What is not required as part of a water heater installation?
a means to provide continous circulation
There is provision in the code for continuos circulation
What is required to be installed in the cold water line feeding a bottom feeded water heater?
Vacuum relief valve
504.2
Unless the tanks working pressure is less, What is maximum pressure settings for a T&P valve?
150PSI
504.5
What is the minimum required level working space on the control side of a water heater?
30” x 30”
502.5
The maximum temperture setting of a T & P relief valve?
210 degrees
504.5
A storage tank-type water heater is required to be installed in a pan when?
installed in an attic
504.7 amended
The drain pipe of a water heater pan shall not be less than?
3/4 “
504.7.1
The relieving capacity of a temperature relief valve shall not be less than ?
heat input of the heater
504.5
Galvanized steel drainpans for water heater must fabricated of not less than what gauge metal?
24
504.7
The maximum allowable water temperature from a tankless-type water heater intended for domestic use is?
140 degree
501.6
What is the minimum access opening for water heaters installed in attics?
20” x 30”
502.3
An electric water heater requires what safety feature that a gas water heater doen’t?
A means of disconnecting the power supply
504.3
What are the requirements for a water heater pan size?
1 1/2” deep & large enough to catch all the drippings & condensate from the heater
Temperture relief valves shall be so located in what part of the water heater?
In the top 6” of the tank
504.4.1
A water heater shall be located not more than how many feet from the attic access?
20 feet
502.3