B. 110°C (230°F) C. 99°C (210°F) D. 134°C (273°F) E. 60°C (140°F)
A
C. 99°C (210°F)
13
Q
Answer Chapter 6 Basic Fittings for Hot Water Boilers
- D
- C
- E
- A
- A
- D
- E
- E
- B
- C
- A
- C
A